System Grounding - Sharp SRS Mounting System Installation Manual

Solar power system, rectangular modules
Table of Contents

Advertisement

6
IN S TAL L AT IO N WO Rk

6.8 SySTEM gROuNdINg

SRS utilizes single point integrated grounding. Use a minimum #10 AWG ground wire for this purpose. The equipment
SRS utilizes rail to rail integrated
grounding conductor will continue down to the DC disconnect, inverter and AC service equipment.
SINGLE POINT INTEGRATED GROUNDING
EXPLODED VIEW OF RAIL GROUNDING
Minimum #10
bare copper
ground wire
Use # 10 x 1" stainless steel machine screw,
lock washer and nut.
Continuous equipment grounding of modules
and mounting system is provided by the Module
Mounting Clips.
Mounting Clips, Rails, and Splices.
Ensure that every sub array is grounded and that
during replacement or repair, removal of the last
module breaks the ground path.
This can be achieved by installing grounding hardware
This can be achieved by installing grounding
on either end of bottom rails.
hardware on one end of each row of rails.
1. Install outdoor rated ground lugs or ring terminals
with ground wire (per above drawings). Use the
marked ground hole on either end of the rail.
2. Connect a minimum # 10 AWG solid conductor
copper, ground wire to the ground lug or ring
terminal.
3. Connect the end of the equipment grounding
conductor in the array junction box
4. Connect the equipment grounding conductor
to the DC disconnect, inverter, and AC service
equipment.
5. Connect the ground wire from the inverter to a
grounding electrode.
Stainless steel nut
Stainless steel lock washer
Outdoor rated
tin plated copper
ground lug
ILSCO GBL4-DBT
(or equivalent)
Stainless steel set screw
Stainless steel screw
Solar array
Existing
AC service
equipment
AC grounding
Unspliced 6 AWG conductor serves as
Existing
1. AC equipment grounding conductor
electrode
2. DC grounding electrode conductor
 1