17
Daylight Sensor Inputs
Navigate to DayX menu
Press Menu, inpX menu is displayed.
Press Enter, the occX menu is displayed.
Press Up to scroll to the dayX menu.
Note: The user can press the Input button at this time to switch to an daylight input on a different input
bank. The menu will advance from day1 to day2, thru to day4.
Set Input Polarity
Press Enter at the dayX menu, the Polarity list control is displayed.
Press Enter for polarity options list.
Use the Up and Down buttons to display options in the list. The current
programmed option will be displayed first:
Hi – active high (10V reorts max. light), sourcing*
Lo – active low (0V reports max. light), sinking* (default)
Press Sel to choose the displayed option. The apostrophe LED will be lit for the current selected option.
Press Store button to record the new setting.
*Note: Dip switch SW1-x must also be set to ON for active low, OFF for active high.
Assign a Zone to Daylight Sensor Input
Press Enter at the dayX menu, the Polarity list control is displayed.
Press the Up button to scroll to the zone list control.
Press Enter to show the first item in the zone list.
Use the Up and Down buttons to scroll thru the list of available zones:
Zon1-4* – 4 circuit panel
Zon1-8* – 8 circuit panel
Press Sel to assign or un-assign the displayed zone. The apostrophe LED will be lit for each assigned
zone. Press Store button to record the new zone assignments.
*Note: Only one sensor per zone, you must un-assign a zone(s) from one daylight input before assigning
to another daylight input. The list will contain available zones.
Secondary Daylight Zone Adjustment
See Control/Test section on Control menu item DASC, page 31.