Senlan SB200 Series User Manual page 125

High performance general space verctor control
Table of Contents

Advertisement

F8-36
Trial Working frequency
Setting
1.00~F0-07"Upper Limit Frequency"
Range
F8-37
Pump Trial Operation
111
operation
Setting
Range
331~335
operation at a variable frequency
F8-38
Pump Trial Operation Timekeeping
Setting
0.5~3000.0s
Range
Pump Trial Operation: This parameter is used for system debugging and is effective only when
F8--00 ≠ 0 and the pump is shut down. Set Parameter F8-37, enter the command and you will
enter the testing status. If the variable-frequency circulator pump is subject to line frequency trial
operation, the pump will be directly switched to line frequency. For a variable-frequency
circulator pump, variable frequency/line frequency trial operation can be conducted to confirm if
the rotation direction is uniform. If a line frequency operation is required, you must confirm that
the rotation directions of line-frequency operation and variable-frequency operation are uniform.
Pump
F8-39
Sequence
Units digit: Shutdown sequence (applicable only to auxiliary pumps)
0: First to be started and first to be shut
down
Tens digit: Startup sequence (Circulator Pumps 0~5 startup/shutdown options)
0: Pumps to be first started will be selected via the control terminal
Setting
1: Pump #1 is the first to be started
Range
2: Pump #2 is the first to be started
3: Pump #3 is the first to be started
4: Pump #4 is the first to be started
5: Pump #5 is the first to be started
6: Pumps involving a relatively long startup/shutdown time
Shutdown Sequence: The shutdown sequence applies to auxiliary pumps only. The startup
before shutdown mode applies primarily to pumps with different capacity.
Startup Sequence: If "0" is selected, the control terminal will select the first pump to be started.
Settings of external terminals include 55 "Priority Pump Startup Option 1", 56 "Priority Pump
Startup Option 2" and 57 "Priority Pump Startup Option 3". See the description of terminal
functions on Page 55.
Sleeping pump in trial
Pumps #1~#5 in trial
Startup/Shutdown
Details about Function Parameters
Factory
25.00
Settings
Hz
Factory
000
Settings
222
Drainage pump in trial operation
441~445
Pumps #1~#5 in trial operation
at a line frequency
Factory
20.0s
Settings
Factory
10
Settings
1: First to be started and last to be shut down
Modification
Modification
×
Modification
Modification
×
121