7 iGEM Software Downloads - IEC version

7
iGEM Software Downloads - IEC version
Follow the procedure below to upload pump code.
1 Connect laptop via a Null Modem Cable to J26 on computer board.
2 Set SW2 and SW3 over to the right position.
3 Press and hold the RESET button and press and hold the BOOT button.
4 Release the RESET button, and after 2 seconds release the BOOT button.
5 Start servTerm on the PC.
6 Select the correct COM port.
7 Select TTL connection.
8 Press the BOOT button.
9 A new window will show the text "Entering GEM boot strap".
10 Select the new program bin file.
11 The program will upload to GEM.
12 Press the COLD button.
*If this process is now interrupted for any reason, the Bootstrap procedure must then be used
to download to the dispenser, therefore, do not run other programs or perform other actions on
the desktop. See Bootstrap Procedure on the following page.
Also refer to the iGEM Function Programming manual WM048525 IEC version for details on
iGEM functions and statistics.
166
WM048523
Rev 08
01/2019