8 Creation of the PDM Network Structure for the Maintenance Project
9. Add the other devices/modules following the procedure in steps 7 to 8.
Enter:
the PROFIBUS address of the PROFIBUS device.
the IP address of the PROFINET device.
the port for modules of a PROFIBUS DP or PROFINET Station.
the channel number for HART field devices.
the PA bus address for PA field devices.
Figure 8-16
8.3.2

PROFINET Network Directly via Switch/Service Bridge [B2]

No data record gateway is required here.
The connected PROFINET devices and stations can be inserted directly below the
PROFINET segment. Description in Chapter for steps 8 and 9.
8.3.3

PROFIBUS Network via IE/PB Link [A2]

If you connect the PDM MS via an IE/PB Link to an external system—without an
S7 CPU with a PROFIBUS DP network—the network components must be
configured manually.
1. Right-click the PROFINET network and select "Insert new object > Object" from
the context menu.
The "Insert Object" window opens.
2. In the "Insert Object" window, click "Assign Device Type..." and select the
corresponding IE/PB Link type, e.g. "Devices > S7 DSGW > Network
Components > Siemens AG > IE/PB Link V3.0".
PDM Maintenance Station
Entry ID: 109776936,
V1.0,
02/2020
55