Fan Coil Unit Wind-Free Cassette for Global
(Water, 50/60Hz)
Model : AG***TN1DKH(1Way Cassette)

Advertisement

Table of Contents
loading

Summary of Contents for Samsung AG TN1DKH Series

  • Page 1 Technical Data Book Fan Coil Unit Wind-Free Cassette for Global (Water, 50/60Hz) Model : AG***TN1DKH(1Way Cassette)
  • Page 2 History Version Modification Date Remark Release FCU Wind-Free 1Way Cassette for Global TDB 20.07.21 Ver.1.0 Ver.1.1 Updated the Appendix : Capacity Table pages 21.05.14...
  • Page 3 Nomenclature Indoor Unit Model Name Buyer (1) Classification (5) Product Notation Chiller / FAN COIL UNIT 1 Way Cassette 4 Way Cassette (600x600) 4 Way Cassette, 360 Cassette LSP Duct (2) Capacity MSP Duct Ceiling X 1/10 kW (3 digits) Console RAC (with EEV) RAC (without EEV)
  • Page 4 Features & Benefits Simply fits into a small ceiling space. Efficiently cools with no cold wind. Create a comfortably cool environment in every corner. The Sam- sung 1Way Cassette air conditioner’s Wind-Free Cooling cools ™ effectively without the unpleasant feeling of cold wind being blown directly onto your skin.
  • Page 5: Table Of Contents

    Contents 1. Line-up 2. Specification 3. Summary Table 4. Dimensional Drawing 5. Center of Gravity 6. Electrical Wiring Diagram 7. Sound Data 8. Temperature and Airflow Distribution 9. Piping Diagram 10. Installation ※ Appendix : Capacity Table...
  • Page 6: Line-Up

    1. Line-up Fan Coil Unit (kW) Model Type Image Wind Free 1Way Cassette...
  • Page 7: Specification

    2. Specification Wind Free 1Way Cassette Model AG026TN1DKH/EU AG032TN1DKH/EU AG042TN1DKH/EU Power Supply Φ, #, V, Hz 1,2,220~240,50/60 1,2,220~240,50/60 1,2,220~240,50/60 Mode Cooling 2.60 3.00 4.15 Performance Capacity (Nominal) Heating 2.90 3.35 5.00 Cooling 27.0 35.0 55.0 Power Input (Nominal) Heating 27.0 35.0 55.0 Power...
  • Page 8 2. Specification Wind Free 1Way Cassette Model AG026TN1DKH/TK AG032TN1DKH/TK AG042TN1DKH/TK Power Supply Φ, #, V, Hz 1,2,220~240,50/60 1,2,220~240,50/60 1,2,220~240,50/60 Mode Cooling 2.60 3.00 4.15 Performance Capacity (Nominal) Heating 2.90 3.35 5.00 Cooling 27.0 35.0 55.0 Power Input (Nominal) Heating 27.0 35.0 55.0 Power...
  • Page 9 2. Specification Wind Free 1Way Cassette Model AG026TN1DKH/TS AG032TN1DKH/TS AG042TN1DKH/TS Power Supply Φ, #, V, Hz 1,2,220~240,50/60 1,2,220~240,50/60 1,2,220~240,50/60 Mode Cooling 2.60 3.00 4.15 Performance Capacity (Nominal) Heating 2.90 3.35 5.00 Cooling 27.0 35.0 55.0 Power Input (Nominal) Heating 27.0 35.0 55.0 Power...
  • Page 10 2. Specification Wind Free 1Way Cassette NOTE • Cooling : Indoor temperature 27°C DB, 19°C WB / Water In/Out temperature 7°C, 12°C Heating : Indoor temperature 20°C DB, 15°C WB / Water In/Out temperature 45°C, 40°C • Sound level was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
  • Page 11: Summary Table

    3. Summary Table 3. Summary Table Fan Coil Unit Capacity (kW) Airflow Sound Sound Model Pressure Level Power Level Cooling Sensible Heating Fan Speed [dBA] [dBA] High AG026TN1DKH/EU High AG032TN1DKH/EU 14.6 High 4.15 12.6 AG042TN1DKH/EU 10.7 High AG026TN1DKH/TK High Wind Free AG032TN1DKH/TK 1Way Cassette 14.6...
  • Page 12 3. Summary Table Fan Coil Unit Electrical Characteristics Power Power Supply Current Model Input MCA (A) MFA (A) FLA (A) (Φ, #, V, Hz) Input (A) 0.14 0.14 AG026TN1DKH/EU AG032TN1DKH/EU 0.19 0.19 AG042TN1DKH/EU 0.29 0.29 Wind 0.14 0.14 AG026TN1DKH/TK Free 1, 2, 220~240, 50/60 0.19 0.19...
  • Page 13: Dimensional Drawing

    4. Dimensional Drawing 4. Dimensional Drawing Wind Free 1Way Cassette AG026/032TN1DKH/** 단위 : mm [inch] Name Description Water pipe connection out PF Male 3/4" (20A) Water pipe connection in PF Male 3/4" (20A) Air vent valve Drain hose VP20 (OD26, ID20) Power supply &...
  • Page 14 4. Dimensional Drawing Wind Free 1Way Cassette AG042TN1DKH/** 단위 : mm [inch] Name Description Water pipe connection out PF Male 3/4" (20A) Water pipe connection in PF Male 3/4" (20A) Air vent valve Drain hose VP25 (OD32, ID25) Power supply & Communication wiring conduit Air discharge part Air suction part...
  • Page 15: Center Of Gravity

    5. Center of Gravity Wind Free 1Way Cassette Units : mm [inches] AG026TN1DKH/**, AG032TN1DKH/** AG042TN1DKH/** 1410 [ 4' 7 ½"] 1198 [47-3/16] 175 [6-3/4] Model AG026TN1DKH/** 555 [21-7/8] 220 [8-5/8] 108 [4-1/4] AG032TN1DKH/** 555 [21-7/8] 220 [8-5/8] 108 [4-1/4] AG042TN1DKH/** 755 [29-5/8] 200 [7-7/8] 108 [4-1/4]...
  • Page 16: Electrical Wiring Diagram

    EEPROM EEPROM Sub PBA LOUVER Up/Down, Left/Right Blade EVA-OUT Thermistor (Eva-Out) 25’C at 10Kohm M (BLDC) BLDC Motor (Indoor Fan) Samsung Plasma Ion ROOM Thermistor (Air) 25’C at 10Kohm DISPLAY LED Lamp Display 250V T2.5A FUSE NOTE • This wiring diagram applies only to the Fan Coil Unit.
  • Page 17: Sound Data

    7. Sound Data Wind Free 1Way Cassette Sound Pressure level Unit: dB(A) Model HIGH AG026TN1DKH/** AG032TN1DKH/** AG042TN1DKH/** • NR Curve 2) AG032TN1DKH/** 1) AG026TN1DKH/** 3) AG042TN1DKH/** NOTE • Specifications may be subject to change without prior notice. • Sound Pressure Level - Sound pressure level is obtained in an anechoic room.
  • Page 18 7. Sound Data Wind Free 1Way Cassette Sound Power level NOTE Unit: dB(A) • Specifications may be subject to change without prior notice. Model Cooling - Sound power level is an absolute value that a sound source AG026TN1DKH/** generates AG032TN1DKH/** - dBA = A weighted sound power level - Reference power : 1pW AG042TN1DKH/**...
  • Page 19: Temperature And Airflow Distribution

    8. Temperature and Airflow Distribution Wind Free 1Way Cassette • AG026TN1DKH/** Discharge angle : 60 Cooling Air Velocity distribution Cooling temperature distribution Heating Air Velocity distribution Heating temperature distribution • AG032TN1DKH/** Discharge angle : 60 Cooling Air Velocity distribution Cooling temperature distribution Heating Air Velocity distribution Heating temperature distribution...
  • Page 20 8. Temperature and Airflow Distribution Wind Free 1Way Cassette • AG042TN1DKH/** Discharge angle : 60 Cooling Air Velocity distribution Cooling temperature distribution Heating Air Velocity distribution Heating temperature distribution...
  • Page 21: Piping Diagram

    9. Piping Diagram Thermistor - IDU Heat Exchanger In (T_II) Water In Thermistor Heat Exchanger - Indoor Room - Indoor unit (T_IR) (HX_ID) Indoor Fan Motor Thermistor (IFM) - IDU Heat Exchanger Out (T_IO) Water Out Water Flow Cooling/Heating Units : mm (Inches) Water pipe Medel AG026TN1DKH/**...
  • Page 22: Installation

    10. Installation Choosing the installation location Installing the fan coil unit Preparations for installation Installation location requirements The piping that will be connected to the fan coil unit must • Air must be distributed optimally. be completed before installation. • The passage of air must not be disturbed. 1 Check the product to install and its installation •...
  • Page 23 10. Installation Installing on a new ceiling 4 Secure a total of 8 nuts and washers to each suspension bolt. However, leave a little space between 1 Place the pattern sheet on the ceiling at the spot the nuts into which the hanger bracket of the fan coil where you want to install the fan coil unit.
  • Page 24 10. Installation Connecting the water pipes When the installation template is made of paper 1 Purge inert gas. (Unit: mm) • The fan coil unit comes with nitrogen gas (inert Slim 1 way cassette (Small, Wind-free panel) gas) charged at the factory for protection of the unit during transportation.
  • Page 25 10. Installation Installing the water pipes Air vent valve Installation site area 2-way 1 Remove the caps from the w ater pipe inlet and outlet. electric valve Loose nut (PF 3/4") Loose nut (PF 3/4") Air vent valve Ceiling Flexible tube CAUTION (water pipe outlet) •...
  • Page 26 10. Installation 5 Manage water quality in accordance with the following Slim 1 way cassette AG026/032TN1DKH* water quality standards for refrigeration equipment: Slim 1 way cassette AG042TN1DKH* CAUTION • If water quality is not managed in accordance with Connecting the drain hose the water quality standards, corrosion and scales may develop, which may shorten the life of the product and •...
  • Page 27 10. Installation 4 Fully insulate the drain pipe inside the building (on site). Individual drainage If the drain pipe is sloped insufficiently, install the drain Use a leveler to check that the fan coil unit is parallel to pipe vertically from the hose connection port (on site). the ceiling.
  • Page 28 10. Installation Slim 1 way cassette 1000 to 1500 mm Air vent of the fan coil unit 200 mm or less Full thread bolt hanger 300 mm or less 20 mm or more 550 mm or less Horizontal drain pipe (transverse pipe) More than 1/100 slope Flexible hose Ceiling...
  • Page 29 10. Installation Connecting the power and communication cables 1 Power and communication cable connection CAUTION • Before wiring work, you must turn off all power source. • The circuit diagram given above shows only wiring schematic, and the details of the actual installation are •...
  • Page 30 10. Installation 3 Specifications of the terminal blocks Wiring diagram when connecting a 2-way valve (Unit: mm) AC power: Communication: Communication: M4 screw M3 screw M3.5 screwELB 6.62 7.62 CAUTION • When installing the product, be sure to install a 2-way 1-NO 1-NC 2-NO 2-NC electric valve on the water inlet pipe.
  • Page 31 10. Installation • Depending on the 05 series installation options (SEG15 and SEG22), the contact output signals are as follows: SEG22: 0 (Cooling/Heating synchronizing signal) SEG22: 1 (Cooling/Heating signal separated) SEG15: 0 SEG15: 1 SEG15: 0 SEG15: 1 Common Optional Cooling Heating Operation...
  • Page 32 10. Installation Installation example Total power cable length L = 100 [m], initial pull-in current i = 10 [A], running current of each unit = 1 [A], total 10 fan coil units are installed. 10 [A] 9 [A] 1 [A] MCCB Fan coil unit Fan coil unit...
  • Page 33: Appendix : Capacity Table

    ※ Appendix : Capacity Table Wind Free 1Way Cassette (AG026TN1DKH/**) ※ Total Capacity : Total cooling capacity (kW) / Sensible : Sensible cooling capacity (kW) Cooling Water Flow : Water flow rate (ℓ/min) / ΔP : Water in-out pressure drop (kPa) Air temperature 24-17 (DB℃...
  • Page 34 ※ Appendix : Capacity Table Wind Free 1Way Cassette (AG032TN1DKH/**) ※ Total Capacity : Total cooling capacity (kW) / Sensible : Sensible cooling capacity (kW) Cooling Water Flow : Water flow rate (ℓ/min) / ΔP : Water in-out pressure drop (kPa) Air temperature 24-17 (DB℃...
  • Page 35 ※ Appendix : Capacity Table Wind Free 1Way Cassette (AG042TN1DKH/**) ※ Total Capacity : Total cooling capacity (kW) / Sensible : Sensible cooling capacity (kW) Cooling Water Flow : Water flow rate (ℓ/min) / ΔP : Water in-out pressure drop (kPa) Air temperature 24-17 (DB℃...
  • Page 36 2021.05 Ver.1.1 Samsung Electronics Co., LTD. Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677 Website : www.samsung.com, https://partnerhub.samsung.com Email : airconditioner@samsung.com Images and data in this book may subject to change without prior notice.