Page 28
MULTI Flaring Procedure One of the main causes of refrigerant leaks is a defective connection. For LG HVAC systems, the installer needs to know how perform flared connections successfully. • During installation, it is imperative to keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust.
Page 33
3. When all piping installation has been completed, perform the triple leak / pressure and evacuation tests (see the Final Installation Proce- dures Section in the Multi F / Multi F MAX Outdoor Unit Installation Manual), verify that the system does not have any leaks, and then fully insulate all joints / connections.
Page 38
Ensure all refrigerant piping is insulated. Exposed refrigerant piping will cause burns if touched. Wrap all refrigerant and condensate piping including field-provided isolation ball valves and flexible pipe connection kits provided by LG. All pipes must be insulated and each pipe must be separately wrapped. Any exposed piping will generate condensate or will cause burns if touched.
Page 41
Do not include splices or wire nuts in the communication cable. • Multi F and Multi F MAX with LGRED systems operate at 1Ø, 208-230V, 60Hz, and power is wired to the outdoor unit only. The outdoor unit will supply power to the indoor units and the branch distribution units (Multi F MAX with LGRED systems only) through the communication / connection (power) cable (indoor units and branch distribution units draw minimum power).
Page 43
Power (1[L1]) and Neutral (2[L2]) Cable at Least Two (2) Inches for Each Indoor Unit. Outdoor and Indoor Unit appearances may vary depending on the model. Figure 66: Schematic of a Multi F MAX with LGRED System When the Wiring is GREATER THAN 130 Feet. At Least Two (2) Inches...
Page 44
After all wiring is connected to the indoor and outdoor units, test the accompanying remote controllers for performance. As always, follow all safety warnings and notes when operating the units using the remote controller. Additionally, all of the Multi F / Multi F MAX outdoor units can use the following controllers when accompanied with the PI 485 VNet Accessory: •...
Page 54
(4) to five (5) feet above the finished floor. • It could be necessary to use a handy box that is sized in metric units, depending on the sensor model. Check with your LG representative to verify which size of handy box is needed for the sensor in question.
Page 61
Pipe insulation was not compressed at any point. Y-branch fittings were properly INSTALLED per details provided in the Multi F / Multi F MAX with LGRED Outdoor Unit Installation Manual. Y-branch fittings were properly SUPPORTED per details provided in the Multi F / Multi F MAX with LGRED Outdoor Unit Installa- tion Manual.
Page 62
The power supplied was clean with voltage fluctuations within specifications. (±10% of nameplate). Power wiring to the Multi F / Multi F MAX with LGRED outdoor unit was field supplied, solid or stranded, and installed per all local, state, and NEC requirements.
Page 63
Who to call for assistance Freight Damage and Unit Replacements Your LG Manufacturer Representative Missing Parts Your LG Manufacturer Representative Freight Damage and Unit Replacements Your LG Manufacturer Representative Received Wrong Indoor Unit Model Your LG Manufacturer Representative Installation, Startup, and Commissioning Technical Assistance 1-888-865-3026 For warranty information, visit www.lghvac.com.
Page 64
20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Customer Information Center, Commercial Products 1-888-865-3026 USA LG Electronics, U.S.A., Inc. Follow the prompts for commercial A/C products and parts. Air Conditioning Technologies 4300 North Point Parkway IM_MultiF_StdWallMount_9HVT_HSV5_11_18 Alpharetta, Georgia 30022 Supersedes: IM_MultiF_StdWallMount_11_15 www.lghvac.com...