Page 1
AMIAD WATER SYSTEMS EBS-10,000 IN-LINE FILTER Serial number: Order number: Catalogue number: Filtration degree: Tested by: Installation, Operation and Maintenance Instructions 910101-000109 / 09.17 EBS 10000 IL 910101-000109 / 09.17 Page 1 of 24...
Page 2
This document does not replace any certified drawing, procedure or information provided by Amiad in reference to a specific customer, site or project. Amiad assumes that all users understand risks involved within this file and/or its attached materials. This document is given in good faith and is not intended to impose any obligation to Amiad.
TECHNICAL SPECIFICATIONS General Maximum flow rate 800m 3500USgpm Consult manufacturer for optimum flow depending on filtration degree & water quality. Min. Operating pressure 2.5bar 35psi Or lower if pressure is increased for flushing Max. Operating pressure 10bar 150psi 16bar (240psi) upon request Filter area 10,000cm 1550in...
➢ Always observe standard safety instructions and good engineering practices whilst working in the filter’s vicinity. ➢ Use the filter only for its intended use as designed by Amiad, any misuse of the filter may lead to undesired damage and may affect your warranty coverage.
Page 6
Operation procedures exactly as described in this manual. ➢ Commissioning the filter should be done by an authorized Amiad technician, do not attempt to commission the filter unaccompanied since this may lead to undesired damage and may affect your warranty coverage.
Page 7
Maintenance Before any maintenance or non-regular operation please read the following: ➢ Servicing the filter should be done only by technicians authorized by Amiad. ➢ Disconnect the filter from the power supply and lock the Main Power Switch. ➢ Disconnect the compressed air supply, release the residual pressure and lock the Pneumatics Main Valve.
DESCRIPTION OF FILTER OPERATION Filtering process: The EBS is a sophisticated yet easy-to-operate automatic filter, with a self-cleaning mechanism driven by an electric motor. The EBS is designed to work with various types of screens in filtration degrees from 500 to 10 micron, and is available in 8", 10", 12" and 14" inlet/outlet diameter.
INSTALLATION Design recommendations If flow increases and pressure drops dramatically for a long period of time during network filling-up, it is recommended that a pressure sustaining valve is installed downstream of the filter. The pressure sustaining valve will ensure a controlled filling-up of the line.
the cable. (It is recommended that this installation meets or exceeds local or national electrical codes, this is a "high" voltage connection). Control wiring: The connection between the control junction box and the control board should be by 6 x 1.5 mm 2 (16 AWG) wire in flex- conduct.
MAINTENANCE Before beginning any maintenance procedure, carefully read the safety instructions in chapter 2 of this document and make sure that all the workers at the filtration site are fully aware of and comply with, these and any other local safety instructions. General inspection of the filter operation This is the visual basic general inspection procedure of the filter for proper operation.
Page 13
Maintenance prior to re-operation Make sure that the filter is disconnected from power, compressed air and water supply. Grease the drive shaft and the drive bushing. Connect the control board to the mains. Connect the compressed air supply. Connect the filter to its water supply. Perform a General Inspection of the Filter Operation as described above.
TROUBLESHOOTING Before beginning any troubleshooting, carefully read the safety instructions in chapter 2 of this document and make sure that all the workers at the filtration site are fully aware of and comply with, these and any other local safety instructions. The filtration system may enter a malfunction mode in the following cases: Symptom Remarks and Actions...
DISMANTLING AND ASSEMBLING THE FILTER COMPONENTS Opening the filter and disassembling its inner components is necessary for changing screens, periodic maintenance and repairs. Prior to opening the filter it is recommended to initiate a flushing cycle by pressing the "TEST" push button. Before beginning any maintenance procedure, carefully read the safety instructions in chapter 2 of this document and make sure that all the workers at the filtration site are fully aware of and comply with, these and any other local safety instructions.
Page 16
Please note that the screen is heavy and in order to avoid damage and injury it should be lifted only with Amiad’s standard Extractor and a standard lifting device operated by an authorized operator.
Page 17
Reassembling the "EBS" filter: Before reassembling, visually check that all components are complete and in good mechanical condition. Before reassembling, carefully read the safety instructions in chapter 2 of this document and make sure that all the workers at the filtration site are fully aware of and comply with, these and any other local safety instructions.
Distributor may not return the Defective Product unless such return was coordinate and approved by Amiad in advance. Amiad's obligation under this warranty shall be limited to, at its option, the repair or exchange, free of charge, of the Product or any part which may prove defective under normal use and service during the Warranty Period.