STAND ALONE INSTALLATION
If installing this furnace as a stand alone unit, ensure all local codes and all instructions in this manual are followed,
including clearance to combustibles, floor protector specifications and safety warnings.
PARALLEL FURNACE INSTALLATION
To install the new furnace in parallel with an existing furnace follow the instructions for series installation with a
few additional requirements listed below.
• The return air will duct directly to the return of the new furnace, and not be pulling through any other
furnace.
• The output of the existing furnace must be equal to or greater than this wood furnace.
• If installing in a parallel configuration the ductwork may need adjustments so as to maintain the static
pressure between 0.2" W.C. And 0.05" W.C.
• A back flow damper must be installed in the supply duct work of the new furnace, to ensure that air does
not circulate back through the wood furnace.
• Some installation configurations may require dampers to be installed in the supply duct work of both
furnaces.