Fail-Safe Material Level (Failsafe Mat. Le) (2.4.2.); Fail-Safe Level (2.4.4.); Diagnostics (3.); Echo Profile (3.1.) - Siemens SITRANS LR260 Operating Instructions Manual

Radar transmitters ma/hart
Hide thumbs Also See for SITRANS LR260:
Table of Contents

Advertisement

Note
The last valid reading is maintained until the Fail-safe timer expires. After the timer expires, the
reading is set based on Fail-safe Material Level.
8.5.49

Fail-safe Material Level (FAILSAFE MAT. LE) (2.4.2.)

8.5.50

Fail-safe Level (2.4.4.)

Defines a user-defined level to report when the Fail-safe timer expires.
Note
This value can be used only if Fail-safe Material Level is set to VALUE.
8.6

Diagnostics (3.)

8.6.1

Echo Profile (3.1.)

Allows you to request the current echo profile either via the handheld programmer, or via
SIMATIC PDM. (For more detail see Echo Processing (Page 151).)
To request a profile via SIMATIC PDM:
1. Open the menu View – Echo Profile.
2. If desired, press Save.
3. To view the saved profile, open the menu View – Show Echo Profile.
SITRANS LR260 with mA/HART
Operating Instructions, 11/2019, A5E32337683-AD
Options
*
Values
Range: 3.6 mA to 22.6 mA
Default: 22.6 mA
HI: Use 22.6 mA (max. mA Limit) as material level
LO: Use 3.6 mA (min. mA Limit) as material level
HOLD: Level remains at last reading
VALUE: User-selected value (defined in Fail-safe Level)
Parameter reference
8.6 Diagnostics (3.)
95