Procedures for maintenance and repair
Procedure no. 9
Calibration of Ø160/Ø50 hydraulic cylinders.
Calibrations of Balluff transducer BTL7-E100-Mxxx-B-S32 using teach in mode.
 
Description of calibration step
LED indicators
Picture of step
by step
4. Set end point
Bring the hydraulic cylinder
piston to new end point
Right LED is off and left LED
is red
Press button 2 for at least 2
seconds
Both LED flashes green in
alternation
5.1 Exit teach-in and
deactivate buttons
Press both buttons in, hold
for at least 6 seconds
The left LED flashes green
5.2 Exit teach-in and
deactivate buttons
Press button 1 or 2 shortly
under 1 second
The left LED is green
The buttons are now
deactivated
Note: If this step is not carried
out, the automatic deactivation
will become active after 10
minutes where the buttons are
inactive