Page 2
Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death. mrcool.com...
OUTDOOR UNIT 3. Piping Diagrams Applicable for 18k, 24k, 30k, 36k cooling only type Fig. 3-1 Applicable for 18k, 24k, 30k, 36k cooling & heating type Fig. 3-2 mrcool.com | Page 4...
Page 7
OUTDOOR UNIT Applicable for 42k, 48k, 60k cooling only type Fig. 3-3 Applicable for 42k, 48k, 60k cooling & heating type Fig. 3-4 mrcool.com | Page 5...
2. Replacement wire must be the same gauge and insulation type as original wire. 3. The units should install the stated-cross-section ground wire and keep it grounding properly and reliably. 4. For indoor transformer, the current of 24V load voltage is not less than 1.5A. mrcool.com | Page 6...
(18K, 24K, 30K, and 36K units only) to shorten the restart time. In the case of high and low pressure imbalance, a booster can increase the starting torque of the compressor allowing it to start normally. mrcool.com | Page 8...
Installation and Insulation Drainage Pipe Installation Drainage Pipe Installation And Insulation And Insulation Vacuum Drying and Leakage Check Additional Refrigerant Charge Insulate the joint and connections of the refrigerant pipe Wiring connection and electrical safety check Test operation mrcool.com | Page 9...
• If a protective structure is built over the unit to prevent direct sunlight, rain exposure, direct strong wind, snow, or the accumulation of other types of debris, make sure the heat that radiates from the condenser is not restricted. Fig 8-1 mrcool.com | Page 10...
Fig.9-2 and install the unit in a level position. Normal operating sound levels may be undesirable if the unit is placed directly under windows of certain rooms (bedrooms, study, etc.). The top of unit discharge area must be unrestricted for a minimum 6 feet above the unit. mrcool.com | Page 11...
Page 14
When installing units on a roof, the structure must be capable of supporting the total weight of the unit. This also includes any framing of the unit, rails, etc., which should be used to minimize the transmission of sound or vibration into the conditioned space. mrcool.com | Page 12...
Always use a pressure regulator and safety valve to ensure that only low pressure dry nitrogen is introduced into the tubing. Only a small amount of flow is necessary to displace air and prevent oxidation. mrcool.com | Page 13...
Page 16
After brazing, cool the joint with a wet rag. •The valve can be opened by removing the plunger cap, and then fully insert a hex wrench into the stem turning counter-clockwise until the valve stem just touches the chamfered retaining wall. Fig. 10-2 mrcool.com | Page 14...
3. Install period is taking an extended amount of time, rain water or moisture could penetrate into the pipeline. NOTE: Be sure to use a micron gauge during vacuuming that can hold under 800 microns. Pull down to 500 microns. mrcool.com | Page 15...
Multiply the length of the liquid pipe and the empirical coefficient (the coefficient is determined by the pipe diameter) to verify the correct charge. mrcool.com | Page 16...
• Insulate the joint parts Purpose of drainage pipe insulation The temperature of condensate drainage water is very low. However, if insulation is insufficient, it could cause condensate to form and cause leakage which could lead to property damage. mrcool.com | Page 17...
• Wiring of varying voltage should not be in one wire tube. • Ensure that the color of the wires of the outdoor unit and the terminal No. are same as those of indoor unit respectively. Electric Wiring Guage Table - 6 mrcool.com | Page 18...
Outdoor Unit: Is there any vibration or abnormal noise during operation? Does the generated wind, noise, or condensation created by the air conditioner have any negative influence on the surrounding area? Has any of the refrigerant leaked? mrcool.com | Page 20...
OUTDOOR UNIT 16. Troubleshooting System Alarm: Green light or Yellow light slowly flashes System lock: Green Turn off power for 10-15 light goes minutes and then out and restart. Yellow light is on mrcool.com | Page 21...
Page 24
Well connected, then replace sensor and PCB the sensor or PCB Sensor is open circuit? Error Check the sensor is good or Replace the bad sensor Sensor is short circuit? not? Error Check PCB Component damaged? Replace PCB Wet? mrcool.com | Page 22...
Page 25
Discharge the refrigerant & vacuum, There is N or air in the system then recharge the refrigerant Error Too much refrigerant in the system Discharge some refrigerant Error Check the switch and PCB Replace the switch and PCB mrcool.com | Page 23...
Page 26
Discharge the refrigerant & vacuum, There is N or air in the system then recharge the refrigerant Error Check if the low pressure is too slow Clean the system to remove contaminants Error Check the Pcb Replace the Pcb mrcool.com | Page 24...
Page 27
PRODIRECT™ Series Split System Heat Pump & Air Conditioner 13 -14 SEER 1.5-5 Tons Model HHP140* & HAC140* The design and specifications of this product and/or manual are subject to change without prior notice. Consult with the sales agency or manufacturer for details.
Need help?
Do you have a question about the PRODIRECT Series and is the answer not in the manual?
Questions and answers