Advertisement

Terminal layout

Do not connect to the "×" terminals, or the relay may not operate properly.
Drawing out and housing operation of subunit (Unit-drawer type)
For unit-drawer type (RD type), it is possible to draw
out the subunit from the case without removing external
wiring, which makes easier to carry out inspection and
testing.
When drawing out and housing, be careful not to touch the
electrical
circuit
(e.g.
transformer) and be sure to hold the drawer handle or the
frame part when transporting. (Touching the electrical
circuit may cause electric shock or damage to the
circuit.)
Subunit
Cover (Transparent)
Drawer fixing
screw
P1
M
Y1
P2
N
Y2
9
9
9
Fig. 2-7 Terminal layout
substrate,
capacitor,
Fig. 2-8 Structures of unit-drawer type (RD type)
Z1
×
a11
a12
Z2
E
a21
a22
9
9
9
MDG-A3V-R/RD
Before the subunit is to be drawn out, ensure that the
following items are checked in order not to carry out the
work in hot-line condition.
・ Lock of the tripping circuit
・ Turning off the main circuit
and
・ Disconnect CT/VT circuit
・ Turning off the auxiliary power supply
The CT circuit is equipped with an automatic short circuit
piece so that the CT secondary circuit won't be opened
even
if
the
disconnecting the CT circuit.
18
14
relay
subunit
is
drawn
Connector of case
Connector of subunit
(Back side)
Drawer handle
(Back side)
out
without
JEP0-IL9554