V-HFD Fixed-Temperature Heat Detector
Installation Sheet
EN FR
EN: Installation Sheet
Operation
The V-HFD Fixed-Temperature Heat Detector is an intelligent
analog device that contains a 135°F (57°C) fixed-temperature
heat sensor to detect heat from fire. The heat sensor monitors
the temperature of the air in its surroundings and determines
whether to initiate an alarm. The detector is capable of
performing comprehensive self-diagnostics and storing the
results.
LED operation
The detector provides a bicolor LED that shows its status.
Normal: Green LED flashes
Alarm/active: Red LED flashes
Electronic addressing
The control panel automatically assigns addresses to the
detectors. Use a laptop computer to address custom
addresses to the detectors. No addressing switches are used.
Installation
Refer to Smoke and Heat Detector Application Bulletin
(P/N 3101109) for additional information on detector placement
and spacing.
WARNINGS
This detector does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
This detector does not sense fires in areas where smoke
cannot reach the detector. Smoke from fires in walls,
roofs, or on the opposite side of closed doors may not
reach the detector.
This detector is intended for use with ionization and/or
photoelectric smoke detectors. The heat detector by itself
does not provide life safety protection.
© 2013 UTC Fire & Security. All rights reserved.
This detector does not detect oxygen levels, smoke, toxic
gases, or flames. Use this device only as part of a broad-
based, life-safety program which includes a variety of
information sources pertaining to heat and smoke levels,
extinguishment systems, visual and audible devices, and
other safety measures.
Independent studies recommend using heat detectors only
for property protection. Never rely on heat detectors as the
sole means of fire protection.
To ensure proper operation, schedule maintenance
(regular or selected) in accordance with the requirements
of the authority having jurisdiction. Refer to NFPA 72 and
CAN/ULC−S536.
To ensure proper operation, store the detector within the
recommended ranges. Allow the detector to stabilize to
room temperature before applying power.
Keep the dust cover (supplied) on the detector during
installation and remove it prior to commissioning and
service. The dust cover is not a substitute for removing the
detector during new construction or heavy remodeling.
To install the detector:
1.
Install and wire the detector base using the installation
sheet supplied with the detector base.
2.
Connect the detector to the base by rotating the detector
clockwise until it snaps into the locked position.
The head can be removed by turning it counterclockwise.
3.
If the head must lock to the base, break away the locking
tab using a pair of pliers. See Figure 1.
To then remove the detector head after breaking away the
locking tab, insert a small screwdriver into the slot on the
side of the base and press in while simultaneously turning
the detector head counterclockwise.
4.
Log the serial number on the appropriate worksheet.
1 / 4
P/N 3101072 • REV 04 • REB 24JAN13

Advertisement

loading
Need help?

Need help?

Do you have a question about the V-HFD and is the answer not in the manual?

Questions and answers

Summary of Contents for Vigilant V-HFD

  • Page 1 Operation other safety measures. The V-HFD Fixed-Temperature Heat Detector is an intelligent • Independent studies recommend using heat detectors only analog device that contains a 135°F (57°C) fixed-temperature for property protection.
  • Page 2 Fonctionnement To test the detector: Le détecteur de la chaleur de la fixe-température, V-HFD est un appareil analogique intelligent qui comporte un capteur de Before initial testing, remove the dust cover from the chaleur fixe de 57°C (135°F) capable de détecter la chaleur detector and notify the proper authorities that the fire dégagée par un incendie.
  • Page 3 • Le détecteur ne localisera pas d’incendies qui débutent Figure 1 : Languette d’écartement dans les endroits où la chaleur ne peut l’atteindre. Il se peut que la chaleur provenant de foyers d’incendie dans les murs, sur les toits ou du côté opposé de portes fermées ne puisse pas atteindre le détecteur.
  • Page 4 Répond : UL-521, CAN/ULC-S530-M91 américaines Suivez : NFPA-72 et CAN/ULC-S524 [1] Pour la garantie et le retour voir “Coordonnées”. Coordonnées Pour obtenir nos coordonnées, consultez le site Web www.vigilant-fire.com. 4 / 4 P/N 3101072 • REV 04 • REB 24JAN13...