6300 OPERATING MANUAL
6. 6 DISABLE OUTPUTS
Select 'YES' and press 'ACCEPT' to disable all outputs.
The disablement LED will be lit and the buzzer will sound.
To mute the buzzer, exit all menus and press 'ACCEPT'.
Note: On a networked system, the disable outputs menu only applies to the specific panel used. It is not global.
6. 7 LAMP TEST
Press 'ACCEPT' to initiate the Lamp Test.
All indications and the buzzer will operate for approximately 3 seconds.
The LCD is tested by filling in every dot in the character display one line at a time as follows: -
LCD TEST LINE1
The reverse of the above will then be displayed. That is, the bottom line of the LCD will be 'filled', with the
top line displaying text.
Note: On a networked system, the lamp test menu only applies to the specific panel used. It is not global.
6.8 WALK TEST
This option is only available in the 'user' menu if the panel has been programmed to display it by the
commissioning engineer. If this option is available, it will be in the 'Advanced Options' menu.
The 'Walk Test' function performs an automatic silence and reset five seconds after a fire is triggered from a
device in test. A specific Zone can be set to be in test.
Note: On a networked system, the Zone in test is panel specific. A fire from another panel with the same
zone number WILL trigger the fire alarm.
The outputs affected during Walk Test mode will have been pre-programmed during commissioning as 'No
Control Outputs' activated or 'No Outputs Activated'.
Find the 'WALK TEST?' option from the 'Advanced Options' menu using 'NEXT/PREVIOUS' buttons.
WALK TEST: OFF_
Select a zone to be put into test. On the right of the selection the following message appears
'USE ACCEPT TO START'. On pressing 'ACCEPT' the message will change to 'NOW IN WALK TEST'.
Use the 'MENU' button to return to the 'Advanced Options' menu.
The test is terminated by selecting 'OFF', the panel will perform an automatic reset and lamp test and the
TEST indication will be extinguished. It will then return to the 'Advanced Options' menu.
Note: On a networked system, the test fires are not sent across the network. They are panel specific.