Summary of Contents for Franklin Fueling Systems EVO 600

  • Page 1 600 AND EVO 6000 AUTOMATIC TANK GAUGES INSTALLATION GUIDE...
  • Page 2 Copyright © 2020 Franklin Fueling Systems, LLC, Madison, WI 53718. All world rights reserved. No part of this publication may be stored in a retrieval system, transmitted, or reproduced in any way, including, but not limited to, photocopy, photograph, magnetic, or other record, without the prior written permission of Franklin Fueling Systems.
  • Page 3: Table Of Contents

    Contents Introduction ............................1 Questions and concerns ........................1 Conventions used in this manual ....................1 Operating precautions ........................2 Installation............................3 Standard installation materials ......................3 Circuit Breaker ..........................3 Cable or Wire for TSP/FMP-XXX Sensors ..................3 Cable or wire for FMP-ULS(UHS) sensors ................3 Cables required for liquid level probes and FMP-XXX-U sensors ..........3 Required wire ..........................4 Thread sealant (UL classified) .....................4 Riser pipes ...........................4...
  • Page 4 Intrinsically Safe Wiring ........................23 Vapor Flow Meter ............................24 Probe Module (PRB) ........................24 Supported devices ........................25 2-Wire Sensor Module (2WSNS) ....................26 3-Wire Sensor Module (3WSNS) ....................27 Supported devices ........................28 4-20mA Analog Input Module (420IB) ..................29 RS-485 Module (FMP-485IS Module) ....................30 Control Drawing 1 ..........................31 Control Drawing 2 ..........................32...
  • Page 5: Introduction

    Introduction This manual contains installation instructions for the Franklin Fueling Systems (FFS) 600 and EVO 6000 Automatic Tank Gauges (ATGs). Read this entire manual and follow all safety information, warnings, and other information carefully. If you do not, the result could be faulty operation, equipment damage, injury, or death.
  • Page 6: Operating Precautions

    Operating precautions FFS equipment is designed to be installed in areas where volatile liquids such as gasoline and diesel fuel are present. Working in such a hazardous environment presents a risk of severe injury or death if you do not follow standard industry practices and the instructions in this manual. Before you work with or install the equipment covered in this manual, or any related equipment, read this entire manual, particularly the following precautions: IMPORTANT: To help prevent spillage from an underground storage tank, make sure the delivery...
  • Page 7: Installation

    Installation Standard installation materials Recommended standard materials should be selected and installed per all applicable local, state and federal codes governing the installation of this product and its associated systems. Please see the corresponding console/module wiring section or the associated devices section of this manual for complete installation details.
  • Page 8: Required Wire

    Belden™ Cable Outer Diameter (OD) Maximum Length Capacitance (pF) Inductance (µH) 87760 0.15" (3.7 mm) 260' (80 m) <100 pF/ft ( <330 pF/m) <0.2 µH/ft (<0.7 µH/m) 87761* 0.12' (2.9 mm) 400' (120 m) <60 pF/ft (<200 pF/ft) <0.2 µH/ft (<0.7 µH/m) 89182* 0.31' (7.8 mm) 1500' (450 m)
  • Page 9: Splice Connector Kits

    Splice Connector Kits Use FFS-approved, moisture-resistant, no-strip splice connectors for liquid level probe and leak detection sensor wires. (Order either TSP-KW30INSERT or FMP-CON30. Both kits contain 30 of these connectors.) Using moisture-resistant splice connectors: • Reduces or eliminates corrosion of the wire connections from repeated exposure to water condensation, which causes eventual signal loss and system failure.
  • Page 10 11.1 " (282 mm) " (229 mm) 8.25" (210 mm) Optional LCD Display LED INDICATOR LIGHTS 11.7 " (297 mm) OPTIONAL PRINTER MOUNTING TABS 4 PLCS 6000 17" (432 mm) 9" (229 mm) 14.2" (361 mm) 11.7" (297 mm)
  • Page 11 expansion console (EVO-EXPC) 16.5" 8" (419 mm) (203 mm) 14.2" (361 mm) 11.1" 12.1" (307 mm) (282 mm) Front view Side view expansion console 2 (EVO-EXPC2) 10.5" 8" (267 mm) (203 mm) 8.2" (208 mm) 11.1" 12.1" (307 mm) (282 mm) Side view Front view...
  • Page 12: Communication Ports

    Communication ports The EVO 600 and EVO 6000 consoles have several communication ports that can be used to talk to various devices. The communication ports can be used for a wide variety of applications: to connect the console to a computer network, to print reports on an external printer or to fax reports via the optional internal fax/modem.
  • Page 13: Wiring The Console And Modules

    Wiring the console and modules Conduit must only enter the console enclosure through the designated knockouts as shown below. When installing additional modules, FFS recommends installing non-IS modules from left to right (from the open slot closest to the power supply) and IS modules from right to left. In this scenario, all unused slots will be concentrated in the middle of the enclosure, which lets the IS barrier be easily moved and allows for the possibility of adding future modules to the system without needing to rewire those devices already in place.
  • Page 14 Controller Module (CM) Power Supply Module (PS) Isolation barrier Non-IS modules IS modules (red) (blue) 6000 (Front view with cover removed) NOTE:Isolation barriers can be moved if it does not interfere with the conduit knockouts."...
  • Page 15: Non-Intrinsically Safe Wiring

    Non-Intrinsically Safe Wiring WARNING: Always lock out and tag electrical circuit breakers while installing or servicing this equipment and any related equipment. A potentially lethal electrical shock hazard and the possibility of an explosion or fire from a spark can result if the electrical circuit breakers are accidentally turned on during installation or servicing.
  • Page 16 Power Supply Module (PS) The PS is a non-intrinsically safe module that provides power to the console from line voltage rated 110 - 240 VAC. The PS is two inches wide, occupies two slots and is located immediately to the right of the CM. The PS consists of two AC/DC switching power supplies - one switching power supply is +5V and the other is +24V.
  • Page 17: Line Power Wiring

    Line power wiring At the electrical power panel, use or install a 20 amp circuit breaker. This breaker should be dedicated to supplying power to only the EVO 600 and EVO 6000. Mark this circuit “EVO or EVO 6000 console power ONLY” on the circuit label (at the back of the electrical power panel door).
  • Page 18: 110/240 Vac Line Power Wire Connections

    110/240 VAC line power wire connections Electrical Panel No. Conductors, Color (Gauge) Circuit 20 Amp Circuit Breaker 1 Black wire, 14 AWG (2.5 mm²) min. 110/240 VAC Power Neutral 1 White Wire, 14 AWG (2.5 mm²) min. Neutral Ground Bus 1 Green wire, 14 AWG (2.5 mm²) min.
  • Page 19: Ac Input Module (Aci)

    AC Input Module (ACI) The ACI is a non-intrinsically safe module that has 12 identical optically isolated AC input channels that can be used for dispenser hook isolation, vapor processor input, or as generic AC inputs. Your console can handle a total of 36 AC inputs, up to three AC Input Modules in one system, or 72 AC Inputs an expansion console and six AC Input Modules.
  • Page 20: Relay Module (Rly)

    Relay Module (RLY) The RLY is a non-intrinsically safe module with 8 identical Form C output channels. Each channel has three terminals and a field-replaceable, 3A, 250V, fast-acting fuse. Each channel can be configured as NO or NC with the power off by wiring to the appropriate terminals. The EVO and EVO 6000 console can accommodate up to 24 outputs (8 outputs on up to 3 modules) or up to 48 outputs with an expansion console.
  • Page 21 NOTE: If a dispenser’s current rating is between 2 and 10 amps, use a 10 Amp Relay Module. Refer to the 10 Amp Relay Module section for details. The EVO 600 and EVO 6000 consoles are limited to a total of three relay modules, regardless of the amperage rating and a total of six modules with an expansion console.
  • Page 22: Input/Output Module (Io)

    Input/Output Module (IO) The Low Voltage Input/Output Module is a non-intrinsically safe module that provides eight separate AC or DC voltage inputs that can range from 3 to 240 volts. In addition to the AC/DC inputs, the IO module also includes four 4-20 mA signal outputs. The AC/DC inputs are NOT dry contact inputs (there are 2 dry contact inputs on the power supply).
  • Page 23 IO Module SCADA System – (optional) – – – Chan Chan Chan Chan Chan Chan Chan Generic Device Line Chan Neutral (optional) NOTE: Connected devices are not powered by the IO Module. The eight channels shown in the diagram above are only inputs. The four terminals at the top are 4-20 mA outputs.
  • Page 24: Amp Relay Module (10Arly)

    10 Amp Relay Module (10ARLY) The 10 Amp Relay Module is a non-intrinsically safe module that has 6 identical Form C output channels. Each channel has a fuse and three terminals. Each channel can be configured as NO or NC with the power off by wiring to the appropriate terminals. EVO 600 and EVO 6000 consoles can accommodate up to 18 outputs (6 outputs on up to 3 modules) or up to 36 outputs with an...
  • Page 25 10ARLY Module Switching Current 10A Max. Switching Power 1500 VA Max. 110/240 VAC Electrical Panel Line Neutral DISPENSER 1 10 Amp Relay Module Line disables power to the dispenser upon alarm Neutral conditions. NOTE: If a dispenser’s current rating is higher than 10 Amps, use an appropriate extension relay. NOTE: The line from the dispenser must be connected to NO1 programmed as inverted, if the setup on the console is intended to shut the dispenser down when alarm conditions occur via conditions (California Vapor Recovery).
  • Page 26: 4-20Ma Exp Analog Input Module (420Exp)

    4-20mA EXP Analog Input Module (420EXP) The 420EXP has 8 identical channels for loop powered non-IS sensors with a 4-20 mA interface. 600 and EVO 6000 consoles can support up to 24 inputs (3 modules total including 420IB models with 8 inputs each) and up to 48 inputs with an expansion console, depending on available space in your console.
  • Page 27: Intrinsically Safe Wiring

    Intrinsically Safe Wiring DANGER: Always lock out and tag electrical circuit breakers while installing or servicing this equipment and any related equipment. A potentially lethal electrical shock hazard and the possibility of an explosion or fire from a spark can result if the electrical circuit breakers are accidentally turned on during installation or servicing.
  • Page 28: Vapor Flow

    Probe Module (PRB) The Probe Module (PRB) gathers data from LL2 and LL3 probes, UDP sensors (FMP-XXX-U), DMS sensors, and Vapor Flow Meters. Each PRB can accommodate 12 devices and the EVO 600 and 6000 supports a total of 36 inputs (3 modules with 12 inputs each) or 72 inputs with an expansion console.
  • Page 29: Supported Devices

    Supported devices Model Description FMP-LL3-XXX Digital leak detection and inventory probes of various lengths v. 3 TSP-LL2-XXX Leak detection and inventory probes of various lengths FMP-LL3-XXX-I Digital inventory control probes of various lengths v. 3 TSP-LL2-XXX-I Inventory control probes of various lengths TSP-DMS Discriminating Magnetorestrictive Sensor FMP-DDS-U...
  • Page 30: 2-Wire Sensor Module (2Wsns)

    2-Wire Sensor Module (2WSNS) The 2-Wire Sensor Module (2WSNS) is designed to accept up to 12 sensor inputs per module, and the system as a whole can accept a total of 36 sensors (3 modules with 12 inputs each). The 2WSNS only supports standard sensors, and does not accept inputs from BRITESENSORs®. The 2WSNS Sensor Module can also support devices defined as Simple Apparatus.
  • Page 31: 3-Wire Sensor Module (3Wsns)

    3-Wire Sensor Module (3WSNS) This sensor module is designed to accept up to 8 sensor inputs per module, and the system as a whole can accept up to a total of 24 sensors (3 modules with 8 inputs each) and up to 48 sensors with an expansion console.
  • Page 32: Supported Devices

    Supported devices Model Description FMP-EIS Electo-optical Interstitial liquid-Standard sensor FMP-ULS Universal Liquid - Standard sensor FMP-ULS-15 High product Level, 15" - Standard sensor FMP-HLS-30 High product Level, 30" - Standard sensor FMP-HIS Hydrostric Interstitial reservoir - BRITESENSOR® FMP-HIS-XL Hydrostric Interstitial reservoir, extralong - BRITESENSOR® FMP-DIS Discriminating Interstitial liquid - BRITESENSOR®...
  • Page 33: 4-20Ma Analog Input Module (420Ib)

    4-20mA Analog Input Module (420IB) The 4-20mA Input Module has 8 identical channels for loop powered IS sensors with a 4-20 mA interface. EVO 600 and EVO 6000 consoles can support up to 24 inputs (3 modules with 8 inputs each) and up to 48 inputs with an expansion console, depending on available space in your console.
  • Page 34: Rs-485 Module (Fmp-485Is Module)

    RS-485 Module (FMP-485IS Module) The RS-485 Module is an intrinsically safe module that can connect up to four independent Mulitplexing Sensor Hubs (MSH). The communication to the MSHs is via RS-485 protocol. All connections to this module must maintain intrinsically safe protocols. Entity Parameters Uo, V 10.71...