CWFL-800/1000/1500 Series Contents <1> Cautions ---------------------------------------------------------------- <2> Contour and parts introduction ---------------------------------- <3> Installation -------------------------------------------------------------- <4> Operation and parameters adjustment ----------------------- <5> Flow adjustment in high temperature segment ---------- <6> Flow alarm and output ports ------------------------------------- <7> Specifications -------------------------------------------------------- <8> Simple troubleshooting...
Page 3
CWFL-800/1000/1500 Series Thank using machine from GUANGZHOU TEYU ELECTROMECHANICAL CO., LTD. Please read the installation instructions carefully before installing and operating and keep it properly. This installation instructions is not a quality assurance. GUANGZHOU TEYU ELECTROMECHANICAL CO., LTD reserves the right to the interpretation of correction of typographical errors, improper mentioned information and product improvement.
CWFL-800/1000/1500 Series <2> Contour and parts introduction HIGH TEMP LOW TEMP POWER SWITCH WATER PRESSURE GAUGE AIR OUTLET WATER INLET (L) WATER OUTLET (L) AIR INLET (FILTER GAUZE) WATER OUTLET (H) WATER SUPPLY INLET WATER INLET (H) WATER LEVEL GAUGE...
6. Adjust parameters of temperature controller. CWFL-800/1000/1500 series use an intelligent thermostat. Normally users do not need to adjust the parameters. If it is necessary, please refer to page 6,...
Page 6
CWFL-800/1000/1500 Series <4> Operation status and parameters adjustment The new T506 intelligent temperature controller does not need to adjust the controlling parameters under normal circumstance. It will self-adjust controlling parameters according to room temperature for meeting equipment cooling requirements. The new T506H intelligent temperature controller is selected constant temperature control mode as factory setting with water temperature at 25 ℃...
Page 7
CWFL-800/1000/1500 Series (4). RST key: confirm (5). SET key: setting function 2. Restore to factory settings Before machine startup, press and hold keys until the controller displays rE, 6 seconds later after releasing the keys, the controller works in normal order. All parameters values settings of the controller have been restored to factory settings.
Page 8
CWFL-800/1000/1500 Series 5. General settings adjustment Press SET key to enter into the user-defined state. Meanwhile, PARAM SET is on, controller in parameters setup status. (1) Under intelligent mode, the control panel displays the temperature difference value between water and air (default value is -2).
CWFL-800/1000/1500 Series 7. Advanced parameters adjustment cases: T-506 T-506H Value in Value in Temperature Temperature Order Code Item case 1 case 2 controller controller Factory Setting Factory Setting Temperature setting Temperature Difference values Cooling hysteresis Way of control Alarm for over high...
<6> Flow alarm and output ports In order to guarantee the equipment will not be damaged while cooling water circulation is out of control, CWFL-800/CWFL-1000 dual temperature series chiller possesses a low flow alarm protection. Flow alarm output ports and the wiring diagram 2.
CWFL-800/1000/1500 Series <7> Specifications CWFL-800 Model CWFL-800AN CWFL-800BN Voltage AC 1P 220 V AC 1P 220 V Frequency 50 Hz 60 Hz Current 3.4~11.2A 1.06 KW 1.05 KW Compressor power 1.44 HP 1.43 HP 10714 Btu/h 10611 Btu/h Nominal cooling 3.14 KW...
Page 12
CWFL-800/1000/1500 Series CWFL-1000 Model CWFL-1000AN CWFL-1000BN Voltage AC 1P 220 V AC 1P 220 V Frequency 50 Hz 60 Hz Current 3.4~15 A 1.36 KW 1.48 KW Compressor power 1.84 HP 2.01 HP 14126 Btu/h 14757 Btu/h Nominal cooling 4.14 KW 4.33 KW...
Page 13
CWFL-800/1000/1500 Series CWFL-1500 Model CWFL-1500AN CWFL-1500BN Voltage AC 1P 220 V AC 1P 220 V Frequency 50 Hz 60 Hz Current 3.4~16 A 1.73 KW 1.69 KW Compressor power 2.35 HP 2.30 HP 17623 Btu/h 17145 Btu/h Nominal cooling 5.17 KW 5.03 KW...
CWFL-800/1000/1500 Series <8> Simple troubleshooting Failure Failure Cause Approach Check and ensure the power interface Power cord is not plugged in place and the power plug is plugged in place and in good contact. Machine turned on but Open the electric box cover, check the...
Page 15
CWFL-800/1000/1500 Series CWFL-800/1000/1500 双温系列工业冷水机 使用安装说明书...