3.5
Fuse
Miniature circuit breaker
Inputs
The supply lines of groups are to be protected with a 4 A miniature circuit breaker with
tripping characteristic C or B.
Below, you see the connection for "Sourcing" mode and for "Sinking" mode.
Outputs
The supply lines, max. 16 outputs of a group, are to be protected with a 4 A miniature circuit
breaker with tripping characteristic B or C.
The connection module is to be protected with a 6 A miniature circuit breaker with tripping
characteristic B.
Figure 3-5
"Sourcing" mode for the inputs
Digital input/output module DI 32x24VDC SNK/SRC/DQ 32x24VDC/0.3A SNK BA (6ES7523-1BP50-0AA0)
Equipment Manual, 07/2020, A5E48027024-AA
Wiring
3.5 Fuse
19