Mitsubishi Electric EHPT20Q-VM2EA Service Manual page 26

Cylinder unit
Hide thumbs Also See for EHPT20Q-VM2EA:
Table of Contents

Advertisement

<Table 9-4-1>
Request
code
154
Water circulation pump 1 - Accumulated operating time (after reset)
158
Water circulation pump A - Accumulated operating time (after reset)
162
Indoor unit - DIP SW1 setting information
163
Indoor unit - DIP SW2 setting information
164
Indoor unit - DIP SW3 setting information
165
Indoor unit - DIP SW4 setting information
166
Indoor unit - DIP SW5 setting information
175
Indoor unit - Output signal information
176
Indoor unit - Input signal information
190
Indoor unit - Software version 1st 4 digits
191
Indoor unit - Software version last 4 digits
340
Water circulation pump 1 - Accumulated operating time reset
344
Water circulation pump A - Accumulated operating time reset
504
Indoor unit - Zone 1 room temp. (TH1A)
506
Indoor unit - Return water temp. (THW2)
507
Indoor unit - Zone 2 room temp. (TH1B)
508
Indoor unit - Stored water temp. (lower)(THW5B)
510
Indoor unit - Outside air temp. (TH7)
511
Indoor unit - Flow water temp. (THW1)
533
Indoor unit - Flow water temp. (THW3)
534
Indoor unit - DHW supply temp. (THW4)
535
Indoor unit - Stored water temp. (upper)(THW5A)
540
Flow rate for space heating (Flow sensor 1)
541
Flow rate of the secondary (Potable) circuit (Flow sensor A)
542
Flow rate of the primary circuit (Flow sensor B)
550
Indoor unit - Error postponement history 1 (latest)
551
Indoor unit - Operation control at time of error
552
Indoor unit - Operation mode at time of error
553
Indoor unit - Output signal information at time of error
554
Indoor unit - Input signal information at time of error
555
Indoor unit - Zone 1 room temp. (TH1A) at time of error
556
Indoor unit - Zone 2 room temp. (TH1B) at time of error
558
Indoor unit - Flow water temp. (THW1) at time of error
559
Indoor unit - Return water temp. (THW2) at time of error
560
Indoor unit - Stored water temp.(lower) (THW5) at time of error
Indoor unit - Failure (P1/L5) thermistor
567
Operated Flow switch / Flow sensor at time of failure (L7)
569
571
Flow rate for space heating at time of error (Flow sensor 1)
572
Indoor unit - Flow water temp. (THW3) at time of error
573
Indoor unit - DHW supply temp. (THW4) at time of error
574
Indoor unit - Stored water temp. (upper)(THW5A) at time of error
575
Indoor unit - Failure (LF) folw sensor
576
Indoor unit - Failure (LU) pump
578
Flow rate of the secondary (Potable) circuit (Flow sensor A) at time of error
579
Flow rate of the primary circuit (Flow sensor B) at time of error
Note
Request codes 103 to 105 indicate error histories of both indoor and outdoor units.
As only four digits can be displayed at one time the software version number is displayed in two halves.
Enter code 190 to see the first four digits and code 191 to see the last four digits.
For example software version No. 5.01 A000, when code 190 is entered 0501 is displayed, when code 191 is entered A000 is displayed.
GCH15010
Request content
Range
0 - 9999
0 - 9999
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
Refer to Note below.
Refer to Note below.
–39 - 88
–39 - 110
–39 - 88
–39 - 110
–39 - 88
–39 - 110
–39 - 110
–39 - 110
–39 - 110
0 - 255
0 - 255
0 - 255
Displays postponement code.
("– –" is displays if no postponement code is present.)
0 Standard, 1 Heater
0 OFF, 1 DHW, 2 Heating
5 Freeze protection, 6 Operation stop, 7 Defrost
Refer to detail contents described hereinafter
Refer to detail contents described hereinafter
–39 - 88
–39 - 88
–39 - 110
–39 - 110
–39 - 110
0 Failure thermistor is none, 1 TH1A, 2 TH2, 3 THW1, 4 THW2,
5 THWB1, 6 THW5B, 7 THWB2, 8 TH1B, 9 THW3, A THW6,
B THW7, C THW8, D THW9, E THW4, F THW5A
0 No operated flow switch, 1 Flow switch 1, 2 Flow switch 2,
3 Flow switch 3, 4 Flow sensor 1, 5 Flow sensor B
0 - 255
–39 - 110
–39 - 110
–39 - 110
0 Failure flow sensor is none,
1 Flow sensor 1,
2 Flow sensor A,
3 Flow sensor B
0 Failure pump is none,
1 Water circulation pump 1,
2 Water circulation pump A
0 - 255
0 - 255
26
Unit
10 hours
10 hours
°C
°C
°C
°C
°C
°C
°C
°C
°C
0.1L/min.
0.1L/min.
0.1L/min.
°C
°C
°C
°C
°C
0.1L/min.
°C
°C
°C
0.1L/min.
0.1L/min.