AIR PURGE MANUAL
From MAINTENANCE, select AIR PURGE MANUAL, the following
screen will be displayed:
R1234yf
PRESS ENTER TO PURGE
PRESS ENTER TO PURGE
Tank pressure
xxx psi
Tank Temperature
xxx °F
Target Pressure
xxx psi
AIR PURGE MANUAL
If "PRESS ENTER TO PURGE" is displayed, there is air in the tank. In
this case, press ENTER: the machine will begin discharging the air.
Press ESC to pause the Air Purging process.
NOTE: If there isn't air into the tank, the following message is
displayed: AIR PURGE NOT NECESSARY.
Press ESC to terminate the Air Purging process, and return to the
MAINTENANCE menu.
CALIBRATION
For assistance, call the Snap-on
toll-free
Technical Support Line
800-225-5786
in the continental U.S. or Canada.
MAINTENANCE
• 33 •
GAS ANALYSIS
The machine will test the purity of the refrigerant gas in the A/C
system before beginning recovery. Contaminated refrigerant
cannot be recovered, since it would contaminate all the
refrigerant contained in the storage bottle. Purity testing is
conducted after a sample of the refrigerant gas to be analyzed is
taken.
From MAINTENANCE, select GAS ANALYSIS, the following screen
will be displayed:
R1234yf
Connect and open HP and LP coupling to A/C
system Press ENTER
GAS ANALYSIS
Connect and open the coupling connected to the A/C system,
then press OK:
R1234yf
GAS ANALYZER
CALIBRATION
GAS ANALYSIS
The analyzer will begin the calibration, then after few second will
start gas analysis:
R1234yf
GAS ANALYZER
REFRIGERANT SAMPLE
GAS ANALYSIS
If the refrigerant is PURE the machine will display the following
screen for few seconds:
R1234yf
REFRIGERANT PURITY
R1234yf:
R1134a:
R22:
Hydrocarb.:
Air:
GAS ANALYSIS
MAINTENANCE
MAINTENANCE
xx %
MAINTENANCE
xx %
MAINTENANCE
yyy %
x %
x %
x %
x.x %
Need help?
Do you have a question about the POLARTEK YF EEAC333 and is the answer not in the manual?
Questions and answers
WHAT IS THE PART NUMBER FOR THE ANALYZER FILTER AND HOW OFTEN SHOULD IT BE CHANGED