Allen-Bradley 193-CT-UL-300A Installation Instructions

Allen-Bradley 193-CT-UL-300A Installation Instructions

Overload current transformers

Advertisement

Installation Instructions

Overload Current Transformers

(Cat 193-CT-UL )
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of malfunction or
damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.
1
Cat
193-CT-UL-300A
E205113
UL , cUL Recognized and CSA Certified
As per ANSI/IEEE C57.13 , IEC, OR relevant
standard
B
C
D
F
G
2
193-CT-UL-600A
231838
A
I
J
E
H
INSULATION LEVEL
600 V; BIL 10kV full wave
FREQUENCY
50-400 Hz.
RATING FACTOR
1.33 @ 30 deg. C ambient
OUTER ENCAPSULATION
Plastic Cased
TERMINALS
Brass studs No 8 -32 UNC with one flat washer,
lockwasher and regular nut.
APPROX. WEIGHT
0.5 lbs.
Catalog Number
193-CT-UL-300A
193-CT-UL-600A

DIMENSIONS

193-CT-UL-300A
(INCHES)
A
B
C
D
E
F
G
H
I
J
K
K
L
L
Current
Accuracy
Burden VA
Ratio
(60 Hz)
300:5A
± 1 %
600:5A
± 1 %
193-CT-UL-600A
1.09
3.28
5.29
3.13
4.85
2.7
2.34
1.27
4.56
2.40
2.13
1.96
1.75
1.59
3.78
1.75
2.50
1.14
0.17
0.118
1.08
0.94
2.13
1.96
8.0
30.0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 193-CT-UL-300A and is the answer not in the manual?

Questions and answers

Summary of Contents for Allen-Bradley 193-CT-UL-300A

  • Page 1 Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of malfunction or damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product. 193-CT-UL-300A 193-CT-UL-600A INSULATION LEVEL 600 V;...
  • Page 2 RELAY T2 T3 Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. *PN-457409*...

This manual is also suitable for:

193-ct-ul-600a

Table of Contents