Tyco Fire Product CENTRAL ELOC Instruction Manual

Concealed pendent fusible link automatic sprinklers

Advertisement

Quick Links

CENTRAL
Model ELOC
11.2 K-factor
Quick Response
Extended Coverage Light Hazard
Concealed Pendent Fusible Link Automatic Sprinklers
Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
General
Description
The Central Model ELOC, 11.2
K-factor, Quick Response, Extended
Coverage Light Hazard (ECLH)
Concealed Pendent Sprinklers are
decorative fusible link sprinklers
designed for use in light hazard
occupancies such as churches,
hospitals, offices, and restaurants.
They are intended for use in automatic
sprinkler systems designed in accor-
dance with standard installation rules
(e.g., NFPA 13) for the protection of
light hazards up to a maximum cover-
age area of 324 ft
2
(30,1 m
2
), as
compared to the maximum coverage
2
2
area of 225 ft
(20,9 m
) for standard
coverage sprinklers.
Each unit includes a Cover Plate
Assembly which conceals the sprinkler
operating components above the
ceiling. The separable two-piece design
of the Cover Plate and Support Cup
Assemblies allows installation of the
sprinklers and pressure testing of the
fire protection system prior to istallation
of a suspended ceiling or application of
the finish coating to a fixed ceiling.
They also permit removal of suspended
ceiling panels for access to building
service equipment without having to first
shut down the fire protection system
and remove sprinklers.
Also, the separable two-piece design of
the sprinkler provides for 7/8" (22,2 mm)
of vertical adjustment, to reduce the
accuracy to which the length of fixed
pipe drops to the sprinkler must be cut.
The ELOC ECLH Concealed Pendent
Sprinkler is shipped with a Disposable
Protection Cap. The Protective Cap is
temporarily removed to install the
ELOC, and then replaced to protect the
ELOC while the ceiling is being installed
and finished. The tip of the Protection
Cap can be used to mark the center of
the ceiling hole into plaster board,
ceiling tiles, ect. by pushing the ceiling
product against the Protection Cap.
When the ceiling installation is com-
ELOC
plete, the Protection Cap is removed
and the Cover Plate Assembly installed.
Operation: When exposed to heat from
a fire, the Cover Plate, which is
soldered to the Retainer Assembly at
three points, falls away to expose the
Sprinkler Assembly. At this point the
Deflector supported by the Arms drops
down to its operational position.
The fusible link assembly is comprised
of two link halves which are joined by a
thin layer of solder. When the rated
temperature is reached, the solder
melts and the two link halves separate,
which then allows the sprinkler to
activate and flow water.
WARNING
The Model ELOC ECLH Concealed
Pendent Sprinklers described herein
must be installed & maintained in
compliance with this document, as well
as with the applicable standards of the
National Fire Protection Association, in
addition to the standards of any other
authorities having jurisdiction. Failure to
do so may impair the integrity of these
devices.
The owner is responsible for
maintaining their fire protection system
and devices in proper operating
condition. The installing contractor or
sprinkler manufacturer should be
contacted relative to any questions.
Technical
Data
Sprinkler Identification Number
SIN C5522
Approvals
UL and C-UL Listed. NYC Approved.
(Refer to Table 1. The approvals apply
only to the service conditions indicated
in the Design Criteria Section)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
Discharge Coefficient
1/2
K = 11.2 GPM/psi
(161,3 LPM/bar
O P
T
I M
Extended
Coverage Light
Hazard
Concealed
Pendent
Sprinklers
Temperature Ratings
160°F/71°C Sprinkler - 135°F/57°C Plate
212°F/100°C Sprinkler - 165°F/74°C Plate
Finishes
Sprinkler: Natural Brass
Cover Plate: Chrome or Brass Plated;
*Flat White, Bright White, or Custom
Painted
* Standard Finish supplied when
White is specified
Physical Characteristics
The Model ELOC ECLH Concealed
Pendent Sprinklers utilize a dezincification
resistant (DZR) bronze frame and a monel
thermal sensitive link. The sprinkler frame
orifice is sealed with a gasketed spring
plate (Belleville Seal) consisting of a
beryllium nickel disc spring that is sealed
on both its inside and outside edges with a
Teflon
TM
gasket. The arms and deflector
are bronze, and the support cup is steel.
The cover plate and retainer assembly are
1/2
brass.
)
2-01
A
No. 2-7.0

Advertisement

loading
Need help?

Need help?

Do you have a question about the CENTRAL ELOC and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco Fire Product CENTRAL ELOC

  • Page 1 CENTRAL ELOC 2-01 Model ELOC 11.2 K-factor Quick Response Extended Coverage Light Hazard Concealed Pendent Fusible Link Automatic Sprinklers Tyco Fire Products --- www.centralsprinkler.com 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385 Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 plete, the Protection Cap is removed General...
  • Page 2 Figure 1 - Model ELOC, Figure 2 - Model ELOC, ECLH ECLH Concealed Pendent Sprinkler Concealed Pendent Sprinkler (Activated) 2-1/2" ± ± 1/8" (63,5mm ± 3,2mm) Hole Diameter WRENCH FLAT 1-1/8" (28,6mm) Max. 3/16" 3-1/4"(82,6mm) 1/4" (6,4mm) Min. (4,8mm) Diameter ELEVATION VIEW ELEVATION VIEW Figure 4 - ELOC Sprinkler Wrench...
  • Page 3 Design Criteria The Model ELOC ECLH Concealed Pendent Sprinklers are UL and C-UL listed and NYC Approved (MEA 7-95-E), for use in light hazard occupancies, using the design criteria in Table 1 as well as any additional requirements specified in current NFPA 13 Standards for Extended Coverage Pendent Sprinklers.
  • Page 4 (e.g., NFPA 25), in addition to the Care & Ordering standards of any other authorities having jurisdiction. The installing Maintenance contractor or sprinkler manufacturer Information should be contacted relative to any questions. The Model ELOC ECLH Concealed Ordering Information: When It is recommended that automatic Pendent Sprinklers must be maintained placing an order, indicate the full...