SYNCHRONISM CHECK UNIT:
89 OPEN, Compare V1 with V2:
• Remove auxiliary voltage from terminal PI1 (89 open).
• Apply 60 Vac at 60 Hz to V1 and V2 with an angle difference of 0º between both voltages.
• Change the following settings and check that contacts SP1, SP2, SP3 and SP4 close.
• Increase voltage V1 and check that for 70 Vac, contacts SP1, SP2, SP3 and SP4 open.
• Decrease V1 voltage to 60 Vac.
• Change V1 angle with respect to V2, and check that when reaching 10º , contacts SP1, SP2, SP3 and SP4
open.
89 CLOSED, Compare V1 with V4:
• Apply auxiliary voltage only to PI1 (89 closed).
• Apply 60 Vac at 60 Hz to V1, V2 and V4 with an angle difference of 0º between V1-V4 and V2-V4, and check
that contacts SP1, SP2, SP3 and SP4 close.
• Increase V4 and check that when reaching 70 Vac, contacts SP1, SP2, SP3 and SP4 open.
• Decrease V4 to 60 Vac.
• Change V4 angle with respect to V1 and V2, and check that when reaching 10º, contacts SP1, SP2, SP3 and
SP4 open.

6.16. IRIG-B

• Synchronise the relay with the date and time of the PC that is being used to communicate with the unit.
• Check that the relay and the PC show the same time.
• Place in the IRIG-B receiver a date/time completely different from the current time, which is on the PC.
• Connect the IRIG-B receiver to the relay.
• Check that the relay and the IRIG-B receiver show the same date/time.
GEK-106271
GENERAL SETTINGS
FREQUENCY
25 SETTINGS FOR 521
79/ DL-DB
79/ LL-DB
79/ DL-LB
79/ SYNCHECK
CLOSE/ DL-DB
CLOSE/ LL-DB
CLOSE/ DL-LB
CLOSE/ SYNCHECK
25 SETTINGS FOR 520
79/ DL-DB
79/ LL-DB
79/ DL-LB
79/ SYNCHECK
CLOSE/ DL-DB
CLOSE/ LL-DB
CLOSE/ DL-LB
CLOSE/ SYNCHECK
MIV Digital Multifunctional Protective Relay
60 Hz
Not permitted
Not permitted
Not permitted
permitted
Not permitted
Not permitted
Not permitted
permitted
Not permitted
Not permitted
Not permitted
permitted
Not permitted
Not permitted
Not permitted
permitted
6. ACCEPTANCE TESTS