Chapter 1 Safety Precautions Before Supplying Power to the Inverter Warning The main circuit must be correctly wired. For single phase supply use input terminals (R/L1, T/L3) and for three phase supply use input terminals (R/L1, S/L2, T/L3). Terminals U/T1, V/T2, W/T3 must only be used to connect the motor. Connecting the input supply to any of the U/T1, V/T2 or W/T3 terminals will cause damage to the inverter.
Do not connect a braking resistor directly to the DC terminals P (+) and N (-), otherwise fire may result. Use wire gauge recommendations and torque specifications. (See Wire Gauge and Torque Specification in section 3.6) Never connect input power to the inverter output terminals U/T1, V/T2, W/T3. ...
Page 4
Carefully check the performance of motor or machine before operating at high speed, otherwise Injury may result. Note the parameter settings related to the braking unit when applicable. Do not use the inverter braking function for mechanical holding, otherwise injury may result.
Chapter 2 Environment and Installation 2.1 System Diagram ~ ~ ~ Power supply: Power Supply Make sure the correct voltage is applied to avoid damaging the inverter. Molded-case circuit breaker (MCCB) or fused disconnect: Molded A molded-case circuit breaker or fused disconnect must be installed Circuit between the AC source and the inverter that conforms to the rated Breaker...
2.2 General Wiring Diagram 2KΩ 750Ω 100Ω Notes: *1: Models 200V 1 ~ 25HP and 400V 1 ~ 40HP or lower ratings have a built-in braking transistor. To use this braking transistor a braking resistor can be connected between B1 and B2. *2: Use SW3 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multi-function digital input terminals S1~S8.
2.3 Power Terminals 200V: 1 ~ 25HP 200V: 30 ~ 150HP 400V: 1 ~ 40HP Terminal 400V: 50 ~ 425HP 575V: 1 ~ 10HP 690V: 50 ~ 270HP 690V: 15 ~ 40HP R/L1 S/L2 Input Power Supply (For single phase use terminals R/L1 and S/L2) T/L3 B1/P ...
Page 8
Type Terminal Terminal Function Signal Level / Information Power for external speed potentiometer +10V (Max. current , 20mA) +10V Only above 200V 3HP/ 400V 5HP (include) support -10V (Max. current , 20mA) -10V this terminal function From 0 to +10V, Multi-function analog input for speed reference (0- From -10V to +10V 10V input)/(-10V~10V input)
*2:Multi-function analog input/ output can be referred to in our instruction manual.. - Group 04 - External Terminal Analog Signal Input (Output) Function Group. Caution Maximum output current capacity for terminal 10V is 20mA. Multi-function analog output AO1 and AO2 are used for an analog output meter. Do not use these outputs for feedback control.
Chapter 3 Parameters Parameter group Group Name Basic Parameters Group 00 V/F Control Parameters Group 01 IM Motor Parameters Group 02 External Digital Input and Output Parameters Group 03 External Analog Input and Output Parameters Group 04 Multi-Speed Parameters Group 05 Automatic Program Operation Parameters Group 06 Start /Stop Parameters...
Page 11
Group 00: Basic Parameters Group 00: Basic Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 0: V/F UP/DOWN 1: V/F+PG Communication Control (RS-485) 2: SLV Control Mode 4: Pulse Input 00-00 3: SV Selection 5: Reserved 4: PMSV...
Page 12
Group 00: Basic Parameters Group 00: Basic Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Modified 0:Disable 00-19 Acceleration 0.1~0600.0 Parameters 00-33 Time (only for LCD 1:Enable keypad) 00-20 Deceleration 0.1~0600.0 00-34 Time Reserved 00-40 Acceleration...
Page 13
parameter will make the motor parameter Group 01: V/F Control Parameters automatically be changed. Parameter Attrib Code Setting Range Default ***** If the maximum output frequency of motor is over Name 300HZ,the frequency resolution is changed to 0.1Hz. Voltage of 400V: 0.0~510.0 Motor 1 575V: 0.0~670.0...
Page 14
Group 02: IM Motor Parameters Group 02: IM Motor Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name No-Load No-Load 02-00 Current of 0.01~600.00 02-20 Current of 0.01~600.00 Motor1 Motor 2 Modes of V/F, 10%~200% of Rated Current V/F+PG are...
Page 15
Group 03: External Digital Input and Group 03: External Digital Input and Output Parameters Output Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Command 1 21: PID Integral Reset 3: Multi- 22~23 : Reserved Speed/Position Setting 24: PLC Input...
Page 16
Group 03: External Digital Input and Group 03: External Digital Input and Output Parameters Output Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Torque 1xxxb: S4 B Command Contact 46: Zero-Servo xxx0b: S5 A Command Contact xxx1b: S5 B...
Page 17
Group 03: External Digital Input and Group 03: External Digital Input and Output Parameters Output Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 23: Source of short-circuit Operation braking Command 57: Low Current Note2 24: Source of Detection...
Page 18
Group 03: External Digital Input and Group 03: External Digital Input and Output Parameters Output Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name xxx0b: Photo- Frequency coupler A 03-44 Detection 0.0~599.0 Photo-coupler Contact Level 2 03-29 Output...
Page 19
Group 04: External Analog Input and Group 04: External Analog Input and Output Parameters Output Parameters Parameter Parameter Attrib Attrib Code Setting Range Default Code Setting Range Default Name Name 2: Output 04-03 AI1 Bias -100.0~100.0 Voltage 0: Disable 04-04 Negative AI Note4 3: DC Voltage 1: Enable...
Page 20
Group 05: Multi-Speed Parameters Group 04: External Analog Input and Output Parameters Parameter Attrib Code Setting Range Default Name Parameter Attrib Code Setting Range Default 0: Acceleration Name and deceleration of Multi Acceleration time are set by Speed 0 00-14 ~ 00-24 Deceleration 05-00 Deceleration...
Page 21
Group 04: External Analog Input and Group 04: External Analog Input and Output Parameters Output Parameters Parameter Parameter Attrib Attrib Code Setting Range Default Code Setting Range Default Name Name Deceleration of Multi Time Setting Speed 14 05-32 0.1~6000.0 10.0 of Multi Acceleration Speed 7...
Page 22
Group 06: Automatic Program Operation Group 06: Automatic Program Operation Parameters Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name last stage. Restart Operation- speed is based on Stage 14 the speed of stage *Frequency Setting of 06-15...
Page 23
Group 06: Automatic Program Operation Group 06: Automatic Program Operation Parameters Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Operation Direction 1: Forward Selection of Time Setting 2: Reverse 06-29 0.0~6000.0 Speed-Stage of Speed- Stage 13 Operation Operation...
Page 24
Group 07: Start /Stop Parameters Group 07: Start /Stop Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name DC Injection Start-up Mode 0: Start with Selection of 07-07 Braking 0~100 speed search 07-26 SLV Coast to Current 1: Normal start Stop...
Page 25
Group 07: Start /Stop Parameters Group 08: Protection Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Function Level in 950V 575V:900~1000 1: STP2 Disable Selection Deceleration 1140V 690V:1080~1200 DC Injection Stall 07-46 0~150 100 Note5 HD:160 Current Limit...
Page 26
Group 08: Protection Parameters Group 08: Protection Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name when Reaching Base Speed the Set Stall Frequency. Prevention 2: Start to Detect 08-22 Detection 2~100 when the Time in Operation is Operation...
Page 27
Group 08: Protection Parameters Group 08: Protection Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Stall Disconnection 1: Fire Mode Prevention Selection Speed (08-52) Limit 2: Motor 1 Maximum Frequency (01- 08-42 Protection 0.1~10.0V Level PTC Restart...
Page 28
Group 09: Communication Parameters Group 10: PID Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 2: Deceleration to Output + Stop Based on Frequency Deceleration Time 2 Command when Feedback Communication 10-04 0.01~10.00 1.00 Fault Occurs.
Page 29
Group 10: PID Parameters Group 10: PID Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 10-28 Reserved 10-46 0: Disable Proportional 10-47 0.00~10.00 3.00 Note4 PID Sleep Gain 3(P) 10-29 1: Enable Selection Integral Time 2: set by DI 10-48...
Page 30
Group 11: Auxiliary Parameters Group 11: Auxiliary Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Frequency 3 Filter Fall Amount Jump 11-11 Frequency 0.0~25.5 DC Voltage Width 11-35 Filter Dead 0.0~99.0 10.0 band Level Manual Energy 11-12 0~100...
Page 31
Group 11: Auxiliary Parameters Group 11: Auxiliary Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 575V: 540~570 Parameter of Preventing 690V: 540~684 Oscillation Zero-servo 11-49 0.01~5.00 1.00 Gain 0: Mode1 Selection of Zero-servo 11-62 Preventing 11-50...
Page 32
Note: The parameter of 11-01 can be changed during run Group 12: Monitoring Parameters operation, the range is 1~16KHz. Setting Range Parameter Attrib Code Default Name 4: Display Line Speed with the Third Decimal Group 12: Monitoring Parameters Place (xx.xxx) Setting Range Parameter Attrib...
Page 33
Group 12: Monitoring Parameters Group 12: Monitoring Parameters Setting Range Setting Range Parameter Attrib Parameter Attrib Code Default Code Default Name Name Frequency current output current torque frequency command (100% Display the corresponds to 12-18 Output Current current output motor torque ) current Display the Display the...
Page 34
Group 12: Monitoring Parameters Group 12: Monitoring Parameters Setting Range Setting Range Parameter Attrib Parameter Attrib Code Default Code Default Name Name frequency set by current fault 01-02 or 01-16) Description is Display output of similar to 12-05 the PID controller Display the (100% inverter status...
Page 35
Group 12: Monitoring Parameters Group 13: Maintenance Parameters Setting Range Parameter Attrib Parameter Attrib Code Default Code Setting Range Default Name Name 12-66 Encoder Angle 0~360 Locked are read-only except 13-06 Cumulative 12-67 0.0 ~ 999.9 and main Energy (KWHr) frequency Cumulative 12-68...
Page 36
Group 13: Maintenance Parameters Group 13: Maintenance Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Function 1: Clear Fault History thirteen Fault History History Parameter Exhibit Previous 13-10 Password 0 ~ 9999 Previous 13-34 fourteen Fault Note1...
Page 37
Group 13: Maintenance Parameters Group 14: PLC Setting Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Fault History twenty eight 14-32 0~65534 (Note4) AS3 Set Value 3 Fault History 14-33 0~65534 (Note4) AS4 Set Value 1 Exhibit 14-34 0~65534 (Note4)
Page 38
Group 15: PLC Monitoring Parameters Group 16: LCD Function Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 15-27 AS4 Current Value 0~65534 (Note4) display unit is MD1 Current rpm. 15-28 0~65534 (Note4) Value 3~39: MD2 Current Reserved...
Page 39
Group 16: LCD Function Parameters Group 17: Automatic Tuning Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 5: Rotation 20: °C Auto-tuning 21: RPM Combination 22: Bar (item: 4+2+0) 23: Pa 6: Static Auto- 24: KPa tuning 16-05 LCD Backlight 0~7...
Page 40
Group 17: Automatic Tuning Parameters Parameter Attrib Code Setting Range Default Name Inductance Group 19: Wobble Frequency Parameters Motor Slip 17-13 0.10~20.00 1.00 Parameter Attrib Frequency Code Setting Range Default Name 0: VF Rotation Center Selection of Auto-tuning Frequency of 17-14 Rotation Auto- 1: Vector...
Page 41
Group 20: Speed Control Parameters Group 20: Speed Control Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name 1: Speed control Speed is enabled either Deviation 20-24 0.0~10.0 in acceleration (DEV) or deceleration. Detection Time Delay 0: Deceleration 20-08...
Page 42
Group 21: Torque And Position Control Group 21: Torque And Position Control Parameters Parameters Parameter Attrib Parameter Attrib Code Setting Range Default Code Setting Range Default Name Name Filter Time of The Command 21-01 Torque 0~1000 of Rotation 21-16 -9999 ~ 9999 Reference Cycle Number 0: According to...
Page 43
* Refer to the attachment 1 in our instruction Group 21: Torque And Position Control manual. Parameters Parameter Attrib Code Setting Range Default Name The Command of Rotation 21-30 -9999 ~ 9999 Cycle Number Group 22: PM Motor Parameters of Section 10 Parameter Attrib The Command...
LED display Possible solutions 4.2 Fault Detection Function running inverter. Check resistance When a fault occurs, please refer to Table 4.1 between cables and for possible causes and take appropriate ground. measures. Reduce carrier frequency. Increase deceleration Use one of the following methods to restart: time Over voltage...
Page 46
LED display Possible solutions LED display Possible solutions 15 / 08-16). detection Check and reduce motor load, check and operation duty cycle. External fault Check under torque (S1) Under torque detection parameters (08- detection 19 / 08-20). Check load / application. External fault Switch for (S2)
LED display Possible solutions Note: The fault contact output does not Check IGBTs energize on a self-diagnostics error. While a fuse open Check for short circuit at self-diagnostics code is active the inverter inverter output. does not accept a run command until the ...
Page 48
LED display Corrective action LED display Corrective action Check wiring baseblock (flash) Inverter over Multi-function input heating function set incorrectly. warning Check wiring (flash) External baseblock Check over torque (flash) detection parameters over torque (08-15 / 08-16). detection ...
Page 49
LED display Corrective action LED display Corrective action Replace inverter with overload EF4 ( flash ) larger rating. External fault Check and reduce (S4) motor load, check and operation duty cycle. (flash) EF5 ( flash ) Check connection communication External fault ...
Page 50
LED display Corrective action LED display Corrective action Check 10-29 and 10-03 RunEr Wrong running Revise the command direction Error among 11-00, jog and HPErr DI control to see if any Model Check inverter capacity difference selection error setting 13-00.
Table 4.4, for fault information during tuning, 4.4 Auto-tuning Error cause and corrective action. When a fault occurs during auto-tuning of a standard AC motor, the display will show the Table 4.4 Auto-tuning fault and corrective “AtErr” fault and the motor stops. The fault actions for PM motor information is displayed in parameter 17-11.
Main Circuit Terminal Wiring UL approval requires crimp terminals when wiring the inverter’s main circuit terminals. Use crimping tools as specified by the crimp terminal manufacturer. Teco recommends crimp terminals made by NICHIFU for the insulation cap. The table below matches inverter models with crimp terminals and insulation caps. Orders can be placed with a Teco representative or directly with the Teco sales department.
Page 89
Type 1 During installation, all conduit hole plugs shall be removed, and all conduit holes shall be used. 690V 80A...
Page 90
Motor Overtemperature Protection Motor overtemperature protection shall be provided in the end use application. ■ Field Wiring Terminals All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper connections that are to be made to each terminal and indicate that copper conductors, rated 75°C are to be used.
Page 91
Préface Le produit est un lecteur conçu pour commander un moteur à induction triphasé. lire attentivement ce manuel pour garantir le bon fonctionnement, la sécurité et pour se familiariser avec les fonctions d'entraînement. Le lecteur est un appareil électrique / électronique et doit être installé et géré par un personnel qualifié...
1.2 Câblage Avertissement Coupez toujours l'alimentation électrique avant de procéder à l'installation d'entraînement et le câblage des terminaux utilisateurs. Le câblage doit être effectué par un personnel qualifié / électricien certifié. Assurez-vous que le lecteur est correctement mis à la terre. (220V Classe: impédance ...
pendant que l'alimentation du lecteur est allumé, un choc électrique peut se produire autrement. Ne pas brancher ou débrancher le moteur pendant le fonctionnement. Le variateur pourrai se déclencher et ainsi endommager le lecteur. Les opérations peuvent commencer soudainement si une alarme ou un défaut est réarmé...