Introduction Safety notes Installing/mounting SITRANS F Connecting Coriolis flowmeters SITRANS MASS 2100 & FC300 Commissioning (FCT010) Service and maintenance Compact Operating Instructions Technical data Product documentation and support 7ME481 (MASS 2100/FC300 with FCT010) 05/2020 A5E40504094-AB...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
● product identification ● product specifications ● certificates and approvals Note Identification Identify your device by comparing your ordering data with the information on the product and specification nameplates. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Device specific order number Figure 1-1 MASS 2100 nameplate example Flowmeter serial number construction The flowmeter serial number is constructed as follows: PPYMDDxxxxxx where PP = Production factory (Siemens S.A.S. Haguenau: N1) SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 7
Month (M) Code January February March April June July August September October November December Date (DD) Code Day 1 to 31 01 to 31 (corresponding to the actual date) SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Range of ambient temperature ⑫ MAWP Maximum allowable working pressure ⑬ Size Size ⑭ Serial No. Device specific serial number ⑮ Order No. Device specific order number Figure 1-2 FC300 nameplate example SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
FCT010 transmitter: Nameplate with specific information ① 2813 ATEX Notified Body ID (SIRA Certification) ② Ex approvals Ex approval specifications for the transmitter (for details on all approvals refer to Disposal (Page 45)) SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
4. Check the scope of delivery by comparing your order to the shipping documents for correctness and completeness. WARNING Using a damaged or incomplete device Risk of explosion in hazardous areas. ● Do not use damaged or incomplete devices. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber...
Page 12
Introduction 1.7 Transportation and storage The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Operation of this equipment in a residential area is likely to cause harmful interference to radio communications, in which case the user will be required to correct the interference at his own expense. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
If you need additional information not covered by these instructions, contact your local Siemens office or company representative. Note Operation under special ambient conditions...
● Connect the device with type of protection "Intrinsic safety" solely to an intrinsically safe circuit. ● Observe the specifications for the electrical data on the certificate and/or in Technical data (Page 47). SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 16
Safety notes 2.3 Use in hazardous areas SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Refer to the information in Technical data (Page 47). Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
Damage to device by severe external stresses and loads (e.g. thermal expansion or pipe tension). Process media can be released. ● Prevent severe external stresses and loads from acting on the device. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
● Install the device so that there is sufficient air supply in the room. ● Observe the maximum permissible ambient temperature. Refer to the information in the section Technical data (Page 47). SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
● Avoid long drop lines downstream from the sensor to prevent process media separation causing air / vapor bubbles in the tube (min. back pressure: 0.2 bar). ● Avoid installing the flowmeter immediately upstream of a free discharge in a drop line. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
The sensitivity and the accuracy of the sensor do not change with reverse flow. The indicated flow direction (positive/negative) is configurable. CAUTION Accurate measurement The sensor must always be completely filled with process media in order to measure accurately. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
3.2 Sensor installation Orienting the sensor The sensor operates in any orientation. The optimal orientation depends on the process fluid and the process conditions. Siemens recommends orienting the sensor in one of the following ways: 3.2.3 MASS 2100 DI 1.0 - 2.1...
Installation in a dropline is only possible if a pipeline reduction or orifice with a smaller cross- section can be installed to prevent the sensor from being partially drained during the measurements. ① Orifice Pipe ② Valve Figure 3-3 Installation in drop line SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
● If the device contains hazardous media, it must be emptied prior to disassembly. Make sure that no environmentally hazardous media are released. ● Secure the remaining connections so that no damage can result if the process is started unintentionally. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
20 °C (36 °F). ● Before taking the device into operation, let the device adapt for several hours in the new environment. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 28
● Shielded cables that cross into hazardous areas should be grounded only at one end. ● If grounding is required at both ends, use an equipotential bonding conductor. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 29
For metal enclosures there is an increased electromagnetic compatibility compared to high- frequency radiation. This protection can be increased by grounding the enclosure. See also Basic safety notes (Page 27) SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
DIP switches should be set to the EOL Active state. CAUTION Hazardous areas Only change the DIP switches in hazardous areas when the device is deenergized. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 31
It is recommended to use cables supplied by Siemens. ● Siemens supplied cables can be ordered with M12 plug on both ends or without plug. ● To guarantee the IP67 degree of protection, ensure that both ends of the cables are given equivalent protection from ingress of moisture.
Page 32
5. Remove the cap and the ferrule from the cable gland and slide onto the cable. 6. Push the cable through the open gland and anchor the cable shield and the wires with the clamp bar. 7. Remove the terminal block from the electronic. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 33
Blue Figure 4-2 Sensor terminal compartment 9. Reinstall the electronic including the mounting screw. 10.Connect the sensor connection and the sensor cable. 11.Restore the flexible strap around all wires. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 34
Only change the DIP switches in hazardous areas when the device is deenergized. Location of DIP switch The DIP switch is located in the electronic as shown below. FW3 (before 07/2018) SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 35
EOL not active NOTICE Avoid DIP switch settings not mentioned in the table DIP switch settings not mentioned in the table preceding are not allowed and may reduce communication interface reliability. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 36
Connecting 4.2 Connecting MASS 2100/FC300 SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Loss of explosion protection Risk of explosion in hazardous areas if the device is open or not properly closed. ● Close the device as described in Installing/mounting (Page 17). SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 38
● Check prior to commissioning that the cover, cover locks, and cable inlets are assembled in accordance with the directives. Exception: Devices having the type of protection "Intrinsic safety Ex i" may also be opened in energized state in hazardous areas. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
● Reliability of power supply, lightning protection, and grounds WARNING Impermissible repair and maintenance of the device ● Repair and maintenance must be carried out by Siemens authorized personnel only. WARNING Impermissible repair of explosion protected devices Risk of explosion in hazardous areas ●...
● Do not use any aggressive cleansing agents or solvents, e.g. acetone. Plastic parts or the painted surface could be damaged. The inscriptions could become unreadable. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
WARNING Impermissible repair of explosion protected devices Risk of explosion in hazardous areas ● Repair must be carried out by Siemens authorized personnel only. WARNING Maintenance during continued operation in a hazardous area There is a risk of explosion when carrying out repairs and maintenance on the device in a hazardous area.
Page 42
● As long as the device is under pressure, do not loosen process connections and do not remove any parts that are pressurized. ● Before opening or removing the device ensure that process media cannot be released. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
● Seal integrity of the process connections, cable entries, and cover screws ● Reliability of power supply, lightning protection, and grounds NOTICE Repair and service must be carried out by Siemens authorized personnel only. Note Siemens defines flow sensors as non-repairable products.
● Devices/replacement parts should be returned in their original packaging. ● If the original packaging is no longer available, ensure that all shipments are properly packaged to provide sufficient protection during transport. Siemens cannot assume liability for any costs associated with transportation damages.
Information about battery / product return (WEEE) (https:// support.industry.siemens.com/cs/document/109479891/) Note Special disposal required The device includes components that require special disposal. ● Dispose of the device properly and environmentally through a local waste disposal contractor. SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 46
Service and maintenance 6.7 Disposal SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Ex ia IIC T6…T3 Ga Ex ia IIIC T135°C Da (For dust applications (IIIC) the maximum ambient temperature is limited to 100°C ac‐ cording to IEC 60079-11 table 4.) SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
Page 50
100°C ac‐ cording to IEC 60079-11 table 4.) EU Declaration of Conformity A5E31814816A/010 Pressure equipment ● 2014/68/EU Pressure Equipment Directive (PED) ● Canadian Registration Number (CRN) SITRANS MASS 2100 & FC300 (FCT010) Compact Operating Instructions, 05/2020, A5E40504094-AB...
– "Download as html5, only PC": Open or save the manual in the HTML5 view on your PC You can also find manuals with the Mobile app at Industry Online Support (https:// support.industry.siemens.com/cs/ww/en/sc/2067). Download the app to your mobile device and scan the device QR code. Product documentation by serial number Using the PIA Life Cycle Portal, you can access the serial number-specific product information including technical specifications, spare parts, calibration data, or factory certificates.
In addition to our technical support, Siemens offers comprehensive online services at Service & Support (http://www.siemens.com/automation/service&support). Contact If you have further questions about the device, contact your local Siemens representative at Personal Contact (http://www.automation.siemens.com/partner). To find the contact for your product, go to "all products and branches" and select "Products &...