Download Print this page

hager VE24AH Instruction/Data Sheet page 2

Advertisement

MCB
Use circuit as
normal
YES
Does device
Try & reset device once
stay ON?
NO
NO
Does device
supply socket
outlets
YES
Unplug all
appliances from
circuit and reset
device / replace fuse*
Plug in & switch on
YES
NO
Does device
appliances one at a time
stay ON?
until device trips / blows,
identifying faulty appliance
Dimensions - Garage Board
Dimensions
Enclosure Size
(mm)
VE24AH
A
165
B
190
C
N/A
D
114
3
T
MCB
RCCB
START
MCB
Use circuit as
tripped
normal
MCB
or
RCCB
RCBO
What device
Does device
Try & reset device once
is it?
stay ON?
Turn OFF
all MCBs devices
Reset RCCB
NO
Does device
stay ON?
Unplug faulty
appliance until
Turn ON MCBs
repaired. Reset device.
devices one at a time
Other appliances may
until RCCB trips again,
be used
identifying faulty circuit
ZD0630 - Issue 6 01-21
GB
VE24AH Garage Board
Instructions/Data Sheet
This Garage Board and Hager devices conform with the
following standards:
Consumer Unit: BS EN 61439-3 including Annex ZB.
Residual Current Circuit Breaker (RCCB): BS EN 61008-1
Miniature Circuit Breaker (MCB): BS EN 60898-1
Installation Instructions:
All product(s) must be installed by a suitably competent electrician
Giving consideration to their intended use and in accordance with the
current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act
shall be complied with.
Only equipment and arrangements speci ed in Hager's technical
documentation / catalogue shall be used.
YES
Install in the horizontal plane only.
Important notice:
To prevent potential overheating from loose connections the installer
shall check connections are tight to the torque levels stated in these
instructions prior to energizing this board. This check should include
NO
factory made connections which may have loosened in transit.
Guidance Notes:
The total load must not exceed the rating of the incoming device or the assigned assembly rating (InA) whichever is the lower. Each neutral and earth
connection must correspond numerically to its outgoing way. Additional blanks (ref. JK01B) are available to cover spare ways.
A pack is provided to label this garage board, please consult us for spares or replacements.
Operating Instruction lea et is provided overleaf. This lea et should be left for the end user.
Single conductors below 1.5mm need to be doubled back in the terminal bar.
Precautions need to be taken to prevent faults to earth on the supply side of the RCD (as per BS7671 regulation 531.4.1)
IP Ratings:
Cable access into the garage board must maintain the integrity so far as reasonably practicable. In essence, for surfaces accessible after installation, this
means maintaining the requirement for the horizontal top surface of the enclosure to provide a degree of protection as detailed in g 1 and g 2. For rear
YES
cable access, the minimum number of knockout(s) shall be removed.
Fitting Hager MCBs and RCBOs:
Only equipment and arrangements speci ed in Hager's technical
documentation / catalogue shall be used.
1. Isolate the electrical supply from the Garage Board.
2. Remove the front cover.
3. Fully slacken the lower terminal of the device.
4. Fully open the bottom device clip ( g 1.)
Warranty
This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please call the
technical support number given at the bottom of the page and we will be pleased to help.
For dimensional information and weights please consult the Hager catalogue.
Note: Only BASEC approved cable should be used
1.0mm
2
to 10mm
2
for outgoing cables
up to 10mm
2
for incoming live cables
Single conductors below 1.5mm need to be doubled back in the terminal bar.
1
Fig 1. VE24AH
IP55
Tightening torque values to be applied (Nm)
RCCB's 40A: 2.8 Nm
MCBs: 2.8 Nm
Earth & Neutral terminal bar connections: 2.0 Nm
Single conductors below 1.5mm need to be doubled back in the
terminal bar
Good workmanship and proper materials must be applied by the installer.
5. Locate the device onto the din rail, and busbar. Ensure that the
busbar tooth is within the device terminal cage.
6. Close the bottom device clip.
7. While holding the device rmly onto the busbar, fully tighten the lower
terminal screw.
8. After tting all outgoing devices and connecting all outgoing cables,
please check the tightness of all cable connections. This should
include all factory made connections, which may have loosened
during installation or transit.
g 1.
ZD0630 - Issue 6 01-21

Advertisement

loading
Need help?

Need help?

Do you have a question about the VE24AH and is the answer not in the manual?

Questions and answers