Download Print this page
Guardian G3600LF Series Installation, Operation And Maintenance Manual

Guardian G3600LF Series Installation, Operation And Maintenance Manual

Thermostatic mixing valves

Advertisement

Quick Links

Note: Please provide valve serial number (stamped on cover of valve) when ordering parts.
Angle Checkstop
Installation
1. Install valve in a location where it may be easily cleaned,
adjusted or repaired.
2. Inlets are clearly marked on valve body casting. Connect hot
water to inlet marked "HOT" and cold water to inlet marked
"COLD."
3. Included angle checkstops must be installed on both supply
lines (see above).
4. Use solder or pipe cement sparingly. Flush supply pipes
before connecting valve. Flush outlet pipe and valve once
valve is connected.
Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment).
Guardian Equipment
312 447 8100
1140 N North Branch St
312 447 8101
Chicago, IL 60642
gesafety.com
Thermometer
Hot Water
Inlet
IMPORTANT: THESE SYSTEMS ARE DESIGNED TO PROVIDE MIXED WATER
FROM 60 TO 90°F (15 TO 32°C) FOR EMERGENCY EYE OR EYE/FACE WASH
APPLICATIONS ONLY IN ACCORDANCE WITH ASSE 1071.
telephone
facsimile
Installation, Operation and Maintenance Guide
G3600LF Series Thermostatic Mixing Valves
Cold Water
Inlet
G3600LF
Maximum operating pressure is 125 PSI (860 KPA) for hot and cold
water. Maximum hot to cold water pressure differential is 5%.
Note: Should piping be exposed to excessive hot or cold conditions,
it may be necessary to insulate piping to prevent freezing or scalding
water.
Angle Checkstop
1/2" OD Copper
Tube Inlets
rev. 1215 / © 2015 Guardian Equipment
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the G3600LF Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Guardian G3600LF Series

  • Page 1 APPLICATIONS ONLY IN ACCORDANCE WITH ASSE 1071. Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment). rev. 1215 / © 2015 Guardian Equipment Guardian Equipment 312 447 8100...
  • Page 2: Troubleshooting

    Installation, Operation and Maintenance Guide G3600LF Series Thermostatic Mixing Valves Adjustment and Service Guardian Equipment thermostatic mixing valves may be easily Note: Thermostatic water mixing valves are regulating mechanisms which must be regularly maintained to provide best performance. Local water quality cleaned, adjusted and repaired.
  • Page 3 4. Turn thermostatic valve to full hot and wait ten seconds. deactivate emergency equipment. Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment). rev. 1215 / © 2015 Guardian Equipment Guardian Equipment 312 447 8100...
  • Page 4 Driving Ball Coil Bracket Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment). rev. 1215 / © 2015 Guardian Equipment Guardian Equipment 312 447 8100 telephone...
  • Page 5 Port Sleeve Assembly Check Bonnet Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment). rev. 1215 / © 2015 Guardian Equipment Guardian Equipment 312 447 8100...
  • Page 6: Limited Warranty

    During the warranty period, Guardian Equipment will (at its discretion) repair or replace any product or part thereof, which shall be returned, freight prepaid to Guardian's factory and determined by the manufacturer to be defective in materials or workmanship.