Summary of Contents for Baker Hughes Mooney Flowgrid Slam Shut
Page 1
Mooney ™ Flowgrid Slam Shut ™ ™ 1” Valve Instruction Manual (Rev.D) Baker Hughes Data Classification : Public...
Page 2
OPERATOR ARE STRICTLY LIMITED TO THOSE EXPRESSLY PROVIDED IN THE CONTRACT RELATING TO THE SUPPLY OF THE EQUIPMENT. NO ADDITIONAL REPRESENTATIONS OR WARRANTIES BY BAKER HUGHES REGARDING THE EQUIPMENT OR ITS USE ARE GIVEN OR IMPLIED BY THE ISSUE OF THESE INSTRUCTIONS.
The 1 inch Mooney Flowgrid Slam Shut also has a throttle plate, diaphragm, and main spring. Mooney Flowgrid Slam Shut 1” valve Instruction Manual | 1 Copyright 2021 Baker Hughes Company. All rights reserved.
Slam Shut and may valve. refer to components not ordered with the Slam Shut. Consult the proper IOM for the installation of Flow- grid regulator, filters, restrictors and pilots. 4 | Baker Hughes Copyright 2021 Baker Hughes Company. All rights reserved.
Replace the bleed cap, reset cap, and clear bottom cap. (Make sure the reset pin remains in the ‘reset’ hole) Open the Upstream and Downstream block valves. Mooney Flowgrid Slam Shut 1” valve Instruction Manual | 5 Copyright 2021 Baker Hughes Company. All rights reserved.
Shutoff Test – Any unit with Underpressure Protection Close upstream and downstream block valves and vent line With Mooney Flowgrid Slam Shut units, it is recommended that pressure on inlet and outlet sides. Slam Shut should trip the overpressure protection adjustment screw be turned fully in closed when venting.
Safely release the pressure in the lines. Failure to complete these steps may result in personal injury and property damage. Mooney Flowgrid Slam Shut 1” valve Instruction Manual | 7 Copyright 2021 Baker Hughes Company. All rights reserved.
Page 10
Insert O-ring (Re-install with Lubriplate 105) Use a paper clip to remove insert O-ring.(take care not to scratch). Inspect and/or Replace the following seals • Sense diaphragm (Re-install dry) 8 | Baker Hughes Copyright 2021 Baker Hughes Company. All rights reserved.
Page 11
Slam Shut actuator block removed from plate. the body. The body does not need to be removed from the pipeline when servicing the Slam Shut or Flowgrid. Mooney Flowgrid Slam Shut 1” valve Instruction Manual | 9 Copyright 2021 Baker Hughes Company. All rights reserved.
Figure 8 - Stand Alone Slam Shut Shut downstream overpressure protection Inlet Flowgrid- Sense Line Outlet Slam Shut Sense Line Figure 10 - Pressure reducing Flowgrid with Slam Shut downstream underpressure protection 10 | Baker Hughes Copyright 2021 Baker Hughes Company. All rights reserved.
Page 13
Sense Line Slam Shut- Sense Line Outlet Figure 13 - Working Monitor with Slam Shut (4 bar) Outlet Flowgrid Sense LIne Monitor Mooney Flowgrid Slam Shut 1” valve Instruction Manual | 11 Copyright 2021 Baker Hughes Company. All rights reserved.
Plug Reset Shaft not properly tightened onto Main Shaft Reset Pin missing Rotator Shaft excessively worn or damaged Fails to Trip Closed Rotator Shaft damaged Excessive internal icing 12 | Baker Hughes Copyright 2021 Baker Hughes Company. All rights reserved.
Page 15
Notes Mooney Flowgrid Slam Shut 1” valve Instruction Manual | 13 Copyright 2021 Baker Hughes Company. All rights reserved.
Page 16
Baker Hughes reserves the right to make changes in specifications and features shown herein, or discontinue the product described at any time without notice or obligation.