DSC PowerSeries Neo Installation Manual

DSC PowerSeries Neo Installation Manual

Alarm control
Hide thumbs Also See for PowerSeries Neo:

Advertisement

To download the full installation manual and register your product, please visit:
www.DSC.com/m/29009812 or scan the QR code to the right.
Use this guide in conjunction with the PowerSeries Neo Reference Manual available online from the DSC website.
Quick Setup
1
Plan
Plan the installation including all alarm detection devices,
zone expanders, keypads and other required modules.
2
Mount
Decide on a location for the alarm panel and secure it to the
wall using suitable mounting hardware.
3
Wire
Complete all wiring including modules, zones, bells/sirens,
telephone line connections and ground connections. Record
module serial numbers on page 16.
4
Power
Connect the battery and power up the system. The battery
must be connected.
5
Enroll
Hardwired: Wire the keypad to the Corbus, power up the
First
alarm panel then press any button on the keypad. Wireless:
Keypad
Wire the HSM2Host to the Corbus, then power up the alarm
panel and a wireless keypad. Press any button on the keypad to
enroll it. The HSM2Host is then enrolled on the alarm panel.
Alternately, enroll an RF keypad.
6
Enroll
[*][8][Installer Code][902] subsection [000]. Press [*] to
begin auto-enrollment. Module slots are automatically
modules
assigned. Use scroll keys to view slots. Change slot by typing a
2-digit number.
7
Enroll
[*][8][Installer Code][804] subsection [000]. Note: An
wireless
HSM2HOST or RF keypad must be enrolled first.
devices
8
Program
Basic programming: [*][8][installer code] [001]/[002]> Zone
Type/Zone Attribute [005]>[001] Partition 1 Timers: – Entry
Delay 1 – Entry Delay 2 – Exit Delay [301]>[001] Phone #1
[310]>[000] System Account Code.
9
Test
Test the panel completely to ensure that all features and
functions operate as programmed. – [901] Walk Test – [904]
[000] Wireless Placement Test.
Compatible Devices
Throughout this document, x in the model number represents the operating
frequency of the device as follows: 9 (912-919 MHz), 8 (868MHz), 4
(433MHz).
Note: Only models operating in the band 912-919 MHz are UL/ULC listed
where indicated. Only UL approved devices are to be used with UL/ULC
listed systems.
Table 1-1 Compatible Devices
Modules
Wireless keypads
HS2LCDWFx
HS2LCDWFPx
Hardwired keypads with 2-way
HS2LCDRFx
HS2LCDRFPx
wireless integration module
Hardwired keypads
HS2LCD
HS2LCDP
HS2ICN
Touchscreen Keypad
HS2TCHP
Note: For ULC-s559 Listed applications the HS2TCHP touch screen keypad is for supplementary use
only.
2-way wireless integration module
HSM2HOSTx
8-zone expander
HSM2108
8-output expander
HSM2208
Power supply
HSM2300
4 high current output expander
HSM2204
Alternate communicator
3G2080E
3G2080RE
WARNING: This manual contains information on limitations regarding product use and function and information on the
limitations as to liability of the manufacturer. The entire manual should be carefully read.
PowerSeries Neo Alarm Control Installation Guide
UL
UL
HS2LCDWFPVx
UL
UL
UL
HS2ICNRFx
UL
UL
HS2ICNRFPx
UL
UL
HS2ICNP
UL
UL
HS2LED
UL
UL
UL
UL
UL
UL
UL
UL
TL2803GE
UL
UL
TL2803GRE
TL280E
TL280RE
LE2080(R)
TL280LE(R)
Hardwired Devices
2-wire smoke detectors
FSA-210x
FSA-210xT
y= A, B, or C
FSA-210xS
A: ULC listed models
FSA-210xST
B: UL listed models
FSA-210xLST
C: European and Australian models
4-wire smoke detectors
FSA-410x
FSA-410xT
FSA-410xS
y= A, B, or C
FSA-410xST
A: ULC listed models
FSA-410xLST
B: UL listed models
C: European and Australian models
CO detectors
CO-12/24
12-24SIR
FW-CO12
Wireless Devices
PG smoke detectors
PG smoke and heat detector
PG CO detector
PG PIR motion detectors
PG PIR + camera motion detector
PG curtain motion detector
PG dual tech motion detector
PG mirror motion detector
PG outdoor motion detector
PG glass break detector
PG shock detector
PG flood detector
PG temperature detector (indoor use)
Outdoor temperature probe (requires PGx905)
PG flat PIR
PG recessed contact
PG ceiling mount detector with Smart Presence – Short Range
PG ceiling mount detector with Smart Presence – Long Range
PG outdoor contact
PG outdoor curtain PIR
PG keys
PG panic key
PG 2-button key
PG sirens
PG repeater
PG door/window contacts
PG door/window contact w/ AUX
Central Station Receivers
SG-System I, II, III, IV, 5
Enclosures
PC5003C, PC4050CR (ULC Fire Monitoring), PC4050CAR (UL Commercial Burg), CMC-1(UL
Commercial Burg), PC4051C. Other enclosures are available to suit a variety of system configurations.
UL
TL8803G
UL
TL880LT
TL880LE
UL
PCL-422
UL
UL
FSA-210xR
UL
UL
FSA-210xRT
UL
UL
FSA-210xRS
UL
UL
FSA-210xRST
UL
UL
FSA-210xLRST
UL
UL
FSA-410xR
UL
UL
FSA-410xRT
UL
UL
FSA-410xRS
UL
UL
FSA-410xRST
UL
UL
FSA-410xLRST
UL
UL
FW-CO1224
UL
UL
CO1224
UL
UL
PGx926
UL
PGx936, PGx916
UL
PGx933, PGx913
UL
PGx904(P)
UL
PGx934(P)
UL
PGx924
PGx984(P)
UL
PGx974(P)
UL
PGx994
UL
PGx912, PGx922
UL
PGx935
UL
PGx985
UL
PGx905
PGTEMP-PROBE
UL
PGx914
UL
PGx307
UL
PGx862
UL
PGx872
UL
PGx312
PGx902
UL
PGx939
UL
PGx929
UL
PGx938
UL
PGx949
UL
PGx901
UL
PGx911
UL
PGx920
UL
PGx303, PGx975
UL
PGx945

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PowerSeries Neo and is the answer not in the manual?

Questions and answers

Summary of Contents for DSC PowerSeries Neo

  • Page 1 To download the full installation manual and register your product, please visit: www.DSC.com/m/29009812 or scan the QR code to the right. PowerSeries Neo Alarm Control Installation Guide Use this guide in conjunction with the PowerSeries Neo Reference Manual available online from the DSC website. Quick Setup TL280E...
  • Page 2: Safety Instructions For Service Personnel

    Terminal Descriptions cable(s). Do not connect alarm controller to the same electrical circuit as large appli- The following terminals are available on the PowerSeries Neo alarm controller. ances. Do not select a location that exposes your alarm controller to direct sunlight, Terminal Description excessive heat, moisture, vapors, chemicals or dust.
  • Page 3: Current Ratings

    Primary: 120V, 60Hz Class II Total (must not exceed 700mA) Secondary: 16.5VAC, 40VA Max. Note: Use DSC PTC1640CG for Canadian installations. ***See Corbus Current Calculation Chart. Warning: Do not connect the battery or transformer until all other For UL, ULC and Commercial Listed applications, the total standby and alarm wiring is complete.
  • Page 4: Additional Wiring

    PowerSeries Neo Installation Guide Note: A sealed, rechargeable, lead acid battery or gel type battery is required to Note: For ULC listed installations, use FSA-210A and FSA-410A series. meet UL requirements for power standby times. Single End-of-Line (SEOL) Resistor Connect the RED battery lead to the positive battery terminal and the BLACK When SEOL resistors are installed at the end of a zone loop, the alarm panel battery lead to the negative battery terminal.
  • Page 5: Programming Methods

    PowerSeries Neo Installation Guide Module HS2016 HS2032 HS2064/ HS2128/HS2128E HS2064E (not UL evaluated) Modules can be enrolled automatically or manually using section [902] of Installer programming. To confirm that a module has been successfully enrolled, use Installer Programming section [903].
  • Page 6: Minimum Required Programming

    PowerSeries Neo Installation Guide character and repeat the procedure as needed. Press the [#] key to save changes Set up partition account codes: and exit the program section. [310]>[001]-[008] Minimum Required Programming Set up partition timers: Once basic installation of the alarm panel is complete, the following general Entry/exit delay, settle delay –...
  • Page 7: Testing The System

    PowerSeries Neo Installation Guide means of communication between the alarm panel and the central monitoring Press [*][2] to enter the Trouble menu. On an LCD keypad, scroll to a trouble type then press [*] to view the spe- station. The alternate communicator communicates via 3G (HSPA) or Ethernet.
  • Page 8 PowerSeries Neo Installation Guide IMPORTANT! [01] Zone 001 - 128 Tamper: A wireless or hardwired zone configured for DEOL Ensure you have the following information available before contacting Customer operation is in tamper. Support : [02] Keypad 01 - 16 Tamper: A hardwired or wireless keypad is in tamper.
  • Page 9: Specifications

    (not verified by UL) System Supervision Features Transformer: DSC PTD1640U, PTC1640U,PTC1640UG, PTC1640CG The PowerSeries Neo continuously monitors a number of possible trouble Primary: 120V, 60Hz Class II conditions and provides audible and visual indication at the keypad. Trouble conditions include: Secondary: 16.5VAC, 40VA Max.
  • Page 10: Label Programming

    Press [*] to select options and [#] to exit to the previous menu. For descriptions of all programming options and programming worksheets, refer to the PowerSeries Neo Reference Manual.✔= Default Label Programming 048 –...
  • Page 11: System Options

    PowerSeries Neo Installation Guide 06 – Burglary Alarm Keypad Lockout Attempts 4 – R-Button 041 Access Code Digits 00 – 4-Digit Access Codes ✔ 07 – Open/Close (000006) 5 – Audible Bus Fault 08 – Zone Auto Bypass Keypad Lockout Duration 6 –...
  • Page 12: Event Reporting

    PowerSeries Neo Installation Guide 01 – Phone Line ✔ 06 – Device Fault Restore ✔ 211 – Miscellaneous Open/Close 331 – Module Events 1 01 – Module AC Trouble ✔ 02 – Alt Comm Auto Routing Events 401– System Test Events 01 –...
  • Page 13 PowerSeries Neo Installation Guide 011 – Maximum Dialing Attempts 3 – DLS on Event Buffer 75% 11 – Holiday 3 Repeaters (005) Full 12 – Holiday 4 Repeater Label (LCD only) 012 – PSTN Delay (003 sec.) 8 – DLS On Programming 001 - 128 –...
  • Page 14: System Information And Testing

    PowerSeries Neo Installation Guide 3 – 5th Terminal is PGM 904 Wireless Placement Test Output/Zone 001-128 – Placement Test Zones 1- 4 – Prox Tag Arm/Disarm 7 – Local Display of Temp. 521-528 – Placement Test 8 – Low Temperature Warning Repeaters 1-28 551-566 –...
  • Page 15: Zone Record

    PowerSeries Neo Installation Guide Zone Record Zone Label Location Type Attribute Zone Label Location Type Attribute - 15 -...
  • Page 16: Module Record

    PowerSeries Neo Installation Guide Zone Label Location Type Attribute Zone Label Location Type Attribute Module Record Module Type Slot Serial Number Module Type Slot Serial Number Wireless Device Record Device Type Zone Serial Number Device Type Zone Serial Number Installer-Defined Access Codes 001 –...
  • Page 17: Locating Detectors And Escape Plan

    PowerSeries Neo Installation Guide Consider the following when making your escape plans: Locating Detectors and Escape Plan Ensure all border doors and windows are easily opened. Ensure that they are The following information is for general guidance only and it is recommended not painted shut, and the locking mechanisms operate smoothly.
  • Page 18: Regulatory Approvals

    PowerSeries Neo Installation Guide must be connected to a properly installed RJ-31X jack that is electrically in series with Regulatory Approvals and ahead of all other equipment attached to the same telephone line. Proper installation FCC COMPLIANCE STATEMENT is depicted in the figure below. Consult your telephone company or a qualified installer...
  • Page 19 Note: For ULC Residential/Commercial installations set for daily test Programming transmission. The notes in the programming sections of the PowerSeries Neo Reference Wireless Supervision window shall be set to 4 hrs for Fire Installations Manual describing the system configurations for UL/ULC listed installations shall (Wireless Programming, section [804]>[802] shall be programmed with the...
  • Page 20 PowerSeries Neo Installation Guide Each of the above examples is under the sole responsibility of a single owner. The bell and DACT power supply must be in a protected area including partitioned systems. The bell and DACT power supply must be located where it can be heard by the person or persons responsible for maintaining the security system during the daily arming cycle.
  • Page 21: Aux Loading And Battery Selection

    PowerSeries Neo Installation Guide Aux Loading and Battery Selection UL Resi Fire HS2128/HS2064/ UL Residential Burg UL Home Health Care EN50131 HS2032/HS2016 UL Commercial Burg ULC Fire Monitoring ULC Residential Burg ULC Resi Fire Grade 2/Class II Board current draw 85mA...
  • Page 22 PowerSeries Neo Installation Guide SIA Feature Programming Comments Range/Default Requirement Section Range:45- 255 Exit Time Required seconds Access to Entry and Exit delays and Bell Time Out for the system. [005]>[001], option 3 (programmable) Default: 60 sec. Exit Delay Restart...
  • Page 23: Limited Warranty

    If the laws environment, usage and type. Ambient conditions such as high humidity, high or low of such a jurisdiction apply to any claim by or against DSC, the limitations and temperatures, or large temperature fluctuations may reduce the expected battery life.
  • Page 24: Motion Detectors

    PowerSeries Neo Installation Guide System Users Warning Devices A user may not be able to operate a panic or emergency switch possibly due to Warning devices such as sirens, bells, horns, or strobes may not warn people or waken permanent or temporary physical disability, inability to reach the device in time, or someone sleeping if there is an intervening wall or door.

This manual is also suitable for:

Hs2016Hs2032Hs2064Hs2064eHs2128Hs2128e

Table of Contents

Save PDF