S9360A, S9361A, S9380A, S9381A INTEGRATED BOILER CONTROLLERS
State
State
code
Wait for vent
18
damper to open
Wait for vent
19
damper to close
Wait for vent
20
damper to open –
failed closed
Wait for vent
21
damper to close –
failed open

Temperature Control

Temperature control setpoint on the module can be
adjusted as described in the following sections. Some
modules with temperature control also include a three-
digit display on the printed circuit board to facilitate
adjustments and troubleshooting.
For modules that do not include temperature control on
the module refer to the Honeywell Installation Instructions
for the specific interface module or the appliance
manufacturer's instructions. A separate automatic gas
shutoff device is not required in a system that uses this
control to meet requirements for CSA International ANSI
Z21.87 and UL 353.
The overall range of the setpoint is model-dependent but
is within 130°F to 240°F (54°C to 116°C). Select devices
may have different ranges.
Adjusting Settings for Models with
"On-Board" Display
To discourage unauthorized changing of settings, a
procedure to enter the adjustment mode is required. To
enter the adjustment mode, press the UP, DOWN, and I
buttons (see Fig. 1) simultaneously for three seconds.
Press and release the I button until the parameter
requiring adjustment is displayed.
Then press the UP or DOWN button until the parameter
has reached the desired value. After 60 seconds without
any button inputs, the control will automatically return to
the READ mode.
66-1203—05
Table 5. State Code Definitions. (Continued)
Specific Description
Damper actuator is energized and the system waits for damper to close
Damper actuator is de-energize and the system waits for damper to open
Damper actuator is energized, system waits for damper to open, but the damper is stuck
in closed position (damper end switch is open)
Damper actuator is de-energized, system waits for damper to close, but the damper is
stuck in open position (damper end switch is closed)
Display
In the RUN mode, status items and parameters are
viewable.
To read settings, press and release the I key to find the
parameter of interest. For example, press and release I
until setpoint (sp) is displayed, followed by a three-digit
number, i.e., 220, followed by °F or °C. See Display
Readout, Fig. 7.
TEXT
DESCRIPTION
STA
STATUS (SEE STATUS NUMBERS)
BT
BOILER TEMPERATURE
SP
OPERATING SETPOINT
HL
HIGH LIMIT SETPOINT
HDF
DIFFERENTIAL SETPOINT
FLA
FLAME CURRENT
RUN
RUN TIME HOURS
CYC
BOILER CYCLES
ERR
ERROR (SEE ERROR NUMBERS)
Fig. 7. Display readout parameters.
12
General
Description
DISPLAY
SHOWS
M33683