Selection Benefits; Wide Range Of Utopia Outdoor Units - Hitachi UTOPIA R32 Series Technical Catalogue

Table of Contents

Advertisement

2  Features and benefits
Selection benefits

Basic combinations (Example of 2 indoor units system)
Operating line
Remote control line
Tset (Setting)
Individual setting
Running ON/OFF
Individually
(indoor unit)
Thermo-ON/OFF
Individually
Optional
Individually
functions setting
Application
Multiple rooms
(examples)

Flexible combinations for Individual Operation (Combination example by using Individual
Operation Function)
These configurations are to be used with UTOPIA IVX Prime. 
Operating line
Remote control line

Decreased defrosting operation time and extended heating operation time by control depending
on amount of frost
The amount of frost can be estimated from the length of last defrosting. If the amount of frost is less than the last time, 
then heating operation until next defrosting operation is extended automatically. As a result, unnecessary defrosting 
operation is avoided, increasing availability of continuous heating operation.

2.4 Selection benefits

2.4.1 Wide range of UTOPIA outdoor units

UTOPIA Prime / UTOPIA IVX Prime R32 RAS-H(V)R(C/P)2E
UTOPIA Prime / UTOPIA IVX Prime R410A RAS-H(V)N(C/P)2E
24
UTOPIA IVX Prime
Operating line
Remote control line
and operating cable
for remote control
Tset1
Tset2
All Indoor units same setting
Simultaneously
Individually
(both indoor units linked to 
same Tset)
Individually
Large open space with non 
homogeneous load demand 
Multiple rooms with same 
Tset
Tset1
Tset2
Flexible combinations are realized by using the remote control switches
Defrosting operation
Heating Operation 
Heating Operation 
Time (t)
Estimate
Amount of Frosting
Series
TCGB0136 rev.1 - 05/2021
Operating line
Remote control line
Tset1
All Indoor units same setting
Simultaneously
Simultaneously
(all units Thermo-ON if none 
of them reached Tset)
Simultaneously
All units same setting
Large open space
Operating line
Tset1
Tset2
Tset3
Defrosting operation
Time (t)
If the amount of frosting is 
less than the last time, the 
heating operation is extended
Power Supply
1~ 230V 50Hz
3N~ 400V 50Hz
1~ 230V 50Hz
3N~ 400V 50Hz
UTOPIA Prime
Operating line
Remote control line
and operating cable
for remote control
Tset1
All Indoor units same setting
Simultaneously
Simultaneously
(all units Thermo-ON if none 
of them reached Tset)
Individually
Large open space
Remote control
line
3HP
4HP
5HP
Tset1
6HP