FireClass Precept EN Panel Installation & Commissioning Manual

FireClass Precept EN Panel Installation & Commissioning Manual

Hide thumbs Also See for Precept EN Panel:
Table of Contents

Advertisement

EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
©Johnson Controls.Tyco Fire & Security GmbH, Victor von Bruns-Strasse
21, 8212 Neuhausen am Rheinfall, Switzerland
Installation & Commissioning Manual
FIRECLASS PRECEPT EN
FIRECLASS PREC EN INST
3
13/09/18
Precept EN Fire Detection/Alarm Panel
& Precept EN Repeater
PAGE 1 of 30

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Precept EN Panel and is the answer not in the manual?

Questions and answers

Summary of Contents for FireClass Precept EN Panel

  • Page 1 FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: ©Johnson Controls.Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland Precept EN Fire Detection/Alarm Panel & Precept EN Repeater Installation & Commissioning Manual...
  • Page 2: Table Of Contents

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: List of Contents ..........2 15.7 C IST OF IGURES ONFIGURABLE PTIONS VIA SWITCH ..........2 SELECTION ON EPEATER NTERFACE OARD IST OF ABLES ..............25 ..........
  • Page 3: Introduction

    Introduction Installation and Commissioning Overview The FIRECLASS Precept EN range of panels have been designed, manufactured and tested to meet This section lists the steps that are taken in the requirements of BSEN 54 Parts 2 & 4 and will...
  • Page 4 FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: Figure 2 – Precept EN 8/16 Zone Internal View 3 x Enclosure Mains fixing holes warning/ Secondary earth bar Cable clip for primary for cable screens...
  • Page 5 FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: Figure 4 – 2/4 Zone Precept EN panel - General Assembly (with optional clock module) PAGE 5 of 30...
  • Page 6: Panel - General )

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: Figure 5 – 8/16 Zone Precept EN panel - General Assembly (with optional clock module) PAGE 6 of 30...
  • Page 7: Panel - General )

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: Figure 6 – 32 Zone Precept EN panel - General Assembly (with optional clock module) PAGE 7 of 30...
  • Page 8: Typical Wiring Schematic

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: Typical wiring schematic – 16 Zone Figure 7 – Typical Wiring Diagram PAGE 8 of 30...
  • Page 9: Circuit Connection Details

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: Circuit Connection Details 7.1 2-16 Zone Motherboard Termination Details Figure 8 – C1627 Field Termination Inputs: Outputs: SIL = Silence alarms DIS = Disablement active EVAC = Evacuate...
  • Page 10: Zone Expansionb

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: C1627 Motherboard Features Figure 10 illustrates the motherboard features referred to elsewhere in the documentation. Figure 10 – C1627 Motherboard Layout Remote Inputs: Aux Outputs: Silence Alarms...
  • Page 11: C1632 16 Zone Expansion

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: C1632 16 Zone Expansion Board Features Figure 11 – C1632 16 Zone Expansion Board Connector for Detection zone motherboard terminals for ribbon zones 17 - 32 ...
  • Page 12: Zone Panel Power

    13/09/18 ISSUE No. & DATE: 10.3 32 zone Panel Power Supply Details Figure 12 shows the layout of the 32 zone Precept EN panel power supply. Figure 12 – 32 Zone Panel Power Supply Layout Secondary AC Supply from Transformer...
  • Page 13: Installation

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: highly corrosive substance, and presents significant Installation danger to you and to anything else it touches. In The control panel must be installed by suitably case of accidental skin or eye contact, flush the...
  • Page 14: Installation Instructions

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: 11.2 Installation Instructions 9. Remove the chassis from the enclosure and place carefully to one side. 1. Carefully remove the control panel from the NOTE: The door and chassis both contain packing and lay the panel on a flat surface.
  • Page 15: Optional C1631 R

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: 21. Reinstallation of the chassis is the reverse of 26. Connect the blue battery lead between the removal. Reconnect all wires and ensure none positive (red) terminal of the left-hand battery are trapped between the chassis and backbox.
  • Page 16: Commissioning

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: iii) Functional testing of all circuits and field devices Commissioning to check each circuit and function in turn to ensure correct operation of the entire system.
  • Page 17: Commissioningp

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: 12.6 Configuration terminals at this stage. Remember to remove any links fitted to detector bases. Be very careful 12.6.1 Basic Default Configuration to maintain correct polarity at each device.
  • Page 18: 12.7.3 Class Change Input

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE:  The internal buzzer sounds. o Remove the circuit faults, restoring the circuit to the healthy condition and confirm that the  The fault relay operates.
  • Page 19: 12.7.6 Ancillary Inputs

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: interface relay adjacent the fire protection the alarms operate and the internal buzzer equipment. operates on all repeaters. 3. Press the “Silence” button on the fire alarm 4.
  • Page 20: User Indications

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: User Indications General Indicator Section Description Colour Operating Condition Power Supply On Green Illuminates Steady for Mains or Standby power On. Flashes on any new fire alarm condition, changing to a steady Fire indication on operation of Silence Alarms.
  • Page 21: User Controls

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: User Controls POWER SUPPLY ON EVACUATE TEST DISPLAY FIRE FIRE ROUTING ACTIVE SILENCE/ GENERAL FAULT RESOUND ENABLE ALARMS POWER SUPPLY FAULT SYSTEM FAULT RESET DISABLE EARTH FAULT...
  • Page 22: Operating The Engineer

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: Operating the Engineer’s 2. Select a zone or output to be configured: o On the panel display, press the Select On/Off functions switch to enable the Select Mode.
  • Page 23: T Orestore The Factory

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE:  To clear the invalid condition check the zone INPUTS ARE IN PERMANENT RESET AND OUTPUTS ARE INHIBITED - THE PANEL and output config switches [1/4, 1/5, 1/6, 1/7, WILL NOT RESPOND TO ANY FIRE ALARM.
  • Page 24 FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE:  SW 1/5 - Config I/S Zones: 9 minutes. See Table 1 – Motherboard Delay Switch Settings o OFF: Configuration mode disabled. o ON: Enables selected zones to be configured Table 1 –...
  • Page 25: Configurable Options Via Selection On Repeater

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE:  SW 2/8 - Silent Zone Test: 15.8 Configuring the Fire Routing, Fire Protection and Fault routing O/Ps Select sounder response in One Man [Detector] To configure the Fire Routing Output to volt-free Test Mode: relay contacts, remove links J10, J11 and J12.
  • Page 26 FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: On the rear of the Clock Module PCB, move the Press ENABLE (+) or DISABLE (-) to change SS DIL switch 1, pole 1 on to the ON position.
  • Page 27: Configuring The Clock

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: Table 4 – C1651 Clock Module DIL Switch and 16.2 Configuring the Clock Module Link Settings The Clock Module is configured by setting Link 1 and DIL switch 1, both located on the rear of the...
  • Page 28: Clock Module Errorm

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: 16.3 C1651 Clock Module PCB Features Figure 14 llustrates the PCB features referred to elsewhere in the documentation Figure 14 – C1651 Clock Module PCB LK1 - Select...
  • Page 29: Rom Checksum Error 17. Mechanical , Electrical & E Specification

    FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: Mechanical, Electrical & Environmental Specification Mechanical Precept EN Panel Repeater Specification 2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone Size [mm]...
  • Page 30 FIRECLASS PRECEPT EN EQUIPMENT: FIRECLASS PREC EN INST PUBLICATION: 13/09/18 ISSUE No. & DATE: Precept EN Panel Repeater Battery Specification 2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone Battery charger output: [Temperature compensated float 1.5A...