Main PCB detects
Unit will stop
voltage/current errors
operating.
on output waveform
or current read-out.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
1 Perform a check of the main PCB. See
page 106.
Possible cause: Faulty main PCB or wrong capacity setting.
2 Perform a check of the inverter PCB A3P. See
PCB" on
page 99.
Possible cause: Faulty inverter PCB A3P or non‑compatible
inverter PCB.
3 Perform a check of the compressor. See
page 82.
Possible cause: Faulty compressor.
4 Check if the power supply is conform with the regulations. See
"4.1 Electrical circuit" on
page 130.
Possible cause:
▪ Faulty or disturbance of the power supply (imbalance
>10%),
▪ Power drop,
▪ Short circuit.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
2.3.61
L1-04-10-14 – Power transistor error on
inverter PCB A3P
Main error code
Sub error code
L1
04
10
14
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple
outdoor unit configurations. Main outdoor unit is the unit to
which F1‑F2 IN transmission line is connected. Main, Sub
1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Main PCB detects
Unit will stop
voltage/current errors
operating.
on output waveform
or current read-out.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
1 Perform a check of the main PCB. See
page 106.
Possible cause: Faulty main PCB or wrong capacity setting.
2 Perform a check of the inverter PCB A3P. See
PCB" on
page 99.
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ Heat Pump
ESIE18-14 – 2019.07
Reset
Manual reset via user
interface.
3 Perform a check of the compressor. See
Power reset at
outdoor unit.
4 Check if the power supply is conform with the regulations. See
"3.9 Main PCB" on
"3.8 Inverter
2.3.62
"3.2 Compressor" on
Main error code
L1
Trigger
Main PCB detects
voltage/current errors
on output waveform
or current read-out.
Unit
To solve the error code
Main
Sub 1
Sub 2
1 Perform a check of the main PCB. See
2 Perform a check of the inverter PCB A3P. See
Reset
Manual reset via user
interface.
3 Perform a check of the compressor. See
Power reset at
outdoor unit.
4 Check if the power supply is conform with the regulations. See
"3.9 Main PCB" on
"3.8 Inverter
Possible cause: Faulty inverter PCB A3P or non‑compatible
inverter PCB.
page 82.
Possible cause: Faulty compressor.
"4.1 Electrical circuit" on
page 130.
Possible cause:
▪ Faulty or disturbance of the power supply (imbalance
>10%),
▪ Power drop,
▪ Short circuit.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
L1-05-15-16 – Inverter PCB A3P hardware
fault
Sub error code
05
15
16
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple
outdoor unit configurations. Main outdoor unit is the unit to
which F1‑F2 IN transmission line is connected. Main, Sub
1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Effect
Unit will stop
operating.
INFORMATION
It is recommended to perform the checks in the listed
order.
page 106.
Possible cause: Faulty main PCB or wrong capacity setting.
PCB" on
page 99.
Possible cause: Faulty inverter PCB A3P or non‑compatible
inverter PCB.
page 82.
Possible cause: Faulty compressor.
"4.1 Electrical circuit" on
page 130.
Possible cause:
▪ Faulty or disturbance of the power supply (imbalance
>10%),
▪ Power drop,
▪ Short circuit.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
2 Troubleshooting
"3.2 Compressor" on
Unit
Main
Sub 1
Sub 2
Reset
Manual reset via user
interface.
Power reset at
outdoor unit.
"3.9 Main PCB" on
"3.8 Inverter
"3.2 Compressor" on
Service manual
35