1MRK 511 451-UEN Rev. C
Section 3
3.1

Introduction

An interface is available for connecting the numerical busbar protection to a station
automation system or station monitoring system (SCS/SMS).
For an overview of REB500's communication interfaces, see the
In contrast to feeder control and protection bay units, REB500 is equipped with only a single
interbay bus interface via which all the REB500 bay units in the entire station communicate.
This has to be taken into account by the various bus protocols.
3.2

Basic configuration

The fourth octet in the Data Unit Identification field of an ASDU determines the common
address of ASDU. It normally has to be the same as the station address on the link layer.
Exceptions are permitted where additional common ASDU addresses are needed because of
multiple instances of functions.
In case of REB500, this exception allowed in the IEC recommendation is used to be able to
address the Central Unit and the Bay Units via a single physical connection.
Common Address of ASDU – CAA
Basic setting:
0
1-60
255
The dialog for configuring the communication is accessed by selecting HMI500
Configuration/Communication/SCS Configuration.
Distributed busbar protection REB500
Communication protocol manual IEC 60870-5-103

Interbay bus functions

This document applies for IEC 60870-5-103. However,
document also contains information of a second IBB using IEC 61850-8-1 if
configured.
Central Unit
Bay Units
Global address
© 2019 - 2020 Hitachi Power Grids. All rights reserved
Interbay bus functions
GUID-FC8C1289-F943-4E92-A50E-BDA7281A5337 v1
GUID-7A41F2A2-F366-4D30-9D76-BB6279380110 v3
Operation manual .