SEL-2414 Transformer Monitor
Complete System for Control and Monitoring

Major Features and Benefits

The SEL-2414 Transformer Monitor provides an exceptional combination of monitoring, control, and communications
in a compact package.
Thermal Monitoring and Metering Capabilities. Safeguard transformers from overheating by tracking thermal
conditions. Track the minimum and maximum transformer top oil temperature, hot-spot temperature, and as many
as 10 RTDs or thermocouples. Calculate hot-spot temperature according to the IEEE C57.91-2011 or the
IEC 60076-7:2018 Ed. 2 standards.
Load Tap Position And Control Monitoring. Monitor tap position and raise and lower controls and as many as
32 tap positions by using digital inputs in the binary-coded decimal (BCD) or binary format.
High Reliability, Rugged Design, and Low Price. Apply the SEL-2414 in harsh physical and electrical environ-
ments. The SEL-2414 withstands vibration, electrical surges, fast transients, extreme operating temperatures from
–40° to +85°C, and meets stringent utility standards. Compare our superior specification compliance, higher reli-
ability, lower price, and worldwide, ten-year warranty to other transformer monitor alternatives.
Flexible I/O for Transformer Status, Alarms, and More. Take advantage of input/output options including dig-
ital inputs for status such as oil level and sudden pressure; RTD and thermocouple inputs for measurements such as
ambient, top-oil, and hot-spot temperatures; digital outputs for control and alarms; analog inputs and outputs; and
ac current and voltage inputs. Easily program monitoring and control functions with powerful logic, math, timers,
counters, and edge-trigger functions. These features allow easy integration with new and retrofit transformer mon-
itor applications. Monitor critical substation assets with comprehensive transformer thermal and through-fault
monitoring.
Schweitzer Engineering Laboratories, Inc.
SEL-2414 Data Sheet

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SEL-2414 and is the answer not in the manual?

Questions and answers

Summary of Contents for Sel SEL-2414

  • Page 1 32 tap positions by using digital inputs in the binary-coded decimal (BCD) or binary format. High Reliability, Rugged Design, and Low Price. Apply the SEL-2414 in harsh physical and electrical environ- ments. The SEL-2414 withstands vibration, electrical surges, fast transients, extreme operating temperatures from –40°...
  • Page 2 Figure 1 shows the SEL-2414 functionality. Apply flexible I/O options to meet the many needs of new or retrofit transformer installations. The SEL-2414 includes four slots for plug-in I/O cards. Use digital inputs (DI) to monitor critical transformer alarms and status points. Use analog inputs (AI) to measure pressure, oil level, temperatures, tap positions, and process-level signals (e.g., 4–20 mA,...
  • Page 3 OLTC Tank Oil Bottom Oil Temperature Sensors LTC Tank Oil Temperature OLTC Tap Position OLTC Motor Current Load Voltage (3 for 1) Load Current (3 for 1) Figure 2 Monitoring Inputs and Control Outputs Schweitzer Engineering Laboratories, Inc. SEL-2414 Data Sheet...
  • Page 4 Record analog and digital waveforms at 32 samples/cycle for as many as 64 power system cycles, approximately 1 s. Use the event report to move the oscillographic data to your PC. You can plot your event report data with the SEL-5601-2 ® Event Software or with Microsoft Excel.
  • Page 5 SEL-2414 can receive temperature data at any rate, the thermal element uses the temperature data once per =>>CPR <Enter> "REC_NUM","YEAR","MONTH","DAY","HOUR","MIN","SEC","MSEC","VA_MAG","VB_M minute. AG","VC_M AG","AI301","AI302","AI303","AI304","AI305","AI306","1D7A" 14,2005,9,1,12,10,4,261,2092.127,2099.499,2089.107,-0.001,-0.000, -0.001,-0.001,- The thermal element operates in one of three modes, 0.001,-0.001,"1190" 13,2005,9,1,12,15,3,982,2093.966,2099.176,2088.974,-0.001,-0.001, depending upon the presence or lack of measured -0.001,-0.000,-...
  • Page 6 Load Tap Position and Control Commissioning Monitoring The SEL-2414 front panel simplifies commissioning and The SEL-2414 supports load tap position and control troubleshooting: (LTPC) monitoring by using digital inputs in the View field data and calculated values binary-coded decimal (BCD) or binary format. It can...
  • Page 7 Configuration and Commissioning Software The included QuickSet software program simplifies device configuration in addition to providing ERATOR commissioning and analysis support for the SEL-2414. Access settings creation help online. Use the PC interface to remotely retrieve reports and other system data.
  • Page 8 Metering The SEL-2414 provides extensive metering capabilities. See Specifications for metering and power measurement accuracies. As shown in Table 1, metering includes current and voltage based metering and analog input, math variable, and remote analog metering. Fundamental, maximum and minimum, and demand metering typically includes phase voltages and currents;...
  • Page 9 Automation Flexible Control Logic and Integration Features Replaces Traditional Temperature Gauges The SEL-2414 is equipped with as many as four inde- pendently operated serial ports: one EIA-232 port on the Replace traditional temperature gauges that show the front, one EIA-232 or EIA-485 port on the rear, one...
  • Page 10 EIA-232 or Fiber Optic - Modbus RTU - DNP3 Level 2 Slave Metallic or Fiber-Optic Serial Cable SEL-3555 - SEL ASCII - SEL Fast Message, Fast SER - SEL Fast Meter, Fast Operate SEL-351 SEL-351 SEL Relay SEL Relay SEL-2414...
  • Page 11 IRIG-B, EIA-232 Slot C 8 DI Slot D 10 RTD Slot E 3 CT/3 PT 8 DO Slot Z (A) Rear-Panel Layout (B) Side-Panel Input and Output Designations Figure 12 Rear-Panel Connections and Labels Schweitzer Engineering Laboratories, Inc. SEL-2414 Data Sheet...
  • Page 12 Dimensions Figure 13 SEL-2414 Panel-Mount Figure 14 SEL-2414 Surface-Mount Dimensions SEL-2414 Data Sheet Schweitzer Engineering Laboratories, Inc.
  • Page 13 100 A CMRR Typical: 65 db at 60 Hz (according to IEC 60255 Rated Frequency: 50/60 ±5 Hz 50/60 ±5 Hz Burden (per phase): < 0.050 VA < 0 .002 VA Measurement Category: Schweitzer Engineering Laboratories, Inc. SEL-2414 Data Sheet...
  • Page 14 < 3 s Withstand Voltage CMRR (typical): 100 dBv 4000 V Noise Rejection: Up to 1 Vrms 50/60 Hz Isolation SEL-2414 Digital Input Derating Number of Banks: Two Banks (5 channels each) Max. Working Common Mode: 250 Vdc Cold Junction Compensation:...
  • Page 15 MOV Protection ~1 Km with 200 µm (maximum voltage): 250 Vac/330 Vdc Data Rate: 5 Mb < 50 µs, resistive load Pickup Time: Typical Fiber Dropout Time: 8 ms, resistive load Attenuation: –4 dB/Km Schweitzer Engineering Laboratories, Inc. SEL-2414 Data Sheet...
  • Page 16 ±1% typical, 25°C, 60 Hz, nominal Ymodem file transfer on the front and rear port voltage and current Xmodem file transfer on the front port Power Factor SEL ASCII and Compressed ASCII SEL Fast Meter Three-Phase SEL Fast Operate (wye connected): ±1% typical, 25°C, 60 Hz, nominal...
  • Page 17 EMC Immunity Electrostatic Discharge Immunity: IEC 60255-22-2:2008 IEC 61000-4-2:2008 Severity Level 4 8 kV contact discharge 15 kV air discharge Radiated RF Immunity: IEC 60255-22-3:2007 IEC 61000-4-3:2010 10 V/m IEEE C37.90.2-2004, 35 V/m Schweitzer Engineering Laboratories, Inc. SEL-2414 Data Sheet...
  • Page 18 Technical Support We appreciate your interest in SEL products and services. If you have questions or comments, please contact us at: Schweitzer Engineering Laboratories, Inc. 2350 NE Hopkins Court Pullman, WA 99163-5603 U.S.A. Tel: +1.509.338.3838 Fax: +1.509.332.7990 Internet: selinc.com/support Email: info@selinc.com SEL-2414 Data Sheet Schweitzer Engineering Laboratories, Inc.
  • Page 19 Notes Schweitzer Engineering Laboratories, Inc. SEL-2414 Data Sheet...
  • Page 20 All brand or product names appearing in this document are the trademark or registered trade- 2350 NE Hopkins Court • Pullman, WA 99163-5603 U.S.A. mark of their respective holders. No SEL trademarks may be used without written permission. Tel: +1.509.332.1890 • Fax: +1.509.332.7990 SEL products appearing in this document may be covered by U.S.

Table of Contents