1. Technical Specifications
Product Type:
Operating Voltage:
HF System:
Transmission Power:
Rated Load:
Detection Angle:
Power Consumption:
Detection Range :
Time Setting:
Mounting:
Light Control:
Working Temperature:
*For usage in -35°C ~ -20°C enviroment, please refer to www.hytronik.com/download
->knowledge ->Microwave Sensors - Precautions for Product Installation and Operation
point 4) for more information.
2. Dimensions (mm)
Daylight sensor
Antenna module
Detection area
Hold-time
Daylight threshold
65
71.7
80.5

3. Functions

1. Lux Off Function
The built-in daylight sensor can measure ambient natural light and switch off the fixture
automatically whenever artificial light is not required (natural light lux level exceeds daylight
threshold).
2. Zero-cross Relay Operation
Designed in the software, the sensor switches on/off the load right at the zero-cross point, to
ensure the in-rush current is minimised, enabling the maximum life-time of the relay.
3. Loop-in and Loop-out Terminal
Double L N terminal makes it easy for wire loop-in and loop-out, and saves the cost of
terminal block and assembly time.
Installation and Instruction Manual
ON/OFF Control Microwave Motion Sensor
Against wireless signals interference
220-240VAC 50/60Hz
5.8GHz CW radar
< 0.2mW
800W (resistive load)
400VA (capacitive load)
30~150°
< 0.5W
Max. 10 meters in diameter, adjustable
5s ~ 30 min.
Indoors, Ceiling & walling mounted
2~50 lux, disable
*
-35 ~ +70°C
Intallation hole
L'
N
N
L
4. Wiring Diagram
To connect several standard control gear with 1 sensor (ON/OFF function), the
wiring should be.
N
L
L
N N
L'
With Tridonic switchDIM ballast / driver ( Excel ballast/driver, corridor function) ,
this sensor can also achieve tri-level dimming control:
N
L
L
N N
L'

5. Settings

Detection Range
This determines the effective range of the motion detector and is set by DIP
switches at the sensor itself, refer to figure. Note that reducing the sensitivity
will also narrow the detection range. The following settings are available.
I - 100%
1 2 3
II - 75%
III - 50%
IV - 30%
V - Sensor OFF
Hold Time
Select the dip switch configuration for the full brightness on-time after presense
detection. Please note that this function is disabled when the natural daylight
exceeds the daylight threshold setting more than 5 minutes.
I - Walk test mode 5s
II - 30s
4 5 6
III - 1 minute
IV - 5 minutes
V - 20 minutes
VI - 30 minutes
Daylight Sensor
This setting holds off the 100% light output should there sufficient daylight and
is set using DIP switches at the sensor, refer to figure. The following settings are
available.
I - Disable
7 8 9
II - 50 lux
III - 20 lux
IV - 5 lux
V - 2 lux
* In disable mode the fixture(s) will always be on with motion detection
regardless of the ambient lux level.
N
Control gear
L
N
Control gear
L
N
Control gear
L
Switch-dim.
N
Control gear
L
Switch-dim.
N
Control gear
L
Switch-dim.
N
Control gear
L
HC005S/I-20210128-A0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HC005S/I and is the answer not in the manual?

Questions and answers

Summary of Contents for Hytronik HC005S/I

  • Page 1 2~50 lux, disable Switch-dim. Working Temperature: -35 ~ +70°C Control gear *For usage in -35°C ~ -20°C enviroment, please refer to www.hytronik.com/download Switch-dim. ->knowledge ->Microwave Sensors - Precautions for Product Installation and Operation Control gear L’ point 4) for more information.
  • Page 2 The fixture is on when it should not Adjust zone, change installation site snow) or air expelled from fans, or open windows Hytronik Industrial Ltd. | www.hytronik.com 3rd Floor, block C, complex building, 155#, Bai'gang road south, Bai'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023...

Table of Contents