Amerex HALOTRON BRX 337 Owner's Maintenance Manual

Amerex HALOTRON BRX 337 Owner's Maintenance Manual

Portable extinguishers

Advertisement

Quick Links

All fire extinguishers should be installed, inspected and maintained in accordance with the National Fire
Protection Association standard titled "Portable Fire Extinguishers", NFPA-10 or the National Fire Code of
Canada and the requirements of local authorities having jurisdiction.
When maintenance is indicated, it should be performed by trained persons having proper equipment. Fire
extinguishers are pressure vessels and must be treated with respect and handled with care. They are
mechanical devices and require periodic maintenance to be sure that they are ready to operate properly and
safely. Amerex strongly recommends that the maintenance of portable fire extinguishers be done by a trained
professional – your local authorized Amerex Distributor.
Amerex Corporation makes original factory parts available to ensure proper maintenance – USE OF
SUBSTITUTE PARTS
machined surfaces and threads which are manufactured to exacting tolerances. All parts meet precise
specifications and are subjected to multiple in-house inspections and tests for acceptability. There are
substitute parts available which are incorrectly labeled as U/L component parts, some are advertised as
Amerex type. None of these meet U/L requirements. Use of substitute parts voids the Amerex extinguisher
warranty and U/L listing. DO NOT SUBSTITUTE.
REFERENCES IN THIS MANUAL:
NFPA-10 Portable Fire Extinguishers
CGA C-6 Standard for Visual Inspection of
Compressed Gas Cylinders
CGA C-6.3 Standard for Visual Inspection of
Low Pressure Aluminum Alloy Compressed
Gas Cylinders
REMOVE FROM SERVICE AND REPLACE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE.
AMEREX CORPORATION DOES NOT SERVICE OR MAINTAIN FIRE EXTINGUISHERS. THIS MANUAL
IS PUBLISHED AS A GUIDE TO ASSIST QUALIFIED SERVICE PERSONNEL IN THE INSPECTION AND
MAINTENANCE OF AMEREX FIRE EXTINGUISHERS ONLY. NO INSTRUCTION MANUAL CAN
ANTICIPATE ALL POSSIBLE MALFUNCTIONS THAT MAY BE ENCOUNTERED IN THE SERVICE OF
FIRE EXTINGUISHERS. DUE TO THE POSSIBILITY THAT PRIOR SERVICE PERFORMED ON THIS
EQUIPMENT MAY HAVE BEEN IMPROPERLY DONE, IT IS EXTREMELY IMPORTANT THAT ALL
WARNINGS, CAUTIONS AND NOTES IN THIS MANUAL BE CAREFULLY OBSERVED. FAILURE TO
HEED THESE INSTRUCTIONS COULD RESULT IN SERIOUS INJURY. AMEREX ASSUMES NO
LIABILITY FOR SERVICE OR MAINTENANCE OF FIRE EXTINGUISHERS BY PUBLISHING THIS
MANUAL
P/N 27192
OWNER'S MAINTENANCE MANUAL
INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS
RELEASES AMEREX OF ITS WARRANTY OBLIGATIONS. Amerex parts have
HALOTRON BRX® PORTABLE EXTINGUISHERS
MODELS 337, 347, 349 AND 351
AVAILABLE FROM:
National Research Council Canada, 1200 Montreal Road,
Building M-58 Ottawa, ON K1A 0R6 Canada
National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169-7471
Compressed Gas Association, 14501 George Carter Way,
Chantilly, VA 20151-2923
NO. 27192
4/2021

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HALOTRON BRX 337 and is the answer not in the manual?

Questions and answers

Summary of Contents for Amerex HALOTRON BRX 337

  • Page 1 Amerex strongly recommends that the maintenance of portable fire extinguishers be done by a trained professional – your local authorized Amerex Distributor.
  • Page 2 INTRODUCTION ® This manual covers specific instructions for Amerex Halotron BrX hand portable extinguishers. Special ® maintenance instructions contained in this manual apply to these extinguishers only. Halotron BrX “Clean Agent” extinguishers are designed for Class A, B and C hazards formerly protected with Halon 1211 extinguishers.
  • Page 3 2. Inspect the extinguisher for damaged, missing or substitute parts. Only factory replacement parts are approved for use on Amerex fire extinguishers. 3. Weigh extinguisher and compare with weight printed in the Maintenance section on the nameplate.
  • Page 4 If bent, damaged or improper gauge, replace extinguisher. If pressure is low or high and temperature/pressure relationship has been ruled out: 1. Low pressure – check for leaks. Contact Amerex if under warranty; otherwise remove and replace extinguisher. 2. High pressure (over pressurized or over charged) — Contact Amerex if under warranty;...
  • Page 5 PARTS LIST ® 1.92 lb. Halotron BrX Extinguisher Model 337 ITEM # PART # DESCRIPTION 01387-P SEAL TAMPER (REPL YELLOW) SALES 01532-P ORING NOZ HOSE END SALES 16354-P PULL PIN & CHAIN ASY SM SS SALES 27293-P BKT ASY 899 BTP RD SALES 27440 NOZ ANOD .113 BRX P/N 27192...
  • Page 6 PARTS LIST ® 3.75 lb. Halotron BrX Extinguisher Model 347 ITEM # PART # DESCRIPTION 01387-P SEAL TAMPER (REPL YELLOW) SALES 01532-P ORING NOZ HOSE END SALES 16354-P PULL PIN & CHAIN ASY SM SS SALES 25261-P BKT ASY 898 BRX RD SALES 25627 NOZ .161 ANOD AL BRX P/N 27192...
  • Page 7 PARTS LIST ® 3.75 lb. Halotron BrX Extinguisher Model 349 ITEM # PART # DESCRIPTION 01387-P SEAL TAMPER (REPL YELLOW) SALES 01532-P ORING NOZ HOSE END SALES 15747-P STRAP ASY BK 3/8”X5” SALES 16354-P PULL PIN & CHAIN ASY SM SS SALES 25261-P BKT ASY 898 BRX RD SALES 27189-P...
  • Page 8 PARTS LIST ® 12.5 lb. Halotron BrX Extinguisher Model 351 ITEM # PART # DESCRIPTION 01387-P SEAL YAMPER (REPL YELLOW) SALES 05525-P BKT WALL 820 RD AL 10 SALES 06978-P ORING BR VLV HOSE SALES 12932 BKT ASY 809 BK 5” VEH 13888-P PULL PIN &...