• Near heat sources or strong electromagnetic interferences Disclaimer Vertiv disclaims any and all responsibility or liability for the defects or malfunction caused by: • Application range or operating environment outside the specifications • Unauthorized modification, improper installation or operation •...
Vertiv™ Liebert EXS 80kVA UPS User Manual Safety Precaution This manual contains information concerning the installation and operation of the Liebert EXS 80kVA UPS. Read this manual thoroughly before installing, using and servicing the UPS. To reduce the chance of accident, please read the safety precautions very carefully before operation. The 'Caution, Note, Warning' in this user manual and on the product do not represent all the safety points to be observed, and are only supplement to various safety points.
Page 11
Vertiv™ Liebert EXS 80kVA UPS User Manual WARNING! High earth leakage current 1. Earth connection is critical before connecting the input supply (including both mains supply and battery). 2. Earth leakage current is less than 2500mA. 3. Transient and steady state earth leakage currents, which may occur when the equipment is started, should be taken into account in the selection of instantaneous RCCBs or RCD devices.
Page 12
Vertiv™ Liebert EXS 80kVA UPS User Manual This page is intentionally left blank. Safety Precaution...
Vertiv™ Liebert EXS 80kVA UPS User Manual 1 Overview The Liebert® EXS 80 kVA UPS (UPS for short) is a monolithic transformer-free UPS which delivers reliable and high-quality AC power for mission critical application such as data centers, computers, communication systems, healthcare, railway, and process &...
Vertiv™ Liebert EXS 80kVA UPS User Manual 1.2 Design Concept 1.2.1 System Design This section introduces the working principle of the UPS single module. The UPS adopts AC-DC-AC converter (as shown in Figure 1-1). The first stage conversion (AC-DC) adopts three-phase high frequency rectifier to convert the three-phase input voltage into stable DC bus voltage.
Vertiv™ Liebert EXS 80kVA UPS User Manual 1.2.2 Bypass Through the intelligent control of the 'Bypass Automatic Switch' (as shown in Figure 1-1), the loads can be supplied by the inverter or the bypass. In normal situation, the loads are supplied by the inverter, in which case the automatic inverter switch at inverter side is closed.
Vertiv™ Liebert EXS 80kVA UPS User Manual UPS module failure In case of inverter failure and output fuse blowout, the load will automatically transfer to the bypass, and the output power supply will not be interrupted. In this situation, please contact the local customer service center of Vertiv for technical support.
Vertiv™ Liebert EXS 80kVA UPS User Manual 1.3.2 Parallel System Requirements A group of paralleled modules behave as if it were one large UPS with the advantage of presenting higher reliability. To ensure that all modules are equally utilised and to comply with relevant wiring rules, the following requirements apply: 1.
Page 19
Vertiv™ Liebert EXS 80kVA UPS User Manual Battery mode Upon mains failure or voltage out of range, the rectifier and internal charger will stop running, and the battery will supply power to the load through the inverter. When the mains is recovered, the system will automatically transfer back to the normal mode without any manual intervention, and the power to the load will not be interrupted.
Page 20
Bypass automatic switch Bypass input NOTE: In the event of UPS malfunctions or abnormal operation, contact your nearest Vertiv branch Bypass input switch office or local service center. NEVER attempt to repair the UPS yourself, as this may result in injury to personnel and/or damage to equipment.
Figure 6-4 Figure 6-5. 1.5 Battery Management The following battery management functions are set by the service engineer through the Vertiv setting software. 1.5.1 Normal Function 1. Constant current boost charge Adopt the constant current (within battery charging limit) to charge the battery. The function can be used for battery capacity fast recovery.
9. Maximum boost charge protection time To protect against the battery overcharge damage caused by long time boost charge, a protect time setting is essential. The limit of time setting shall be configured by service engineer through the Vertiv setting software.
VRLA batteries, the EOD voltage is adjustable from 1.60 V/cell to 1.90 V/cell (VRLA). BCB alarm The BCB alarm occurs when the external BCB opens, if you select the Vertiv BCB (optional). The external battery connects to the UPS through the BCB. The BCB is manually closed and tripped by the UPS control circuit.
Page 24
Vertiv™ Liebert EXS 80kVA UPS User Manual This page is intentionally left blank. 1 Overview...
WARNING! Professional installation required 1. The UPS should be installed by a qualified engineer in accordance with the information provided in this section. In the event of any problems, contact your local Vertiv service center immediately. 2. The UPS must NOT be switched on without the approval of the commissioning engineer.
Vertiv™ Liebert EXS 80kVA UPS User Manual 2.2 Transportation Railroad transportation and shipping are the recommended means of transportation. If truck transportation is unavoidable, choose roads that are less bumpy in order to protect the equipment. The UPS cabinet is heavy (see Table 10-3 for its weight).
Page 27
Vertiv™ Liebert EXS 80kVA UPS User Manual Table 2-1 Tools Name Drawing Name Drawing Electric hand drill Adjustable wrench Slotted screwdriver Cross head screwdriver Stepladder Forklift Drill Wire cutting plier Claw hammer Diagonal cutting plier Insulating shoes Antistatic gloves Electrician knife...
Vertiv™ Liebert EXS 80kVA UPS User Manual 2.4 Unpacking Unpack the UPS and battery packages under the guidance of authorized service engineer. Steps: 1. Use a cutting plier to cut off the packing belt, and remove the honeycomb board, as shown in Figure 2-2.
Page 29
Vertiv™ Liebert EXS 80kVA UPS User Manual 2. As shown in Figure 2-3, remove the carton (I, II, III), wrapping film, and protective cardboard at four corners. Figure 2-3 Removing protective cardboard 3. Open the front panel, loosen the fixing screws and remove the bottom fixed part at front of the cabinet.
Vertiv™ Liebert EXS 80kVA UPS User Manual 2.5 Initial Inspection Before installing the UPS, carry out the following inspections: 1. Ensure that the environment of the UPS equipment room meets the environmental requirement specified in the product technical specifications, especially the ambient temperature, ventilation conditions, and the dust situations.
Vertiv™ Liebert EXS 80kVA UPS User Manual 2.6.2. Reserved Space Figure 2-5 Installation clearances (top view) Wall 墙壁 >200mm 500mm 500mm Cabinet 机柜 200mm NOTE: 1. The UPS should only be installed on concrete or other non-inflammable surfaces. 2. As shown in Figure 2-5, the clearance between the rear panel of the wall should be convenient. The clearance should not be less than 500mm, and should be sufficient to allow maintenance operations to be carried out.
Vertiv™ Liebert EXS 80kVA UPS User Manual 2.6.4. Storage Environment Should the UPS not be installed immediately, it must be stored with the original packaging in a room for protection against excessive humidity and heat sources. The battery needs to be stored in a dry and cool place with good ventilation.
Vertiv™ Liebert EXS 80kVA UPS User Manual 3 Electrical Installation This chapter mainly introduces the electrical installation of the UPS, including the power cable and signal cable connecting procedures and methods. After completing the mechanical installation of the UPS, it is required to connect the power cable and signal cable of the UPS.
UPS according to the current value in Table 3-1. 2. We recommend configuring Vertiv BCB box for the UPS with external batteries. If BCB is not selected, please select battery switch according to BCB parameters shown in 9.5 BCB Box.
Vertiv™ Liebert EXS 80kVA UPS User Manual 3.1.5 Power Cable Connecting Terminal The rectifier input, bypass input, output and battery power cables are connected to the corresponding terminals shown in Figure 3-1. 3.1.6 Protection Ground The protective earth cable is reliably connected to the PE input terminal (see Figure 3-1) via the fixing bolt.
Page 38
Vertiv™ Liebert EXS 80kVA UPS User Manual Figure 3-1 Connection terminals and routing method of power cables oA oB oC N N mA bA mB bB mC bC N N Procedures: 1. There are two protective covers at the rear of the cabinet. The user can use the cabling hole on No.1 protective cover for routing the cables according to actual needs.
Page 39
Vertiv™ Liebert EXS 80kVA UPS User Manual WARNING! Before cables connection, make sure that all external and internal power switches of the UPS are off, and post necessary warning signs to prevent inadvertent operation of the switches. Meanwhile, measure the voltages between the UPS terminals and the voltages between the terminals and the earth.
Vertiv™ Liebert EXS 80kVA UPS User Manual 3.2 Wiring of Signal Cable NOTE: 1. Respectively route the power cables and signal cables. The shielding coat of signal cable must be reliably earthed. 2. Refer to 7.2 Connecting Dry Contact Port Cables for the definition of signal cables.
Vertiv™ Liebert EXS 80kVA UPS User Manual 4 Operator Control And Display Panel This chapter introduces the functions and use of the components on the UPS operation and display panel, and provides LCD display information, including the LCD screen types, detailed menu messages, prompt windows message and UPS alarm list.
Vertiv™ Liebert EXS 80kVA UPS User Manual 4.1.2. Audible Alarm (Buzzer) UPS operation is accompanied with the following two different kinds of audible alarms, as described in Table 4-2. Table 4-2 Description of audible alarm Sound Meaning Continuous beep This sound is generated in the event of a UPS fault condition, such as a fuse or hardware failure One beep every 3.3 second...
Vertiv™ Liebert EXS 80kVA UPS User Manual The LCD includes a user-friendly interface and a 320 × 240 dot matrix image display. Thanks to the user- friendly, menu-oriented LCD it is possible to browse easily through the UPS input, output, load and battery parameters, obtain information about the current UPS status and alarm messages, as well as performing functional setting and control operations.
Vertiv™ Liebert EXS 80kVA UPS User Manual 4.2.2. Flow Screen Once the UPS self-test is complete, the flow screen shown in Figure 4-5 will appear. The flow screen provides a total status overview of the UPS, including the input, bypass, rectifier, battery, inverter and output, etc.
Vertiv™ Liebert EXS 80kVA UPS User Manual 4.2.4. Submenu Screen The submenu screen contains the UPS parameters and item settings. After accessing the submenu screen, if there is a tab control, just move the cursor to the tab. At this point, you can press the key to switch the tab.
Page 46
Vertiv™ Liebert EXS 80kVA UPS User Manual Settings page The Settings page can be used to access the Monitor and System settings. See below: System Monitor Language English Date format M/D/Y Settings Control Status Date 01-12-2018 13:55:33 Time Audible alarm...
Page 47
Vertiv™ Liebert EXS 80kVA UPS User Manual Log page The Log page can be used to access a list of current and historical UPS events. See below: Current History 00 Load on Inverter 01-12-2018 13:48:09 Settings Control Status 00 Inverter Manual On...
Page 48
Suspended time rem... Unknown Battery discharge t... 00Day 11Hour 2... Battery discharge c... Maintain page NOTE: The Maintain page is password protected and reserved for use by Vertiv service engineers only. Settings Control Status About Maintain 4 Operator Control And Display Panel...
Vertiv™ Liebert EXS 80kVA UPS User Manual 4.2.5. Default Screen During the UPS operation, if there are no alarms for two minutes, the display will revert to the default as shown in Figure 4-7 While the Default screen is displayed, if there are no alarm or fault conditions active,...
Page 50
Vertiv™ Liebert EXS 80kVA UPS User Manual Prompt Meaning Turn on local INV? OK or This prompt appears when you press the power button, confirm or cancel it Cancel Turn off local INV? OK or This prompt appears when you press the power button, confirm or cancel it...
Page 51
Vertiv™ Liebert EXS 80kVA UPS User Manual Prompt Meaning Please confirm PARA INV is off Please confirm Int MBB (Maint. Sw.) is closed Please confirm Int MBB (Maint. Sw.) and EXT MBB are closed Please confirm Int MIB (Output Sw.) is opened Please confirm Int MIB (Output Sw.) and EXT MIB are opened...
Vertiv™ Liebert EXS 80kVA UPS User Manual 4.4 UPS Alarm Message List Table 4-5, Table 4-6 Table 4-7 list all the UPS alarm messages based on the ‘Current’ and ‘History’ menus. Table 4-5 UPS alarm message list Alarm Meaning Input Phase Reversed...
Page 53
Vertiv™ Liebert EXS 80kVA UPS User Manual Alarm Meaning Communication failure between discrete bus inside the rack. It is recommended to confirm Discrete Bus Comms. Abnormal that the rear communication cables connection inside the rack is reliable Ambient Overtemperature Ambient overtemperature detection, can be set via the host software...
Page 54
Vertiv™ Liebert EXS 80kVA UPS User Manual Fault Meaning All UPSs in the parallel system transfer to bypass at the same time when one of them needs Other Module Transfer to transfer to bypass. This message appears on the LCD of the UPS with passive transfer to...
Page 55
Vertiv™ Liebert EXS 80kVA UPS User Manual Table 4-7 UPS prompt message list Fault Meaning Rectifier in Setting The rectifier starts up and is in synchronization Inverter in Setting The inverter starts up and is in synchronization with the monitoring...
Page 56
2. If the alarm is generated as the result of a software value set-up by Vertiv engineer, and you wish to modify the setting, please get in touch with your local Vertiv customer service center.
This chapter introduces the operating precautions and routine operating methods of UPS in detail. 5.1 Brief Introduction 5.1.1. Precautions IMPORTANT! The user can conduct relative operation only after the Vertiv engineer carries out the first power on and test. WARNING! hazardous mains and/or battery voltage 1.
Vertiv™ Liebert EXS 80kVA UPS User Manual Figure 5-1 UPS power switch Cold start button 5.1.3. Check before Start-up 1. Check and confirm that the UPS power distribution mode is correct, that the power cables and signal cables are connected correctly, and there are no short circuits.
Vertiv™ Liebert EXS 80kVA UPS User Manual 5.2.1. Start-up Procedures in Normal Mode WARNING! 1. To avoid misreporting as faults, all operations relating to disconnection or connection of the maintenance bypass switch shall be finished within three seconds. 2. After the output is closed, If any loads are connected to the UPS output terminals, check with the user that it is safe to apply power.
Page 60
Vertiv™ Liebert EXS 80kVA UPS User Manual Check that the parameters containing input, bypass, battery voltage, frequency and phase are correct, and then back to the Flow page. 5. Access the flow page, press and hold the power button, and the LCD prompt a dialogue box, as shown Figure 5-4.
Vertiv™ Liebert EXS 80kVA UPS User Manual 5.2.2. Start-up Procedures in Battery Mode (Battery Cold Start) 1. Check and confirm the batteries are well connected. 2. Open the front door of the UPS, press and hold any battery cold start button for 2s (see Figure 5-1 its position).
Vertiv™ Liebert EXS 80kVA UPS User Manual Figure 5-7 Flow page on bypass 219.3V 220.4V 50.0Hz 49.9Hz Charge 563.4V 220.2V 50.0Hz 200.0 Min In Inverter mode, press the power button. If the bypass is abnormal, then the interface shown in Figure 5-8 will appear, select ‘NO’...
Vertiv™ Liebert EXS 80kVA UPS User Manual Figure 5-9 Switching the UPS on Confirm 217.7V 219.8V 49.9Hz 49.9Hz 充电 Turn on local INV? 553.9V 219.5V 49.9Hz 11.0分 In Bypass mode, press the power button, and the LCD prompt a dialogue box shown in...
Vertiv™ Liebert EXS 80kVA UPS User Manual 3. Close the maintenance bypass switch Q3. At the moment, the maintenance bypass parallels with the UPS bypass. 4. Unplugging the EPO terminal disconnects the output switch Q5, main input switch Q1, bypass input switch Q2.
Vertiv™ Liebert EXS 80kVA UPS User Manual 2. The tests can be carried out from the operator control and display panel of the UPS by the operator when the following conditions are satisfied: • The load must be between 20% and 80% of rated UPS capacity and must be stable (for battery maintenance test) •...
Vertiv™ Liebert EXS 80kVA UPS User Manual 3. Wait until the test completes. After five seconds, a pop window will appear to show the result of this diagnosis: rectifier, inverter, monitor OK or fault. 5.6 UPS Shutdown Procedures 5.6.1. Procedures for Completely Powering down UPS...
Vertiv™ Liebert EXS 80kVA UPS User Manual 5.8 UPS Reset Procedures after EPO After shutting down the UPS through EPO or reasons of inverter overtemperature, overload, battery overvoltage and DC bus voltage, clear the fault according to the alarm message displaying on LCD screen.
Vertiv™ Liebert EXS 80kVA UPS User Manual 5.10 Selecting Language The LCD menus are available in 13 languages. Procedures for selecting the language: 1. Access the main menu screen and press the key to switch the cursor to select ‘Settings’, then press the key to confirm it.
Vertiv™ Liebert EXS 80kVA UPS User Manual 3. Press the key to highlight the language, see Figure 5-14. Figure 5-14 Language selection Monitor System Language English Date format M/D/Y Date 01-12-2018 13:55:33 Time Audible alarm Enable Serial 1 baudrate 9600 bps...
Page 70
Vertiv™ Liebert EXS 80kVA UPS User Manual Figure 5-16 Main menu screen Settings Control Status About Maintain 2. Press the key to move the cursor to ‘Monitor’, see Figure 5-17. Figure 5-17 Monitor interface System Monitor Language English Date format...
Vertiv™ Liebert EXS 80kVA UPS User Manual 4. Press the key, move the cursor and press the key to change the date and time as required. See Figure 5-19. Figure 5-19 Changing date and time Monitor System Monitor System Language...
Page 72
Vertiv™ Liebert EXS 80kVA UPS User Manual 2. Press the key, the interface shown in Figure 5-21 will appear. Figure 5-21 Inputting password Monitor System Input UPS address Card slot protocol YDN23 Password for settings Change settings password 0***** To change the password, proceed as follows: 1.
Page 73
Vertiv™ Liebert EXS 80kVA UPS User Manual 3. Press the key, the interface shown in Figure 5-24 will appear. Figure 5-24 Password for settings Monitor System Input UPS address Card slot protocol YDN23 Password for settings Change settings password 0***** 4.
Page 74
Vertiv™ Liebert EXS 80kVA UPS User Manual 6. After confirming the new password, press the key; at this point a system prompt appears indicating that the password has been changed successfully, see Figure 5-27. Figure 5-27 Password changed successfully Monitor...
The installation of a parallel UPS should follow the installation procedure for a single UPS module with the additional requirements detailed in this section. WARNING! To achieve normal operation of the parallel system, Vertiv service personnel must execute the CAN resistance operation. Failure to do so could result in system fault.
WARNING! To achieve coordinated operation of the modules in the parallel system, it is required to configure each module separately using Vertiv setting software. This must be done by Vertiv service personnel. 6.3.2. Cabinet Installation Place the UPS modules side by side and interconnect as shown in Figure 6-1.
Vertiv™ Liebert EXS 80kVA UPS User Manual 6.3.3. Power Cables The power cable wiring is similar to that of the UPS module. Refer to 3.1 Wiring of Power Cable. The bypass and rectifier input supplies must use the same neutral line input terminal. If the input has a current leakage protective device, the current leakage protective device must be fitted upstream of the neutral line input terminal.
Vertiv™ Liebert EXS 80kVA UPS User Manual 6.4.2. Parallel System Parameters Setting NOTE: The parameters of parallel system must be set by Vertiv engineer through Vertiv setting software 6.4.3. Power-on Procedures for Parallel System 1. Set the parallel parameter of each UPS in the parallel system, then commission the inverter.
Vertiv™ Liebert EXS 80kVA UPS User Manual 2. After confirming that the inverter of each UPS is normal, commission the parallel system, the specific procedures are as follows: a. Close the external and internal I/O switch of each UPS, and all UPSs are powered on at the same time.
6.4.5. Procedures for Isolating One UPS Module from Parallel System IMPORTANT! These procedures shall only be carried out by service personnel of Vertiv or under their guidance. WARNING! Before operation, confirm that the system capacity has redundancy to avoid system shutdown due to overload.
Vertiv™ Liebert EXS 80kVA UPS User Manual 6.4.7. 6.4.7 Procedures for Completely Powering down UPS Complete UPS shutdown and load power-off should follow this procedure. All power switches, isolating switches and breakers are disconnected, and then UPS no longer supplies power to the load.
Page 83
Vertiv™ Liebert EXS 80kVA UPS User Manual Figure 6-4 LBS system (UPS module) Bypass Bypass Rectifier Rectifier Q2 Q3 Q2 Q3 To load Note: Q1, Q2 and Q5 are optional while Q3 is standard Figure 6-5 LBS system (parallel system)
UPS1 UPS2 UPS3 UPS4 LBS cable 6.5.5. LBS Parameters Setting NOTE: The parameters of LBS parameters must be set by Vertiv engineer through Vertiv setting software 6.5.6. LBS System Commissioning Refer to 6.4 Operation Procedures for Parallel System for details.
Vertiv™ Liebert EXS 80kVA UPS User Manual 7 Communication This chapter briefly introduces the UPS communication. The communication ports include: intelligent card port, dry contact port, monitoring port, CAN port, built-in port, LBS port, parallel port, intelligent temperature sensor port and battery monitor port.
Figure 7-2) is a network management card, which makes the intelligent devices (such as UPS) produced by Vertiv have network communication capability. For more information of the SIC card, refer to Site Interface Web/SNMP Agent Card User Manual. Figure 7-2 SIC card...
Page 87
Vertiv™ Liebert EXS 80kVA UPS User Manual IS-UNITY-LIFE card Figure 7-4 for the appearance of IN-UNITY-LIFE card. Figure 7-4 IS-UNITY-LIFE card For further description of the IS-UNITY-LIFE card, refer to Liebert IntelliSlotTM Unity Card User Manual- Web, SNMP, Modbus, BACnet, YDN23.
Page 88
Vertiv™ Liebert EXS 80kVA UPS User Manual UF-RS85 card The UF-RS485 card converts RS232 signal to RS485 signal to realize UPS networking and communication. It should be installed in an Intellislot port of the UPS. It is hot pluggable for easy installation.
YDN23 or Velocity. The SIC card adopts YDN23 protocol while UNITY-DP card and UNITY-LIFE card adopt Velocity protocol. IMPORTANT!These procedures shall only be carried out by service personnel of Vertiv or under their guidance.
Vertiv™ Liebert EXS 80kVA UPS User Manual 7.2 Connection Cables for Dry Contact Port For on-site specific needs, the UPS needs auxiliary connection to realize battery system (including the external battery switch) management, communicate with PC, provide alarm signal to external devices, realize remote EPO or provide bypass back-feed circuit breaker signal and parallel communication.
Page 91
Vertiv™ Liebert EXS 80kVA UPS User Manual Silkprint Port name Pin No. Pin name Meaning Remarks On Generator / Transfer to Inverter Inhibited Inhibit_trans_to_ (default)/External MIB / External MBB / inverter Module Output Breaker / Battery Ground Configurable Fault / Charger Shutdown/ECO Inhibited...
Page 92
Vertiv™ Liebert EXS 80kVA UPS User Manual Silkprint Port name Pin No. Pin name Meaning Remarks Bypass back-feed normally open contact. BFP_O Closed when there is bypass back-feed Bypass back- feed output BFP_S Bypass back-feed common contact port Bypass back-feed normally closed contact.
Vertiv™ Liebert EXS 80kVA UPS User Manual NOTICE: 1. Ensure that the plug of REPO have been correctly connected to the corresponding Pin of port J14, and that the REPO cable is connected securely in order to ensure that the REPO is not activated inadvertently as the result of poor contacts.
Page 94
Vertiv™ Liebert EXS 80kVA UPS User Manual This page is intentionally left blank.
Vertiv™ Liebert EXS 80kVA UPS User Manual 8 Maintenance This chapter focuses on the UPS maintenance, including the fan maintenance, battery maintenance, UPS cleaning, UPS state check, UPS function check. NOTE: Never attempt to carry out maintenance on the UPS while it is on line. Ensure that the UPS has been switched off completely when performing any internal maintenance operations on it.
Vertiv may not be held liable for the environmental impact resulting from the failure to comply with the guidelines set out in this section, or to use the waste battery recycling system offered by Vertiv.
Vertiv™ Liebert EXS 80kVA UPS User Manual 9 Options This chapter introduces the options that are available for the UPS. 9.1 List of Options Table 9-1 for the list of the available options. Table 9-1 List 0f options Option name...
Vertiv™ Liebert EXS 80kVA UPS User Manual 9.2 Parallel Cables Communication cable is compulsory in parallel system. See Table 9-2 for cable description. Refer to 6.3.4. Parallel Cables for the methods to connect the parallel cables. Table 9-2 Description of the parallel cables...
Vertiv™ Liebert EXS 80kVA UPS User Manual 9.4 Communication Options and Temperature Sensor The communication options and temperature sensor are listed in Table 9-4. Table 9-4 Communication options and temperature sensor Name Type Description Appearance Remotely monitor UPS through TCP/IP protocol...
The BCB box contains a BCB and a BCB control board. Vertiv provides the BCB box for use when the external battery installation is required. In this situation, The BCB box is fitted as close as possible to the battery and connected to the UPS. Refer to...
Vertiv™ Liebert EXS 80kVA UPS User Manual Table 9-6 Description of BCB box components Component Battery connection terminal (BAT+/BAT N/BAT-) UPS connection terminal (UPS+/UPS N/UPS-) Grounding bar Battery switch control board Base plate Current sensor to be installaed when selecting battery ground fault kit...
CAUTION: If the corresponding functions are not required, just do not connect corresponding ternimals. 9.6 Battery Cabinet The BCB cabinet contains batteries, BCB and a BCB control board. Vertiv provides the BCB cabinet for battery backup use. Refer to Figure 9-3, Table 9-8 for description of the BCB cabinet and its data.
Page 103
Vertiv™ Liebert EXS 80kVA UPS User Manual Figure 9-3 Diagram of battery cabinet Battery cabinet Battery position Battery position Front view Rear view 9 Options...
Vertiv™ Liebert EXS 80kVA UPS User Manual 9.7 Output Transformer This UPS includes an isolation transformer (see Figure 9-4 for its position) at the UPS output. This transformer is installed in the cabinet and provides electrical isolation between the UPS output and the load.
Vertiv™ Liebert EXS 80kVA UPS User Manual 9.8 Top Fan The top fan assembly provides the upward air outlet direction for UPS, as shown in Figure 9-5. Assemblied after factory delivery. Please refer to the quick installation instruction manual for the detailed assembly steps.
Vertiv™ Liebert EXS 80kVA UPS User Manual 9.9 IP31 Kit The IP31 kit provides a higher level of protection for the UPS, as shown in Figure 9-6. Assemblied after factory delivery. Please refer to the quick installation instruction manual for the detailed assembly steps.
Vertiv™ Liebert EXS 80kVA UPS User Manual 10 Specifications This chapter lists the UPS specifications. 10.1 Conformance and Standards Table 10-1 Conformance and standards Item Standard IEC/EN62040-2 Conduction emission Standard product meets Class C3, the product with C2 option installed meets Class C2...
Vertiv™ Liebert EXS 80kVA UPS User Manual 10.3 Mechanical Characteristics Table 10-3 Mechanical characteristics Rated power (kVA) Item Unit 80 kVA Dimensions (W × D × H) 600 × 850 × 1600; with top fan kit (600 × 850 × 1805) Net weight 230;...
Vertiv™ Liebert EXS 80kVA UPS User Manual Appendix I LCD Parameters Setting Menu Item Setting range Default setting Chinese, English, Deutsch, Italiano, Français, Čeština, Nederlands, Language English Português, Svenska, Türkçe, Español, Русский, Polski Date format YY/MM/DD, MM/DD/YY, DD/MM/YY MM/DD/YY Date...
Page 112
Vertiv™ Liebert EXS 80kVA UPS User Manual Menu Item Setting range Default setting System configuration Single, Parallel Parallel LBS configuration None, LBS slave, LBS master None Normal, Intelligent parallel, Intelligent parallel demo, ECO, Frequency converter(have battery), Frequency converter(no battery), Power...
Page 113
Vertiv™ Liebert EXS 80kVA UPS User Manual Menu Item Setting range Default setting 208V,220V,380V,400V,415V 208V Note: Note: Default 1.Setting range may vary from different settings may System Voltage model name. be different for Level(L-L) 2.Please don’t set this parameter when...
Page 114
Vertiv™ Liebert EXS 80kVA UPS User Manual Menu Item Setting range Default setting Shared battery Enable , Disable Disable Battery strings Note: Default value may be 80~360 different for Note: Setting range may vary for Cells per string different system...
Page 115
Vertiv™ Liebert EXS 80kVA UPS User Manual Menu Item Setting range Default setting Battery Capacity Setting 0~100% for Load Shed Signal 1 Battery Backup Time Setting for Load Shed 0~3600 Sec 0 Sec Signal 1 Battery Capacity Setting 0~100% for Load Shed Signal 2...
Page 116
Vertiv™ Liebert EXS 80kVA UPS User Manual Menu Item Setting range Default setting Turn on/off/to bypass Mute/Unmute audible alarm Battery maintenance Control test Stop battery test Clear faults Battery capacity test Start equalize charge Stop equalize charge Maintain Battery reset...
Vertiv™ Liebert EXS 80kVA UPS User Manual Appendix II Glossary Alternating current Circuit breaker Cross sectional area Direct current Dual in-line package Digital signal processor Electromagnetic compatibility Electromagnetic interference End-of-discharge Emergency power off Input/output Load bus synchronizer Liquid crystal display...
Need help?
Do you have a question about the Liebert EXS 80kVA UPS and is the answer not in the manual?
Questions and answers