Page 1
VEEDER - ROOT SERIAL INTERFACE MANUAL TLS4 Series TLS-450 Series TLS-450PLUS Series Environmental & Inventory Management System Manual Number 577013-950 Revision L...
Page 2
Notice Veeder-Root makes no warranty of any kind with regard to this publication, including but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this publication.
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 1.0 INTRODUCTION The serial RS-232 interface is used to connect the system to a controlling computer, a display terminal (CRT) or a printing terminal. A modem can be connected directly to the system to provide telephone line access.
Serial Interface Manual TLS4/TLS-450 Monitoring Systems RS-232 signals are wired to the female D-connector as follows: 2.2 EIA RS-232 INTERFACE The EIA RS-232 interface is designed to connect to modems for transmission of data over telephone lines. It can be used for direct local attachment of terminals if the cable run is no more than 50 feet.
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 3.0 CHARACTER FORMAT AND BAUD RATE The system receives and sends characters via the RS-232 interface in an ASCII format that is configured via the system front panel keypads. Selections consist of: 1 start bit; 7 or 8 data bits; odd, even or no parity;...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 5.0 COMMAND MESSAGE FORMAT All command and response messages are configured in a format which includes a surrounding envelope of control characters and a function code and data field message. The control characters are described in this section while the function codes and data field messages are described in subsequent sections.
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 6.0 RESPONSE MESSAGE FORMAT There are two types of response message formats: computer (or packed data format) and display format. Each format uses a different surrounding envelope of control characters. 6.1 COMPUTER FORMAT The computer format is a stream of numbers without any formatting characters; i.e., carriage return, line feed, spaces, labels, etc.
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 6.3 ASCII FLOATING POINT FORMAT 6.3.1 NOTES 6.3.1.1 HHHHHHHH (H = 0-9 or A-F) indicates the 8 "nibble" ASCII-Hexadecimal representation of a 4-Byte Floating Point number. Many data parameters are transmitted in this format. 6.3.1.2 The 32-bits are arranged as follows: Byte...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.0 FUNCTION CODES AND RESPONSE MESSAGES All response messages are sent in a format described in previous sections. The function codes and data fields of these message formats are described in this section. The data field response messages are divided into the following major groupings: Function Codes ....................
Page 13
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Most response messages can be requested for either a single device (tank, sensor, line, etc.) or all devices. A "TT" in the function code signifies single device number 01 through 16. When "TT" is 00, it signifies all devices.
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.1 CONTROL FUNCTIONS Function Code: Version 2 Function Type: Remote Alarm Reset Command Format: Display: <SOH>S00300 Computer: <SOH>s00300 Typical Response Message, Display Format: <SOH> S00300 MAR 27, 1996 8:04 PM <ETX> Typical Response Message, Computer Format: <SOH>s00300YYMMDDHHmm&&CCCC<ETX>...
Page 15
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Cancel Autodial Computer Mode Session Command Format: Display: <SOH>S01000 Computer: <SOH>s01000 Typical Response Message, Display Format: <SOH> S01000 MAR 27, 1996 8:04 PM <ETX> Typical Response Message, Computer Format: <SOH>s00300YYMMDDHHmm&&CCCC<ETX>...
Page 16
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Start In-Tank Leak Detect Test Command Format: Display: <SOH>S052TT (Use 203 command for inquiry) Computer: <SOH>s052TT Typical Response Message, Display Format: <SOH> S052TT MAR 27, 1996 6:28 PM TANK LABEL UNLEADED REGULAR...
Page 17
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Stop In-Tank Leak Detect Test Command Format: Display: <SOH>S053TT Computer: <SOH>s053TT Typical Response Message, Display Format: <SOH> S053TT MAR 29, 1996 6:27 PM TANK LABEL REGULAR UNLEADED LEAK TEST STOP <ETX>...
Page 18
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Delete CSLD Rate Table Command Format: Display: <SOH>S054TT149 Computer: <SOH>s054TT149 Notes: TT - Tank Number (command valid for single tank only) 149 - This verification code must be sent to confirm the command Typical Response Message, Display Format: <SOH>...
Page 19
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Start Pressure Line Leak Test Command Format: Display: <SOH>S081QQ149 Computer: <SOH>s081QQ149 Notes: 149 - This verification code must be sent to confirm the command Typical Response Message, Display Format: <SOH>...
Page 20
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Stop Pressure Line Leak Test Command Format: Display: <SOH>S082QQ149 Computer: <SOH>s082QQ149 Notes: 149 - This verification code must be sent to confirm the command Typical Response Message, Display Format: <SOH>...
Page 21
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Start Pressure Line Leak Test by Type Command Format: Display: <SOH>S087QQ149rr Computer: <SOH>s087QQ149rr Notes: 149 - This verification code must be sent to confirm the command Typical Response Message, Display Format: <SOH>...
Page 22
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Pressure Offset Reset Command Format: Display: <SOH>S089QQ149 Computer: <SOH>s089QQ149 Notes: 149 - This verification code must be sent to confirm the command Typical Response Message, Display Format: <SOH>...
Page 23
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Close Current Shift Command Format: Display: <SOH>S09100 Computer: <SOH>s09100 Typical Response Message, Display Format: <SOH> S09100 MAR 27, 1996 8:04 PM CLOSE CURRENT SHIFT: YES <ETX> Typical Response Message, Computer Format: <SOH>s09100YYMMDDHHmmff&&CCCC<ETX>...
Page 24
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Start Pressure Line Leak Profile Line Test Command Format: Display: <SOH>S092QQ149 Computer: <SOH>s092QQ149 Notes: 149 - This verification code must be sent to confirm the comand Typical Response Message, Display Format: <SOH>...
Page 25
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Stop Pressure Line Leak Profile Line Test Command Format: Display: <SOH>S093QQ149 Computer: <SOH>s093QQ149 Notes: 149 - This verification code must be sent to confirm the comand Typical Response Message, Display Format: <SOH>...
Page 26
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Recalculate Pressure Line Leak Profile Bulk Modulus Command Format: Display: <SOH>S094QQ149 Computer: <SOH>s094QQ149 Notes: 149 - This verification code must be sent to confirm the comand Typical Response Message, Display Format: <SOH>...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.2 OPERATIONAL REPORTS 7.2.1 SYSTEM REPORTS Function Code: Version 1 Function Type: System Status Report Command Format: Display: <SOH>I10100 Computer: <SOH>i10100 Notes: This command will report all active OR unacknowledged alarms and warnings up to the limit of 25 alarms in display format, and 150 alarms in computer format Typical Response Message, Display Format: <SOH>...
Page 29
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 101 Notes: (Continued) 06=Tank Sudden Loss Alarm 07=Tank High Product Alarm 08=Tank Invalid Fuel Level Alarm 09=Tank Probe Out Alarm 10=Tank High Water Warning 11=Tank Delivery Needed Warning 12=Tank Maximum Product Alarm 13=Tank Gross Leak Test Fail Alarm 14=Tank Periodic Leak Test Fail Alarm 15=Tank Annual Leak Test Fail Alarm...
Page 30
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 101 Notes: (Continued) 14=VLLD Annual Test Needed Alarm 15=VLLD Periodic Line Test Fail Alarm 16=VLLD Periodic Line Selftest Fail Alarm 17=VLLD Periodic Pump Test Fail Alarm 18=VLLD Periodic Pump Selftest Fail Alarm 19=VLLD Annual Line Test Fail Alarm 20=VLLD Annual Line Selftest Fail Alarm 21=VLLD Annual Pump Test Fail Alarm...
Page 31
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 101 Notes: (Continued) 05=PLLD Periodic Test Needed Alarm 06=PLLD Sensor Open Alarm 07=PLLD High Pressure Alarm (Obsolete) 08=PLLD Shutdown Alarm 09=PLLD High Pressure Warning (Obsolete) 10=PLLD Continuous Handle On Warning (Obsolete) 11=PLLD Periodic Test Fail Alarm 12=PLLD Annual Test Needed Warning 13=PLLD Annual Test Needed Alarm 14=PLLD Low Pressure Alarm...
Page 32
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 101 Notes: (Continued) 10=Vapor Processor Status Test warning 11=Vapor Processor Status Test alarm 12=Missing Relay Setup alarm 13=Missing Hose Setup alarm 14=Missing Tank Setup alarm 15=Missing Vapor Flow Meter alarm 16=Missing Vapor Pressure Sensor alarm 17=Missing Vapor Pressure Input alarm 18=Setup Fail warning 19=Setup Fail alarm...
Page 33
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 101 Notes: (Continued) - If AA is 65 and NN is: 01=Pump Setup Data Warning 02=Pump Out Alarm 02=Stuck Relay or Continuous Pump If AA is 66 and NN is: 01=Line Setup Data Warning 02=Line Out Alarm If AA is 73 and NN is: 01=Communication Setup Data Warning...
Page 34
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Combined Alarm History Report Command Format: Display: <SOH>I11000 Computer: <SOH>i11000 Notes: This command will report history of all priority & non- priority alarms up to the limit of 50 alarms in both display and computer formats.
Page 35
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Priority Alarm History Report Command Format: Display: <SOH>I11100 Computer: <SOH>i11100 Notes: This command will report history of all priority alarms and warnings up to the limit of 50 alarms in both display & computer formats.
Page 36
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Non-Priority Alarm History Report Command Format: Display: <SOH>I11200 Computer: <SOH>i11200 Notes: This command will report history of all non-priority alarms and warnings up to the limit of 50 alarms in both display & computer formats.
Page 37
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Active Alarm Report Command Format: Display: <SOH>I11300 Computer: <SOH>i11300 Notes: This command will report ALL active alarms and warnings regardless of their acknowledgement state. If there are more than can be contained in the non-priority and priority history storage areas, they will be reported here without time and date stamps...
Page 38
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Cleared Alarm Report Command Format: Display: <SOH>I11400 Computer: <SOH>i11400 Notes: This command will report history of all cleared alarms up to the limit of 50 alarms in both display & computer formats. Typical Response Message, Display Format: <SOH>...
Page 39
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Extended Alarm Report – Date Based Command Format: Display: <SOH>I11C00RRyymmddYYMMDDnnn Computer: <SOH>i11C00RRyymmddYYMMDDnnn Notes: 1. RR -Report Type (Report Type should always be given. The rest of the parameters are optional following the rules below.) 00=Active Alarm Report (for Active and Unacknowledged) 01=Alarm History Report –...
Page 40
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 11C: (Continued) For an Alarm History Report: <SOH> I11C0001 JAN 22, 1996 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..Selected Range: Previous 1 Year: 10/15/2004 04:00 PM – 10/15/2005 04:00 PM Alarm History Report –...
Page 41
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Extended Alarm Report – Date/Time Based Command Format: Display: <SOH>I11D00RRyymmddhhmmYYMMDDHHMMnnn Computer: <SOH>i11D00RRyymmddhhmmYYMMDDHHMMnnn Notes: 1. RR - Report Type (Report Type should always be given. The rest of the parameters are optional following the rules below.) 00=Active Alarm Report (for Active and Unacknowledged) 01=Alarm History Report –...
Page 42
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 11D: (Continued) For an Alarm History Report: <SOH> I11D0001 JAN 22, 1996 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..Selected Range: Previous 1 Year: 10/15/2004 04:00 PM – 10/15/2005 04:00 PM Alarm History Report –...
Page 43
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Last Active Alarm Command Format: Display: <SOH>I11E00AANNTT Computer: <SOH>i11E00AANNTT Notes: AA - Alarm/Warning Category: See explanation for "AA" in Function i10100 NN - Alarm Type Number: See explanation for "NN" in Function i10100 TT - Tank/Sensor Number –...
Page 44
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Extended Sensor Status Report – Date/Time Based Command Format: Display: <SOH>I11FTTRRNNyymmddhhmmYYMMDDHHMMnnn Computer: <SOH>i11FTTRRNNyymmddhhmmYYMMDDHHMMnnn Notes: 1. TT -Device Number (Decimal, 00=all) 2. RR - Report Type (Report Type should always be given. The rest of the parameters are optional following the rules below.) 00=Sensor Status Report (for Active Sensor Alarms and Normal...
Page 45
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 11F: (Continued) Typical Response Message, Display Format: For a Status Report: <SOH> I11F0000 JAN 22, 1996 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..Sensor Status Report – All Sensors Sensor Location Status Regular STP Pump...
Page 46
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 11F: (Continued) Typical Response Message, Computer Format: <SOH>i11F00YYMMDDHHmmAAccNNTTSSYYMMDDHHmm... AAccNNTTSSYYMMDDHHmm&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time AA - Alarm/Warning Category: See explanation for "AA" in Function i10100 cc - Sensor Category 00=Other 01=Annular 02=Dispenser Pan 03=Monitoring Well...
Page 47
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Setup Warning Detailed Information Command Format: Display: <SOH>I12200 Computer: <SOH>i12200 Typical Response Message, Display Format: For a Status Report: <SOH> I12200 JAN 22, 2014 3:06 PM STATION HEADER 1..STATION HEADER 2..
Page 48
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 122: (Continued) 0x00004000 = INVALID ACCUCHART SETUP 0x00008000 = MISSING PRODUCT ASSIGNMENT 0x00010000 = MISSING_DENSITY_CODE 0x00020000 = PROBE INCORRECT FLOAT SIZE 0x00040000 = PROBE INVALID ADDRESS -If AA is 03, 04, 07, 08 or 12 Sensors: 0x00000001 = ADDRESS NOT SET 0x00000002 = VAPOR THRESHOLD NOT SET -If AA is 05 Inputs:...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.2.2 IN-TANK REPORTS Function Code: Version 1 Function Type: In-Tank Inventory Report Command Format: Display: <SOH>I201TT Computer: <SOH>i201TT Typical Response Message, Display Format: <SOH> I201TT JAN 22, 1996 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 51
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Delivery Report Command Format: Display: <SOH>I202TT Computer: <SOH>i202TT Typical Response Message, Display Format: <SOH> I202TT JUL 29, 1997 9:02 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..
Page 52
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 202 Notes: (Continued) Typical Response Message, Computer Format: <SOH>i202TTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=all) p - Product Code (one ASCII character [20h-7Eh]) dd - Number of Deliveries to follow (Decimal, 00 if no data available for this tank) YYMMDDHHmm - Starting Date/Time YYMMDDHHmm - Ending Date/Time...
Page 53
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Leak Detect Report Command Format: Display: <SOH>I203TT Computer: <SOH>i203TT Typical Response Message, Display Format: <SOH> I203TT JAN 22, 1996 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 54
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Active Shift Inventory Report Command Format: Display: <SOH>I204TT Computer: <SOH>i204TT Notes: TT - tank number, 00 = all tanks In Display format mode: a. Shifts will displayed in descending time order b.
Page 55
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 204 Notes: (Continued) Typical Response Message, Computer Format: <SOH>i204TTYYMMDDHHmmTTpssNNFFFFFFFF... TTpssNNFFFFFFFF&&CCCC<ETX> Notes: 1. YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=all) p - Product Code (one ASCII character [20h-7Eh]) ss - Shift Number [01 - 08] NN - Number of eight character Data Fields to follow (Hex) FFFFFFFF - ASCII Hex IEEE floats:...
Page 56
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Status Report Command Format: Display: <SOH>I205TT Computer: <SOH>i205TT Typical Response Message, Display Format: <SOH> I205TT JAN 22, 1996 3:07 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..
Page 57
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Alarm History Report Command Format: Display: <SOH>I206TT Computer: <SOH>i206TT Typical Response Message, Display Format: <SOH> I206TT JAN 22, 1996 3:07 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 58
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 206 Notes: (Continued) Typical Response Message, Computer Format: <SOH>i206TTYYMMDDHHmmTTnnYYMMDDHHmmaaaa... TTnnYYMMDDHHmmaaaa&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=all) nn - Number of alarms in history for tank (Decimal, 00=none) YYMMDDHHmm - Date and time alarm occurred aaaa - Type of alarm: 0001=Tank Setup Data Warning...
Page 59
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Leak Test History Report Command Format: Display: <SOH>I207TT Computer: <SOH>i207TT Typical Response Message, Display Format: <SOH> I207TT JUL 29, 1997 9:02 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 60
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Leak Test Results Report Command Format: Display: <SOH>I208TT Computer: <SOH>i208TT Typical Response Message, Display Format: <SOH> I208TT JAN 22, 1996 3:07 PM PREVIOUS IN TANK LEAK TEST RESULTS TANK 1 REGULAR UNLEADED TEST...
Page 61
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Enhanced In-Tank Leak Detect Report Command Format: Display: <SOH>I209TT Computer: <SOH>i209TT Typical Response Message, Display Format: <SOH> I209TT JAN 22, 2007 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 62
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: HRM Adjusted Delivery Report Command Format: Display: <SOH>I20ATT Computer: <SOH>i20ATT Typical Response Message, Display Format: <SOH> I20ATT JAN 22, 2011 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 63
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: BIR Adjusted Delivery Report Command Format: Display: <SOH>I20BTT Computer: <SOH>i20BTT Typical Response Message, Display Format: <SOH> I20BTT JAN 22, 2009 3:08 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 64
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Most Recent Delivery Report Command Format: Display: <SOH>I20CTT Computer: <SOH>i20CTT Typical Response Message, Display Format: <SOH> I20CTT JUL 29, 1997 9:03 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 65
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: In-Tank Stick Height Report Command Format: Display: <SOH>I20DTT Computer: <SOH>i20DTT Notes: This command will respond only if stick height is enabled. Tank stick height is fuel height (without tilt) + stick offset.
Page 66
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Extended Delivery Report – Date/Time Based Command Format: Display: <SOH>I20FTTRRyymmddhhmmYYMMDDHHMMnnn Computer: <SOH>i20FTTRRyymmddhhmmYYMMDDHHMMnnn Notes: 1. TT -Device Number (Decimal, 00=all) 2. RR - Report Type (Report Type should always be given. The rest of the parameters are optional following the rules below.) 00=Delivery History Report (for Inventory Information for the...
Page 67
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 20F: (Continued) Typical Response Message, Display Format: <SOH> I20F0001 JAN 22, 2008 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..Volume=Gallons Height=Inches Delivery History Report Temp=Fahrenheit Selected Range: All Records: T 1:REGULAR UNLEADED...
Page 68
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 20F Notes: (Continued) FFFFFFFF - ASCII Hex IEEE floats: 1. Starting Volume 2. Starting TC Volume 3. Starting Water 4. Starting Temp 5. Ending Volume 6. Ending TC Volume 7. Ending Water 8.
Page 69
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Static Leak Test Passed Report Command Format: Display: <SOH>I20GTT Computer: <SOH>i20GTT Typical Response Message, Display Format: <SOH> I20GTT JUL 29, 2007 9:02 AM STATIC LEAK TEST LAST PASSED REPORT TANK 1: REGULAR UNLEADED TOTAL AVG.
Page 70
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Static Leak Test History Command Format: Display: <SOH>I20HTTyymmddhhmmYYMMDDHHMMnnn Computer: <SOH>i20HTTyymmddhhmmYYMMDDHHMMnnn 1. yymmddhhmm - Starting Date/Time (If no start date/time is given or either Year, Month or Day are zeroes, it assumes request is for most recent records.
Page 71
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Enhanced In-Tank Inventory Report Command Format: Display: <SOH>I20ITT Computer: <SOH>i20ITT Typical Response Message, Display Format: <SOH> I20ITT JAN 22, 1996 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 72
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 20I Notes: (Continued) Typical Response Message, Computer Format: <SOH>i20ITTYYMMDDHHmmTTpssssNNFFFFFFFF... TTpssssNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=all) p - Product Code (one ASCII character [20h-7Eh]) ssss - Tank Status Bits: Bit 1 - (LSB) Delivery in Progress Bit 2 - Leak Test in Progress Bit 3 - Invalid Fuel Height Alarm (MAG Probes Only)
Page 73
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: BIR Adjusted Delivery Report with Range Command Format: Display: <SOH>I20LTTyymmddhhmmYYMMDDHHmmnnn Computer: <SOH>i20LTTyymmddhhmmYYMMDDHHmmnnn Notes: TT - Tank Number (Decimal, 00=all) yymmddhhmm - Starting Date (00000000 = no starting date = first of the month) YYMMDDHHmm - Ending Date (00000000 = no ending date = current date) nnn - Maximum Records [001…999] (100 = default) (decimal)
Page 75
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: In-Tank Shift Inventory History Report – Date/Time Based Command Format: Display: <SOH>I20MTTRRyymmddhhmmYYMMDDHHmmnnn Computer: <SOH>i20MTTRRyymmddhhmmYYMMDDHHmmnnn Notes: TT - Tank Number (Decimal, 00=All) RR - Report Type (Report Type should always be given. The rest of the parameters are optional following the rules below.) 00=Shift Inventory History Report Times or Manual Shift Closings...
Page 77
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: In-Tank Mass/Density Shift Inventory History Report Command Format: Display: <SOH>I20NTT Computer: <SOH>i20NTT Notes: TT - Tank Number (Decimal, 00=All) In Display format mode: a. Shifts will display in descending time order b.
Page 78
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 20N: (Continued) Typical Response Message, Computer Format: <SOH>i20NTTYYMMDDHHmmTTpssNNFFFFFFFF... TTpssNNFFFFFFFF&&CCCC<ETX> Notes: 1. YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=all) p - Product Code (one ASCII character [20h-7Eh]) ss - Shift Number [01 - 08] NN - Number of eight character Data Fields to follow (Hex) FFFFFFFF - ASCII Hex IEEE floats: 1.
Page 79
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: HRM Adjusted Delivery Report Date/Time Based Command Format: Display: <SOH>I20PTTyymmddYYMMDDnnn Computer: <SOH>i20PTTyymmddYYMMDDnnn Notes: TT - Tank Number (Decimal, 00=All) yymmdd - Starting Date (If no start date is given or zeros are entered for the starting date, then the request is limited by the Maximum Records (below) or the last 240 records.) YYMMDD - Ending Date (If no end date is given or or zeros are entered for...
Page 80
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Tank Chart Report Command Format: Display: <SOH>I211TThhhhhh Computer: <SOH>i211TTFFFFFFFF Notes: TT - Tank number, 00=All tanks hhhhh - height step size (inches or millimeters). Up to 6 decimal digits.
Page 81
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Leak Test History Report 2 Command Format: Display: <SOH>I212TT Computer: <SOH>i212TT Typical Response Message, Display Format: <SOH> I212TT JUL 29, 1997 9:02 AM TANK LEAK TEST HISTORY T 1:REGULAR UNLEADED AVERAGE REPORT TYPE...
Page 82
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Extended Standard Delivery Report Command Format: Display: <SOH>I213TTnn Computer: <SOH>i213TTnn Notes: TT - Tank Number (Decimal, 00=all) nn - Number of most recent deliveries (Decimal) Typical Response Message, Display Format: <SOH>...
Page 83
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 213 Notes: (Continued) Typical Response Message, Computer Format: <SOH>i213TTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=all) p - Product Code (single ASCII character [20h-7Eh]) dd - Number of Deliveries to follow (Decimal, 00 if no data available for this tank) YYMMDDHHmm - Starting Date/Time YYMMDDHHmm - Ending Date/Time...
Page 84
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: In-Tank Mass/Density Inventory Report Command Format: Display: <SOH>I214TT Computer: <SOH>i214TT Typical Response Message, Display Format: <SOH> I214TT JUL 30, 2009 9:02 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 85
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: In-Tank Mas/Density Delivery Report Command Format: Display: <SOH>I215TT Computer: <SOH>i215TT Typical Response Message, Display Format: <SOH> I215TT APR 30, 2010 3:16 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 86
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 215 Notes: (Continued) Typical Response Message, Computer Format: <SOH>i215TTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFFf... TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFFf...&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=all) p - Product Code (single ASCII character [20h-7Eh]) dd - Number of Deliveries to follow (Decimal, 00=no data) YYMMDDHHmm - Starting Date/Time YYMMDDHHmm - Ending Date/Time NN - Number of eight character Data Fields to follow (Hex)
Page 87
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Tank Profile Command Format: Display: <SOH>I217TT Computer: <SOH>i217TT Typical Response Message, Display Format: <SOH> I217TT SEP 16, 2004 3:15 PM TANK PROFILE T 1: REGULAR UNLEADED TANK PRODUCT LABEL PROFILE REGULAR UNLEADED 1 PT...
Page 88
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: (like 201) Version 1 Function Type: In-Tank Inventory Report With User Ullage (90-100%) Command Format: Display: <SOH>I21ATT Computer: <SOH>i21ATT Typical Response Message, Display Format: <SOH> I21ATT JAN 22, 2006 3:06 PM STATION HEADER 1..STATION HEADER 2..
Page 89
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: BIR Extended Adjusted Delivery Report Command Format: Display: <SOH>I21BTTnn Computer: <SOH>i21BTTnn Notes: TT - Tank Number (Decimal, 00=All) nn - Number of most recent deliveries (Decimal) Typical Response Message, Display Format: <SOH>...
Page 90
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Most Recent Delivery Report with Manifolded Results Command Format: Display: <SOH>I21CTT Computer: <SOH>i21CTT Notes: TT - Tank Number (Decimal, 00=all). To eliminate duplication, when TT=00 is used for Display Format the command will print information for a Manifolded Tank only if it is the Primary Tank.
Page 91
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 21C Notes: (Continued) If the Most Recent Delivery involves a non-Manifolded Tank: <SOH> I21CTT JUL 29, 1997 9:03 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..LAST DELIVERY REPORT T 1:REGULAR UNLEADED Fuel Fuel...
Page 92
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Current Siphon Manifolded Total Volumes Command Format: Display: <SOH>I21DTT Computer: <SOH>i21DTT Notes: TT - Tank Number (Decimal, 00=all). Typical Response Message, Display Format: <SOH> I21DTT JAN 31, 2008 14:42 SIPHON MANIFOLDED TANKS INVENTORY TOTALS TANK:PRODUCT 1:PRODUCT 1...
Page 93
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Hourly Inventory Volume Command Format: Display: <SOH>I21ETTyymmddhhmm Computer: <SOH>i21ETTyymmddhhmm Notes: yymmddhhmm - Inventory Hour to request starting with this date to the most recent. If no yymmddhhmm, return the most recent hourly record stored.
Page 94
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Manual Shift Inventory Snapshot Volume Command Format: Display: <SOH>I21Fssdd Computer: <SOH>i21Fssdd Notes: ss - Shift Number (00=All, 01, 02, 03, 04) (Decimal) dd - number Day of Shift (Decimal) 00=all days 01=current day 02=current day-1...
Page 95
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Tank Height Status Command Format: Display: <SOH>I21GTT Computer: <SOH>i21GTT Notes: TT - Tank Number (Decimal, 00=all). Typical Response Message, Display Format: <SOH> I21GTT JAN 31, 2008 14:42 TANK FUEL HEIGHT STATUS ---- ------------------...
Page 96
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Time Ordered Chart Sales Comparison Command Format: Display: <SOH>I21HTTIIiiyymmddYYMMDD Computer: <SOH>i21HTTIIiiyymmddYYMMDD Notes: TT - Tank Number [01..32], (Decimal, 00=all) II - First Chart ID Number [01…99] (Decimal) ii - Second chart ID number [01…99] (Decimal) yymmdd - Optional Start Date YYMMDD - Optional End Date This command will show all daily BIR records within the...
Page 97
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Time Ordered Chart Delivery Comparison Command Format: Display: <SOH>I21ITTIIiiyymmddYYMMDD Computer: <SOH>i21ITTIIiiyymmddYYMMDD Notes: TT - Tank Number [01..32], (Decimal, 00=all) II - First Chart ID Number [01…99] (Decimal) ii - Second Chart ID Number [01…99] (Decimal) yymmdd - Optional Start Date YYMMDD - Optional End Date This command will show all ticketed deliveries within the...
Page 98
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Histogram Comparison of Tank Charts Command Format: Display: <SOH>I21JTTIIiiyymmddYYMMDD Computer: <SOH>i21JTTIIiiyymmddYYMMDD Notes: TT - Tank Number [01..32], (Decimal, 00=all) II - First Chart ID Number [01…99] (Decimal) ii - Second Chart ID Number [01…99] (Decimal) yymmdd - Start Date YYMMDD - End Date Typical Response Message, Display Format:...
Page 99
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Error Plot Comparison of Tank Charts Command Format: Display: <SOH>I21KTTIIiiyymmddYYMMDD Computer: <SOH>i21KTTIIiiyymmddYYMMDD Notes: TT - Tank Number [01..32], (Decimal, 00=all) II - First Chart ID Number [01…99] (Decimal) ii - Second Chart ID Number [01…99] (Decimal) yymmdd - Optional Start Date YYMMDD - Optional End Date...
Page 100
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Manual Delivery Report Command Format: Display: <SOH>I21LTT Computer: not supported Typical Response Message, Display Format: <SOH> I21LTT JAN 31, 2009 14:42 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..
Page 101
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Regulator Tank Chart Report Command Format: Display: <SOH>I21MTTII Computer: <SOH>i21MTTII Notes: 1. This command works for a single Tank and a single Chart ID TT - Tank Number (Decimal) II - Chart ID Number [02…99] (Decimal) Typical Response Message, Display Format: <SOH>...
Page 102
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Tank Chart Report with Chart ID number Command Format: Display: <SOH>I21NTTIIhhhhhh Computer: <SOH>i21NTTIIFFFFFFFF Notes: 1. This command works for a single Tank and a single Chart ID TT - Tank Number (Decimal) II - Chart ID Number [01…99] (Decimal) hhhhhh - Height Step Size (inches or millimeters) FFFFFFFF - Height Step Size (ASCII Hex IEEE flaot)
Page 103
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Ticketed Delivery Report Command Format: Display: <SOH>I221TTtt Computer: <SOH>i221TTtt Notes: TT - Tank Number (Decimal, 00=all) tt - Report Type (if not entered will default to current) 01=current 02=previous Typical Response Message, Display Format: <SOH>...
Page 104
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Bill of Lading Report Command Format: Inquire: Display: <SOH>S222TTtt <SOH>I222TTtt Computer: <SOH>s222TTtt <SOH>i222TTtt Notes: TT - Tank Number (Decimal, 00=All) tt - Report Type (if tt is not entered, default is current) 01=current 02=previous Typical Response Message, Display Format:...
Page 105
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Periodic Delivery Variance Report Command Format: Display: <SOH>I225TTtt Computer: <SOH>i225TTtt Notes: TT - Tank Number (Decimal, 00=all) tt - Report Type (if not entered will default to current) 01=current 02=previous Typical Response Message, Display Format:...
Page 106
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Weekly Delivery Variance Report Command Format: Display: <SOH>I226TTtt Computer: <SOH>i226TTtt Notes: TT - Tank Number (Decimal, 00=all) tt - Report Type (if not entered will default to current) 01=current 02=previous Typical Response Message, Display Format:...
Page 107
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Daily Delivery Variance Report Command Format: Display: <SOH>I227TTMMDD Computer: <SOH>i227TTMMDD Notes: TT - Tank number MMDD - Month and day for Daily Report, if left blank will report current date Typical Response Message, Display Format: <SOH>...
Page 108
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Ticketed Delivery Daily Report Command Format: Display: <SOH>I22ITTyymmddYYMMDDnnn Computer: <SOH>i22ITTyymmddYYMMDDnnn Notes: TT - Tank Number (Decimal, 00=All) yymmdd - Starting Date (000000 = no starting date = first of the month) YYMMDD - Ending Date (000000 = no ending date = current date) nnn - Maximum Records [001…366] (100 = default) (decimal)
Page 109
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Delivery Ticket History Report Command Format: Display: <SOH>I22JTTyymmddYYMMDDnnn Computer: not supported Notes: TT - Tank Number (Decimal, 00=All) yymmdd - Starting Date (000000 = no starting date = first of the month) YYMMDD - Ending Date (000000 = no ending date = current date) nnn - Maximum Records [001…366] (100 = default) (decimal)
Page 110
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Full Inventory Report Command Format: Display: <SOH>I231TT Computer: <SOH>I231TT Typical Response Message, Display Format: <SOH> I23100 16-06-11 07:35 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..
Page 111
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Density Offset History Report Command Format: Display: <SOH>I233PP Computer: <SOH>i233PP Typical Response Message, Display Format: <SOH> I233PP 28-07-11 10:51 DENSITY OFFSET HISTORY REPORT T 1:REGULAR UNLEADED DATE / TIME DENSITY TEMP TC DENSITY...
Page 112
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: In-Tank Mass/Density Inventory Report Command Format: Display: <SOH>I234TT Computer: <SOH>i234TT Typical Response Message, Display Format: <SOH> I234TT MAR 20, 2010 3:25 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 113
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: In-Tank Mass/Density Delivery Report Command Format: Display: <SOH>I235TT Computer: <SOH>i235TT Typical Response Message, Display Format: <SOH> I235TT APR 30, 2010 3:25 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 114
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 235: (Continued) Typical Response Message, Computer Format: <SOH>i235TTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFFf... TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFFf...&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=All) p - Product Code (one ASCII character [20h-7Eh]) dd - Number of Deliveries to follow (Decimal, 00=no data) YYMMDDHHmm - Starting Date/Time YYMMDDHHmm - Ending Date/Time NN - Number of eight character Data Fields to follow (Hex)
Page 115
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Product Inventory Report Command Format: Display: <SOH>I237TT Computer: <SOH>i237TT Typical Response Message, Display Format: <SOH> I237TT JAN 22, 2012 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 116
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Siphon Manifolded Inventory Report Command Format: Display: <SOH>I238TT Computer: <SOH>i238TT Typical Response Message, Display Format: <SOH> I238TT JAN 22, 2012 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 117
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: In-Tank Manifolded Delivery Report With Sales Adjustment if BIR available Command Format: Display: <SOH>I239TT Computer: <SOH>i239TT Typical Response Message, Display Format: <SOH> I239TT JUL 29, 2012 9:02 AM STATION HEADER 1..
Page 118
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: In-Tank Manifolded Delivery Report with Sales Adjustment if BIR available Command Format: Display: <SOH>I23ATT Computer: <SOH>i23ATT Typical Response Message, Display Format: <SOH> I23ATT JAN 22, 2009 3:08 PM STATION HEADER 1..
Page 119
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: BIR Adjusted Mass/Density Delivery Report Command Format: Display: <SOH>I23BTT Computer: <SOH>i23BTT Typical Response Message, Display Format: <SOH> I23BTT JAN 22, 2009 3:08 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 120
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 23B: (Continued) Typical Response Message, Computer Format: <SOH>i23BTTYYMMDDHHmmTTddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... TTddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=All) dd - Number of Deliveries to follow YYMMDDHHmm - Starting Date/Time YYMMDDHHmm - Ending Date/Time NN - Number of eight character Data Fields to follow (Hex) FFFFFFFF - ASCII Hex IEEE floats:...
Page 121
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: CSLD Results Report Command Format: Display: <SOH>I251TT Computer: <SOH>i251TT Typical Response Message, Display Format: <SOH> I251TT JAN 22, 1996 3:09 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..
Page 122
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Inventory History Report Command Format: Display: <SOH>I2E3TTyymmddYYMMDDnnn Computer: <SOH>i2E3TTyymmddYYMMDDnnn Notes: YYMMDDHHmm - Starting Date (000000 = no starting date) YYMMDD - Ending Date (000000 = no ending date) nnn - Maximum Records [001…999] (100 = default) (decimal) Typical Response Message, Display Format:...
Page 123
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Extended In-Tank Inventory Report – Date/Time Based Command Format: Display: <SOH>I2E4TTRRyymmddhhmmYYMMDDHHMMnnn Computer: <SOH>i2E4TTRRyymmddhhmmYYMMDDHHMMnnn Notes: TT - Device Number (Decimal, 00=all) RR - Report Type (Report Type should always be given. The rest of the parameters are optional following the rules below.) 00=Inventory History Report (Inventory Information for the specified Time Period)
Page 124
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 2E4: (Continued) Typical Response Message, Computer Format: <SOH>i2E4TTYYMMDDHHmmTTpnnnnssssYYMMDDHHmmNNFFFFFFFF... ssssYYMMDDHHmmNNFFFFFFFF... TTpnnnnssssYYMMDDHHmmNNFFFFFFFF... ssssYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: 1. YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=all) p - Product Code (one ASCII character [20h-7Eh]) nnnn –...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.2.3 SENSOR REPORTS Function Code: Version 1 Function Type: Liquid Sensor Status Report Command Format: Display: <SOH>I301SS Computer: <SOH>i301SS Typical Response Message, Display Format: <SOH> I301SS JAN 28, 1995 10:10 AM STATION HEADER 1..STATION HEADER 2..
Page 126
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Liquid Sensor Alarm History Report Command Format: Display: <SOH>I302SS Computer: <SOH>i302SS Typical Response Message, Display Format: <SOH> I302SS JAN 28, 1995 10:10 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 127
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Vapor Sensor Status Report Command Format: Display: <SOH>I306SS Computer: <SOH>i306SS Typical Response Message, Display Format: <SOH> I306SS JAN 28, 1995 10:11 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 128
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Vapor Sensor Alarm History Report Command Format: Display: <SOH>I307SS Computer: <SOH>i307SS Typical Response Message, Display Format: <SOH> I307SS JAN 28, 1995 10:11 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 129
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Groundwater Sensor Status Report Command Format: Display: <SOH>I311SS Computer: <SOH>i311SS Typical Response Message, Display Format: <SOH> I311SS JAN 28, 1995 10:11 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 130
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Groundwater Sensor Alarm History Report Command Format: Display: <SOH>I312SS Computer: <SOH>i312SS Typical Response Message, Display Format: <SOH> I312SS JAN 28, 1995 10:11 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 131
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: MAG Sensor Status Report Command Format: Display: <SOH>I31BSS Computer: <SOH>i31BSS Typical Response Message, Display Format: <SOH> I31BSS JAN 22, 2003 3:07 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 132
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: MAG Sensor Alarm History Report Command Format: Display: <SOH>I31CSS Computer: <SOH>i31CSS Typical Response Message, Display Format: <SOH> I31CSS JAN 22, 2003 3:07 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 133
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Pump Relay Monitor Status Report Command Format: Display: <SOH>I322QQ Computer: <SOH>i322QQ Typical Response Message, Display Format: <SOH> I322QQ JUN 22, 2014 3:12 PM PUMP RELAY MONITOR STATUS REPORT PUMP PUMP RELAY DEVICE...
Page 134
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Pump Relay Monitor Alarm History Report Command Format: Display: <SOH>I323QQ Computer: <SOH>i323QQ Typical Response Message, Display Format: <SOH> I323QQ JUN 22, 2014 3:12 PM PUMP RELAY MONITOR ALARM HISTORY REPORT DEVICE LABEL PUMP RELAY UNLEADED...
Page 135
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Type A (2 Wire CL) Sensor Status Report Command Format: Display: <SOH>I341SS Computer: <SOH>i341SS Typical Response Message, Display Format: <SOH> I341SS FEB 18, 1990 10:53 AM STATION HEADER 1..STATION HEADER 2..
Page 136
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Type A (2 Wire CL) Sensor Alarm History Report Command Format: Display: <SOH>I342SS Computer: <SOH>i342SS Typical Response Message, Display Format: <SOH> I342SS FEB 18, 1990 10:53 AM STATION HEADER 1..STATION HEADER 2..
Page 137
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Type B (3 Wire CL) Sensor Status Report Command Format: Display: <SOH>I346SS Computer: <SOH>i346SS Typical Response Message, Display Format: <SOH> I346SS FEB 18, 1990 10:53 AM STATION HEADER 1..STATION HEADER 2..
Page 138
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Type B (3 Wire CL) Sensor Alarm History Report Command Format: Display: <SOH>I347SS Computer: <SOH>i347SS Typical Response Message, Display Format: <SOH> I347SS FEB 18, 1990 10:53 AM STATION HEADER 1..STATION HEADER 2..
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.2.4 LINE LEAK REPORTS Function Code: Version 1 Function Type: Pressure Line Leak Test Results (with 0.20 test data) Command Format: Display: <SOH>I373QQ Computer: <SOH>i373QQ Typical Response Message, Display Format: <SOH> I373QQ JAN 24, 1996 2:52 PM STATION HEADER 1..
Page 140
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 373: (Continued) Typical Response Message, Computer Format: <SOH>i373QQYYMMDDHHmmQQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt... nnYYMMDDHHmmRRtt... QQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt... nnYYMMDDHHmmRRtt&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time QQ - Pressure Line Leak sensor number (Decimal, 00=All) yymmddhhmm - Last 3.00 gal/hr test time rr - 3.00 gal/hr test result (Hex) TT - 3.00 gal/hr test type (unused, always 00) PPPP - Number of 3.00 gal/hr tests passed in previous 24 hours (Hex)
Page 141
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Test History (with 0.20 test data) Command Format: Display: <SOH>I374QQ Computer: <SOH>i374QQ Typical Response Message, Display Format: <SOH> I374QQ JAN 24, 1996 2:52 PM STATION HEADER 1..STATION HEADER 2..
Page 142
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Test Results II (with 0.20 test data) Command Format: Display: <SOH>I375QQ Computer: <SOH>i375QQ Typical Response Message, Display Format: <SOH> I375QQ JAN 24, 1996 2:52 PM STATION HEADER 1..
Page 143
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 375: (Continued) Typical Response Message, Computer Format: <SOH>i375QQYYMMDDHHmmQQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt nnYYMMDDHHmmRRttaabb... QQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt nnYYMMDDHHmmRRttaabb&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time QQ - Pressure Line Leak sensor number (Decimal, 00=All) yymmddhhmm - Last 3.0 gal/hr test time rr - 3.0 gal/hr test result (Hex) TT - 3.0 gal/hr test type (unused, always 00) PPPP - Number of 3.0 gal/hr tests passed in previous 24 hours (Hex)
Page 144
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Passed Tests Results Command Format: Display: <SOH>I376QQ Computer: <SOH>i376QQ Typical Response Message, Display Format: <SOH> I376QQ JAN 24, 1996 2:52 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 145
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Extended Pressure Line Leak Test History (with 0.20 test data) Command Format: Display: <SOH>I377QQRRyymmddhhmmYYMMDDHHMMnn Computer: <SOH>i377QQRRyymmddhhmmYYMMDDHHMMnn Notes: QQ - Device Number (Decimal, 00=all) RR - Report Type (Report Type should always be given. The rest of the parameters are optional following the rules below.) 00=Passed Test History yyyymmddhhmm - Starting Date/Time (If a start date/time is not provided or...
Page 146
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 377: (Continued) Typical Response Message, Display Format: <SOH> I377QQ 6, 2008 10:35 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..PRESSURE LINE LEAK REPORTS - PASSED TESTS HISTORY Ln 1: PRESSURE LLD #1 Test Gross Test...
Page 147
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 377: (Continued) Typical Response Message, Computer Format: <SOH>i377QQYYMMDDHHmmQQPPPPMMMMyymmddhhmmTTyymmddhhmmTTyymmddhhmmTT NNYYMMDDHHmmtt...YYMMDDHHmmttnnYYMMDDHHmmtt...YYMMDDHHmmtt... QQPPPPMMMMyymmddhhmmTTyymmddhhmmTTyymmddhhmmTT NNYYMMDDHHmmtt...YYMMDDHHmmttnnYYMMDDHHmmtt...YYMMDDHHmmtt&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time QQ - Pressure Line Leak sensor number (Decimal, 00 = All) PPPP - Number of 3.0 gal/hr tests passed in previous 24 hours (Hex) MMMM - Number of 3.0 gal/hr tests passed since midnight (Hex) yymmddhhmm - Last 3.0 gal/hr test time (0000000000 if no test) TT - 3.0 gal/hr test type (unused, always 00)
Page 148
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Status Command Format: Display: <SOH>I381QQ Computer: <SOH>i381QQ Typical Response Message, Display Format: <SOH> I381QQ JAN 24, 1996 2:52 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 149
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 381 Notes: (Continued) NN - number of active alarms to follow (Hex) aaaa - type of alarm: 0001=PLLD Setup Data Warning 0002=PLLD Gross Test Fail Alarm 0003=PLLD Annual Test Fail Alarm 0004=PLLD Periodic Test Needed Warning 0005=PLLD Periodic Test Needed Alarm 0006=PLLD Sensor Open Alarm 0007=PLLD High Pressure Alarm...
Page 150
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Alarm History Report Command Format: Display: <SOH>I382QQ Computer: <SOH>i382QQ Typical Response Message, Display Format: <SOH> I382QQ JAN 24, 1996 2:52 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 151
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Test Results (0.10 test data only) Command Format: Display: <SOH>I383QQ Computer: <SOH>i383QQ Typical Response Message, Display Format: <SOH> I383QQ JAN 24, 1996 2:52 PM STATION HEADER 1..STATION HEADER 2..
Page 152
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Test History (0.10 test data only) Command Format: Display: <SOH>I384QQ Computer: <SOH>i384QQ Typical Response Message, Display Format: <SOH> I384QQ JAN 24, 1996 2:52 PM STATION HEADER 1..STATION HEADER 2..
Page 153
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Test Results (with 0.20 test data listed before 0.10 test data) Command Format: Display: <SOH>I385QQ Computer: <SOH>i385QQ Typical Response Message, Display Format: <SOH> I385QQ JAN 24, 1996 2:52 PM STATION HEADER 1..
Page 154
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 385: (Continued) Typical Response Message, Computer Format: <SOH>i385QQYYMMDDHHmmQQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt... nnYYMMDDHHmmRRtt... QQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt... nnYYMMDDHHmmRRtt&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time QQ - Pressure Line Leak sensor number (Decimal, 00=All) yymmddhhmm - Last 3.00 gal/hr test time rr - 3.00 gal/hr test result (Hex) TT - 3.00 gal/hr test type (unused, always 00) PPPP - Number of 3.00 gal/hr tests passed in previous 24 hours (Hex)
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.2.5 I/O DEVICE REPORTS Function Code: Version 1 Function Type: Input Status Report Command Format: Display: <SOH>I401II Computer: <SOH>i401II Typical Response Message, Display Format: <SOH> I401II MAR 27, 1996 5:44 PM STATION HEADER 1..STATION HEADER 2..
Page 156
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Input Alarm History Report Command Format: Display: <SOH>I402II Computer: <SOH>i402II Typical Response Message, Display Format: <SOH> I402II MAR 27, 1996 5:45 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 157
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Input/Generator Alarm History Report (Setup parameters determine whether an input is from a generator.) Command Format: Display: <SOH>I403II Computer: <SOH>i403II Typical Response Message, Display Format: <SOH> I403II MAR 27, 1996 5:47 PM STATION HEADER 1..
Page 158
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Relay Status Report Command Format: Display: <SOH>I406RR Computer: <SOH>i406RR Typical Response Message, Display Format: <SOH> I406RR MAR 27, 1996 5:47 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..
Page 159
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Input Diagnostics Command Format: Display: <SOH>I407II Computer: <SOH>i407II Typical Response Message, Display Format: <SOH> I407II MAR 27, 1996 5:47 PM INPUT DIAGNOSTIC REPORT ADDRESS STATUS DURATION TYPE B1.S4.1 Active 0000 01:01:28 Standard...
Page 160
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Relay Diagnostics Command Format: Display: <SOH>I408RR Computer: <SOH>i408RR Typical Response Message, Display Format: <SOH> I408RR MAR 27, 1996 5:47 PM RELAY DIAGNOSTIC REPORT ADDRESS STATUS DURATION TYPE B1.S4.1 Active 0000 01:01:28 Standard...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3 SETUP FUNCTIONS & REPORTS 7.3.1 SYSTEM SETUP Function Code: Version 1 Function Type: Set Time of day Command Format: Inquire: Display: <SOH>S50100YYMMDDHHmm <SOH>I50100 Computer: <SOH>s50100YYMMDDHHmm <SOH>i50100 Typical Response Message, Display Format: <SOH> I50100 JAN 22, 1996 3:11 PM SYSTEM DATE AND TIME...
Page 162
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Shift Close Time Command Format: Inquire: Display: <SOH>S502SSHHmm <SOH>I502SS Computer: <SOH>s502SSHHmm <SOH>i502SS Notes: SS - Shift 01-08 All Shifts (SS=00) not available for Set or Inquiry Mode Typical Response Message, Display Format: <SOH>...
Page 163
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Print Header Line 1, 2, 3, 4 Command Format: Inquire: Display: <SOH>S503LLaaaaaaaaaaaaaaaaaaaa <SOH>I503LL Computer: <SOH>s503LLaaaaaaaaaaaaaaaaaaaa <SOH>i503LL Typical Response Message, Display Format: <SOH> I503LL JAN 22, 1996 3:12 PM # 1:STATION HEADER 1..
Page 164
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Print Temperature Compensation Flag Command Format: Inquire: Display: <SOH>S50D00f <SOH>I50D00 Computer: <SOH>s50D00f <SOH>i50D00 Typical Response Message, Display Format: <SOH> I50D00 JAN 22, 1996 3:13 PM PRINT TC VOLUMES ENABLED <ETX>...
Page 165
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Temperature Compensation Value Command Format: Inquire: Display: <SOH>S50E00DDD.hh <SOH>I50E00 Computer: <SOH>s50E00FFFFFFFF <SOH>i50E00 Notes: DDD.hh - Compensation Temperature, Degrees and hundredths (Decimal) FFFFFFFF - Compensation Temperature, Degrees (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 166
JAN 22, 2008 3:12 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..FAX SENDER NAME: Veeder-Root <ETX> Typical Response Message, Computer Format: <SOH>i50G00YYMMDDHHmmnnaaaaaaaaaaaaaaaaaaaa&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time nn - Number of characters in Fax Sender Name (00-30)
Page 167
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Header - Fax Number Command Format: Inquire: Display: <SOH>S50H00aaaa……aaaa <SOH>I50H00 Computer: <SOH>s50H00aaaa……aaaa <SOH>i50H00 Notes: Enter ONLY S50H00 to remove Fax Number Typical Response Message, Display Format: <SOH> I50H00 JAN 22, 2008 3:12 PM...
Page 168
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup - Number Format Command Format: Inquire: Display: <SOH>S50I00ab <SOH>I50I00 Computer: <SOH>s50I00ab <SOH>i50I00 Typical Response Message, Display Format: <SOH> I50I00 JAN 22, 2007 3:16 PM DISPLAY SETUP – NUMBER FORMAT Decimal Separator Thousands Separator: .
Page 169
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – Date & Time Format Command Format: Inquire: Display: <SOH>S50J00FFc <SOH>I50J00FF Computer: <SOH>s50J00FFc <SOH>i50J00FF Notes: FF - Field, 00=all Fields, but only valid for Inquiry 01=Date Format 02=Date Separator 03=Time Format...
Page 170
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Inventory Maximum Number of Shifts per Day Command Format: Inquire: Display: <SOH>S50K00N <SOH>I50K00 Computer: <SOH>s50K00N <SOH>i50K00 Typical Response Message, Display Format: <SOH> I50K00 JAN 22, 2009 3:06 PM INVENTORY MAXIMUM NUMBER OF SHIFTS PER DAY MAX.
Page 171
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Inventory Setup Command Format: Display: <SOH>I50L00 Computer: not supported Typical Response Message, Display Format: <SOH> I50L00 JAN 16, 2009 3:15 PM INVENTORY SETUP – SHIFT CLOSE METHOD CLOSE METHOD: SNAPSHOT CLOSE TIMEOUT: NUMBER OF SHIFT PER DAY: 4...
Page 172
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Delivery Setup Command Format: Display: <SOH>I50M00 Computer: not supported Typical Response Message, Display Format: <SOH> I50M00 JAN 16, 2009 3:15 PM DELIVERY SETUP DELIVERY METHOD: STANDARD AUTOMATIC TICKETED DELIVERY: ENABLED TC TICKETED DELIVERY: TC VOLUME <ETX>...
Page 173
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Reconciliation Setup Command Format: Display: <SOH>I50N00 Computer: not supported Typical Response Message, Display Format: <SOH> I50N00 JAN 16, 2009 3:15 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..
Page 174
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 50N: (Continued) BIR MULTIPLE THRESHOLD SETUP REPORT TEST TEST THRESHOLD OFFSET NUMBER TYPE TYPE CONFIG PERCENT VALUE ------ --------------------------- --------------- --------- ------- ------ Monthly 1-Throughput Enabled 1.00 2-Capacity Disabled 1.00 3-Delivery Disabled 1.00 4-Fixed Disabled...
Page 175
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set BIR Shift Close Warning Command Format: Inquire: Display: <SOH>S51100f <SOH>I51100 Computer: <SOH>s51100f <SOH>i51100 Typical Response Message, Display Format: <SOH> I51100 JAN 22, 2009 3:06 PM BIR SHIFT CLOSE PENDING ENABLED <ETX>...
Page 176
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type:Set BIR Daily Close Warning Command Format: Inquire: Display: <SOH>S51200f <SOH>I51200 Computer: <SOH>s51200f <SOH>i51200 Typical Response Message, Display Format: <SOH> I51200 JAN 22, 2009 3:06 PM BIR DAILY CLOSE PENDING ENABLED <ETX>...
Page 177
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set H-Protocol Height/Volume Format Command Format: Inquire: Display: <SOH>S51400f <SOH>I51400 Computer: <SOH>s51400f <SOH>i51400 Typical Response Message, Display Format: <SOH> I51400 JAN 24, 1996 2:53 PM H-PROTOCOL DATA FORMAT HEIGHT <ETX>...
Page 178
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set System Type & Language Flags Command Format: Inquire: Display: <SOH>S51700ULL <SOH>I51700 Computer: <SOH>s51700ULL <SOH>i51700 Typical Response Message, Display Format: <SOH> I51700 JUL 29, 1997 9:03 AM DISPLAY SETUP - LANGUAGE & UNITS SYSTEM LANGUAGE ENGLISH SYSTEM UNITS <ETX>...
Page 179
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set PLLD Duration Before Precision Retest Command Format: Inquire: Display: <SOH>S51900DDD <SOH>I51900 Computer: <SOH>s51900DDD <SOH>i51900 Typical Response Message, Display Format: <SOH> I51900 JUL 29, 1997 9:04 AM PRECISION TEST DURATION HOURS: 12 <ETX>...
Page 180
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Enable/Disable Auto Daylight Saving Time Command Format: Inquire: Display: <SOH>S51A00f <SOH>I51A00 Computer: <SOH>s51A00f <SOH>i51A00 Typical Response Message, Display Format: <SOH> I51A00 JUL 29, 1997 9:04 AM DAYLIGHT SAVING TIME ENABLED ON <ETX>...
Page 181
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Start/End Daylight Saving Date and Time Command Format: Inquire: Display: <SOH>S51BttMMODHHmm <SOH>I51Btt Computer: <SOH>s51BttMMODHHmm <SOH>i51Btt Notes: tt - Start or End Time Indicator 01=Start Date & Time 02=End Date &...
Page 182
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Ticketed Delivery Flag Enable Command Format: Inquire: Display: <SOH>S51C00f <SOH>I51C00 Computer: <SOH>s51C00f <SOH>i51C00 Typical Response Message, Display Format: <SOH> I51C00 JUL 29, 2009 9:04 AM TICKETED DELIVERY ENABLED <ETX>...
Page 183
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Ticketed Delivery Temperature Compensation Flag Command Format: Inquire: Display: <SOH>S51D00f <SOH>I51D00 Computer: <SOH>s51D00f <SOH>i51D00 Typical Response Message, Display Format: <SOH> I51D00 JUL 29, 2009 9:04 AM TICKETED DELIVERY TEMP COMPENSATION STANDARD <ETX>...
Page 184
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Ticketed Delivery Close Day of Week Command Format: Inquire: Display: <SOH>S51E00D <SOH>I51E00 Computer: <SOH>s51E00D <SOH>i51E00 Typical Response Message, Display Format: <SOH> I51E00 AUG 28, 2009 4:29 PM CLOSE DAY OF WEEK <ETX>...
Page 185
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Euro Protocol Prefix Command Format: Inquire: Display: <SOH>S51F00c <SOH>I51F00 Computer: <SOH>s51F00c <SOH>i51F00 Typical Response Message, Display Format: <SOH> I51F00 AUG 28, 2009 4:29 PM EURO PROTOCOL PREFIX <ETX>...
Page 186
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Enable/Disable Custom Help View and Custom Help Edit. Command Format: Inquire: Display: <SOH>S51G00ve <SOH>I51G00 Computer: <SOH>s51G00ve <SOH>i51G00 Typical Response Message, Display Format: <SOH> I51G00 JUN 22, 2001 3:15 PM CUSTOM HELP VIEW AND EDIT VIEW:ENABLED...
Page 187
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Front Panel Security Command Format: Inquire: Display: <SOH>S51H00faaaaaaaaaa <SOH>I51H00 Computer: <SOH>s51H00faaaaaaaaaa <SOH>i51H00 Notes: f – Enable or Disable Status (if disabled no password is required) aaaaaaaaaa – Password (3 to 10 ASCII Characters from 21h – 7Eh) Typical Response Message, Display Format: <SOH>...
Page 188
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Delivery Method Command Format: Inquire: Display: <SOH>S51M00T <SOH>I51M00 Computer: <SOH>s51M00T <SOH>i51M00 Typical Response Message, Display Format: <SOH> I51M00 JUN 22, 2009 3:12 PM DELIVERY METHOD STANDARD AUTOMATIC <ETX>...
Page 189
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: Set HRM Feature Enable Flag Command Format: Inquire: Display: <SOH>S51R00f <SOH>I51R00 Computer: <SOH>s51R00f <SOH>i51R00 Typical Response Message, Display Format: <SOH> I51R00 JUN 22, 2011 3:12 PM HRM FEATURE ENABLE FLAG ENABLED <ETX>...
Page 190
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Time Zone Command Format: Inquire: Display: <SOH>S51S00zzzz...zzzz <SOH>I51S00 Computer: <SOH>s51S00zzzz...zzzz <SOH>i51S00 Typical Response Message, Display Format: <SOH> I51S00 Feb 22, 2012 3:11 PM Time Zone : America/New_York Zone Info : EST EDT Comment UTC Offset: UTC-05:00...
Page 191
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Enable User Ullage Command Format: Inquire: Display: <SOH>S57100e <SOH>I57100 Computer: <SOH>s57100e <SOH>i57100 Typical Response Message, Display Format: <SOH> I57100 JUN 22, 2008 3:15 PM USER ULLAGE: ENABLED <ETX> Typical Response Message, Computer Format: <SOH>i57100YYMMDDHHmme&&CCCC<ETX>...
Page 192
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set User Ullage Percent Command Format: Inquire: Display: <SOH>S57200fff <SOH>I57200 Computer: <SOH>s57200fff <SOH>i57200 Note: Valid Ullage Percent Range (Integer), 90-100% Typical Response Message, Display Format: <SOH> I57200 JUN 22, 2008 3:15 PM USER ULLAGE: 90% <ETX>...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.2 COMMUNICATIONS SETUP Function Code: (Obsolete V2 - See New Command 872) Version 1 Function Type: Set Receiver Configuration Flag Command Format: Inquire: Display: <SOH>S521RRf <SOH>I521RR Computer: <SOH>s521RRf <SOH>i521RR Typical Response Message, Display Format: <SOH>...
Page 194
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: (Obsolete V2 - See New Command 874) Version 1 Function Type: Set Receiver Location Label Command Format: Inquire: Display: <SOH>S522RRaaaaaaaaaaaaaaaaaaaa <SOH>I522RR Computer: <SOH>s522RRaaaaaaaaaaaaaaaaaaaa <SOH>i522RR Typical Response Message, Display Format: <SOH> I522RR JAN 22, 1996 3:14 PM RECEIVER LABEL DEVICE...
Page 195
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Autodial Alarm Status Command Format: Inquire: Display: <SOH>S52DRRf <SOH>I52DRR Computer: <SOH>s52DRRf <SOH>i52DRR Notes: RR - Receiver number (00=all) f - Alarm clear flag 1=clear; all others ignored Typical Response Message Display Format: <SOH>...
Page 196
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: COMM DIM Setup Command Format: Display: <SOH>I52GDD Computer: not supported Notes: DD - COMM number (00=all) Typical Response Message, Display Format: TLS-450 <SOH> I52GDD 16, 2009 8:06 AM GENERAL COMM SETUP COMM 1: CONFIGURED:...
Page 197
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 52G: (Continued) TLS-4 <SOH> I52GDD 16, 2009 8:06 AM GENERAL COMM SETUP COMM 1: CONFIGURED: ENABLED DEVICE: EDIM CARD LABEL: EDIM 1 DIM PROTOCOL: VRPROTOCOLDIM BAUD RATE: 9600 DATA BITS: PARITY: STOP BITS: HAND_SHAKING: NO HANDSHAKING PROTOCOL COMM SETUP...
Page 198
12=Low Volt Mechanical (V2) 13=Wayne ID POS (V4) 14=Smart Crind 15=Tominaga 16=Bennett 17=UK Block 18=Scheidt Bach Typical Response Message, Display Format: <SOH> I52H00 JAN 22, 2009 3:12 PM DIM PROTOCOL COMM LOCATION PROTOCOL OFFICE Veeder-Root <ETX> Part No. 577013-950, Revision L...
Page 199
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 52H: (Continued) Typical Response Message, Computer Format: <SOH>i52HPPYYMMDDHHmmPPdd&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Comm Number (Decimal) dd - DIM Protocol 00=Unknown DIM 01=Gilbarco EDIM (V2) 02=Gilbarco CL (V2) 03=Tokheim 67AB 04=Tokheim DHC 05=Wayne CL...
Page 200
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Beeper Enable/Disable Command Format: Inquire: Display: <SOH>S53000x149 <SOH>I53000 Computer: <SOH>s53000x149 <SOH>i53000 Notes: 149 - This verification code must be sent to confirm the command Typical Response Message, Display Format: <SOH>...
Page 201
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set RS-232 End of Message Command Format: Inquire: Display: <SOH>S531PPf <SOH>I531PP Computer: <SOH>s531PPf <SOH>i531PP Typical Response Message, Display Format: <SOH> I531PP JAN 22, 1996 3:16 PM RS-232 END OF MESSAGE COMM LABEL END OF MESSAGE...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.3 WARNING, ALARM, & AUTO-PRINT SETUP Function Code: Version 1 Function Type: Set RS-232 Security Code per Port Command Format: Inquire: Display: <SOH>S536PPsaaaaaa <SOH>I536PP Computer: <SOH>s536PPsaaaaaa <SOH>i536PP Notes: PP - Port number (Decimal, 01..03 [..06]; 99=this port) s - Enable or Disable Status (if disabled no password is required) aaaaaa - Security code (6 ASCII characters from 20 Hex-7E Hex) Typical Response Message, Display Format:...
Page 203
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Format RS-232 ETX per Port Command Format: Inquire: Display: <SOH>S537PPAB <SOH>I537PP Computer: <SOH>s537PPAB <SOH>i537PP Notes: PP - Port number (Decimal, 01..06]; 99=this port) A - ETX CHAR 1 (value 0-255) B - ETX CHAR 2 (value 0-255) The default end of message character transmitted by the TLS is an <ETX>...
Page 204
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Computer Format RS-232 ETX per Port Command Format: Inquire: Display: <SOH>S538PPAB <SOH>I538PP Computer: <SOH>s538PPAB <SOH>i538PP Notes: PP - Port number (Decimal, 01..06]; 99=this port) A - ETX CHAR 1 (value 0-255) B - ETX CHAR 2 (value 0-255) The default end of message character transmitted by the TLS is an <ETX>...
Page 205
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Shift Close Method Command Format: Inquire: Display: <SOH>S53A00M <SOH>I53A00 Computer: <SOH>s53A00M <SOH>i53A00 Typical Response Message, Display Format: <SOH> I53A00 1, 2009 8:06 AM SHIFT CLOSE METHOD: MANUAL <ETX>...
Page 206
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Set TC Density Enable Command Format: Inquire: Display: <SOH>S54500f <SOH>I54500 Computer: <SOH>s54500f <SOH>i54500 Typical Response Message, Display Format: <SOH> I54500 1, 2010 8:06 AM TC DENSITY ENABLED <ETX> Typical Response Message, Computer Format: <SOH>i54500YYMMDDHHmmf&&CCCC<ETX>...
Page 207
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Periodic Test Needed Warning Command Format: Inquire: Display: <SOH>S54600f <SOH>I54600 Computer: <SOH>s54600f <SOH>i54600 Typical Response Message, Display Format: <SOH> I54600 JAN 22, 1996 3:12 PM TANK PER TEST NEEDED WRN: DISABLED <ETX>...
Page 208
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Days Before Tank Periodic Test Needed Warning Command Format: Inquire: Display: <SOH>S54700dd <SOH>I54700 Computer: <SOH>s54700dd <SOH>i54700 Typical Response Message, Display Format: <SOH> I54700 JAN 22, 1996 3:12 PM TANK PER TEST NEEDED WRN: DAYS= 25 <ETX>...
Page 209
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Days Before Tank Periodic Test Needed Alarm Command Format: Inquire: Display: <SOH>S54800dd <SOH>I54800 Computer: <SOH>s54800dd <SOH>i54800 Typical Response Message, Display Format: <SOH> I54800 JAN 22, 1996 3:12 PM TANK PER TEST NEEDED ALM: DAYS= 30 <ETX>...
Page 210
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Annual Test Needed Warning Command Format: Inquire: Display: <SOH>S54900f <SOH>I54900 Computer: <SOH>s54900f <SOH>i54900 Typical Response Message, Display Format: <SOH> I54900 JAN 22, 1996 3:12 PM TANK ANN TEST NEEDED WRN: DISABLED <ETX>...
Page 211
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Days Before Tank Annual Test Needed Warning Command Format: Inquire: Display: <SOH>S54A00ddd <SOH>I54A00 Computer: <SOH>s54A00ddd <SOH>i54A00 Typical Response Message, Display Format: <SOH> I54A00 JAN 22, 1996 3:12 PM TANK ANN TST NEEDED WRN: DAYS=355 <ETX>...
Page 212
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Days Before Tank Annual Test Needed Alarm Command Format: Inquire: Display: <SOH>S54B00ddd <SOH>I54B00 Computer: <SOH>s54B00ddd <SOH>i54B00 Typical Response Message, Display Format: <SOH> I54B00 JAN 22, 1996 3:12 PM TANK ANN TEST NEEDED ALM: DAYS=365 <ETX>...
Page 213
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set CSLD Evaporation Reid Vapor Pressure Chart Command Format: Inquire: Display: <SOH>S54C00GG.G... <SOH>I54C00 Computer: <SOH>s54C00FFFFFFFF... <SOH>i54C00 Notes: GG.G - 12 Reid Vapor Pressures (Decimal) FFFFFFFF - 12 Reid Vapor Pressures (ASCII Hex IEEE floats) The command will be rejected if any value is outside the range 0.0 to 15.0, or all table values are zero.
Page 214
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Line Re-Enable Method Command Format: Inquire: Display: <SOH>S55300f <SOH>I55300 Computer: <SOH>s55300f <SOH>i55300 Typical Response Message, Display Format: <SOH> I55300 JAN 24, 2000 2:54 PM LINE RE-ENABLE METHOD PASS LINE TEST <ETX>...
Page 215
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Periodic Line Leak Test Auto-Confirm Command Format: Inquire: Display: <SOH>S55400f <SOH>I55400 Computer: <SOH>s55400f <SOH>i55400 Typical Response Message, Display Format: <SOH> I55400 JUL 29, 1997 9:07 AM 0.20 GPH LINE TEST AUTO-CONFIRM: ENABLED <ETX>...
Page 216
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Annual Line Leak Test Auto-Confirm Command Format: Inquire: Display: <SOH>S55500f <SOH>I55500 Computer: <SOH>s55500f <SOH>i55500 Typical Response Message, Display Format: <SOH> I55500 JUL 29, 1997 9:07 AM 0.10 GPH LINE TEST AUTO-CONFIRM: ENABLED <ETX>...
Page 217
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Line Periodic Test Needed Warning Command Format: Inquire: Display: <SOH>S55600f <SOH>I55600 Computer: <SOH>s55600f <SOH>i55600 Typical Response Message, Display Format: <SOH> I55600 JAN 22, 1996 3:12 PM LINE PER TST NEEDED WRN: DISABLED <ETX>...
Page 218
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Days Before Line Periodic Test Needed Warning Command Format: Inquire: Display: <SOH>S55700dd <SOH>I55700 Computer: <SOH>s55700dd <SOH>i55700 Typical Response Message, Display Format: <SOH> I55700 JAN 22, 1996 3:12 PM LINE PER TST NEEDED WRN: DAYS= 25 <ETX>...
Page 219
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Days Before Line Periodic Test Needed Alarm Command Format: Inquire: Display: <SOH>S55800dd <SOH>I55800 Computer: <SOH>s55800dd <SOH>i55800 Typical Response Message, Display Format: <SOH> I55800 JAN 22, 1996 3:12 PM LINE PER TST NEEDED ALM: DAYS= 30 <ETX>...
Page 220
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Line Annual Test Needed Warning Command Format: Inquire: Display: <SOH>S55900f <SOH>I55900 Computer: <SOH>s55900f <SOH>i55900 Typical Response Message, Display Format: <SOH> I55900 JAN 22, 1996 3:12 PM LINE ANN TST NEEDED WRN: DISABLED <ETX>...
Page 221
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Days Before Line Annual Test Needed Warning Command Format: Inquire: Display: <SOH>S55A00ddd <SOH>I55A00 Computer: <SOH>s55A00ddd <SOH>i55A00 Typical Response Message, Display Format: <SOH> I55A00 JAN 22, 1996 3:12 PM LINE ANN TST NEEDED WRN: DAYS=355 <ETX>...
Page 222
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Days Before Line Annual Test Needed Alarm Command Format: Inquire: Display: <SOH>S55B00ddd <SOH>I55B00 Computer: <SOH>s55B00ddd <SOH>i55B00 Typical Response Message, Display Format: <SOH> I55B00 JAN 22, 1996 3:12 PM LINE ANN TST NEEDED ALM: DAYS=365 <ETX>...
Page 223
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Ullage Command Format: Inquire: Display: <SOH>S56400f <SOH>I56400 Computer: <SOH>s56400f <SOH>i56400 Typical Response Message, Display Format: <SOH> I56400 JUN 22, 2006 3:15 PM ULLAGE: 90% <ETX> Typical Response Message, Computer Format: <SOH>i56400YYMMDDHHmmf&&CCCC<ETX>...
Page 224
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Manual Close Timeout in Minutes Command Format: Inquire: Display: <SOH>S56E00NN <SOH>I56E00 Computer: <SOH>s56E00NN <SOH>i56E00 Typical Response Message, Display Format: <SOH> I56E00 JUN 22, 2009 3:15 PM MANUAL CLOSE TIMEOUT: <ETX>...
Page 225
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Inventory Close Start Time Command Format: Inquire: Display: <SOH>S57700hhmm <SOH>I57700 Computer: <SOH>s57700hhmm <SOH>i57700 Typical Response Message, Display Format: <SOH> I57700 JUN 22, 2009 3:15 PM INVENTORY LOG TIME : 12:00 <ETX>...
Page 226
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Inventory Reporting Interval Command Format: Inquire: Display: <SOH>S57800rr <SOH>I57800 Computer: <SOH>s57800rr <SOH>i57800 Typical Response Message, Display Format: <SOH> I57800 JAN 22, 2009 3:16 PM INVENTORY LOG INTERVAL : 1 Hour <ETX>...
Page 227
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Tank Idle Delivery Enable/Disable Command Format: Inquire: Display: <SOH>S57900f <SOH>I57900 Computer: <SOH>s57900f <SOH>i57900 Typical Response Message, Display Format: <SOH> I57900 JAN 22, 2011 3:12 PM TANK IDLE DELIVERY ENABLED <ETX>...
Page 228
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Get Inventory Storage Length Command Format: Display: <SOH>I58000 Computer: <SOH>i58000 Typical Response Message, Display Format: <SOH> I58000 JAN 22, 2009 3:16 PM INVENTORY STORAGE LENGTH: 2000 <ETX> Typical Response Message, Computer Format: <SOH>i58000YYMMDDHHmmFFFFFFFF&&CCCC<ETX>...
Page 229
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: Set Alarm Filter Command Format: Inquire: Display: <SOH>S58100f <SOH>I58100 Computer: <SOH>s58100f <SOH>i58100 Typical Response Message, Display Format: <SOH> I58100 JUN 24, 2011 3:15 PM ALARM FILTERING FLAG: ENABLED <ETX>...
Page 230
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Enable/Disable Custom Alarms Command Format: Inquire: Display: <SOH>S5BD00f <SOH>I5BD00 Computer: <SOH>s5BD00f <SOH>i5BD00 Typical Response Message, Display Format: <SOH> I5BD00 JUN 22, 2001 3:15 PM CUSTOM ALARM LABELS ENABLED <ETX>...
Page 231
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Custom Alarm Label, device number, and indications Command Format: Inquire: Display: <SOH>S5BF00AANNTTflpbdaaaaaaaaaaaaaaaaaaa <SOH>I5BF00 Computer: <SOH>s5BF00AANNTTflpbdaaaaaaaaaaaaaaaaaaa <SOH>i5BF00 Notes: AA - Alarm/Warning Category: See explanation for "AA" in Function i10100 NN - Alarm Type Number: See explanation for "NN"...
Page 232
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 5BF Notes: (Continued) Typical Response Message, Computer Format: <SOH>i5BF00YYMMDDHHmmnnAANNTTlpbdaaaaaaaaaaaaaaaaaaa... AANNTTlpbdaaaaaaaaaaaaaaaaaaa&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time nn - Number of Custom Alarms to follow (Hex) AA - Alarm/Warning Category: See explanation for "AA" in Function i10100 NN - Alarm Type Number: See explanation for "NN"...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.4. ADDRESS BOOK SETUP Function Code: Version 1 Function Type: Add Contact Command Format: Inquire: Display: <SOH>S5G100aaa....aaa <SOH>I5G1RR Computer: <SOH>s5G100aaa....aaa <SOH>i5G1RR Typical Response Message, Display Format: <SOH> I5G1RR JUL 26, 2007 1:36 PM CONTACT NAME CONTACT# NAME Mrs.
Page 234
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Delete Contact Command Format: Inquire: Display: <SOH>S5G2RR <SOH>I5G2RR Computer: <SOH>s5G2RR <SOH>i5G2RR Typical Response Message, Display Format: <SOH> I5G2RR JUL 26, 2007 1:36 PM DELETE CONTACT CONTACT# NAME DELETE STATUS Mrs.
Page 235
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Modem Number Command Format: Inquire: Display: <SOH>S5G3RRaaaa....aaaa <SOH>I5G3RR Computer: <SOH>s5G3RRaaaa....aaaa <SOH>i5G3RR Typical Response Message, Display Format: <SOH> I5G3RR JUL 26, 2007 1:36 PM CONTACT MODEM NUMBER CONTACT# CONTACT NAME MODEM NUMBER Mrs.
Page 236
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Modem Dial-Out String Command Format: Inquire: Display: <SOH>S5G4RRaaaaa..aaaaa <SOH>I5G4RR Computer: <SOH>s5G4RRaaaaa..aaaaa <SOH>i5G4RR Typical Response Message, Display Format: <SOH> I5G4RR JUL 26, 2007 1:36 PM CONTACT MODEM DIAL-OUT STRING CONTACT# NAME : Mrs.
Page 237
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Modem Communication Device Number Command Format: Inquire: Display: <SOH>S5G5RRDD <SOH>I5G5RR Computer: <SOH>s5G5RRDD <SOH>i5G5RR Typical Response Message, Display Format: <SOH> I5G5RR JUL 26, 2007 1:36 PM CONTACT MODEM COMMUNICATION DEVICE CONTACT# CONTACT NAME COMM DEVICE Mrs.
Page 238
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Modem Retry Count Command Format: Inquire: Display: <SOH>S5G6RRnn <SOH>I5G6RR Computer: <SOH>s5G6RRnn <SOH>i5G6RR Typical Response Message, Display Format: <SOH> I5G6RR JUL 26, 2007 1:36 PM CONTACT MODEM RETRY COUNT CONTACT# CONTACT NAME RETRY COUNT Mrs.
Page 239
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Modem Retry Delay Time Command Format: Inquire: Display: <SOH>S5G7RRnnn <SOH>I5G7RR Computer: <SOH>s5G7RRnnn <SOH>i5G7RR Typical Response Message, Display Format: <SOH> I5G7RR JUL 29, 1997 9:06 AM CONTACT MODEM RETRY DELAY TIME CONTACT# CONTACT NAME RETRY DELAY Mrs.
Page 240
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: View Full Contact Info Command Format: Display: <SOH>I5G8RR Computer: <SOH>i5G8RR Typical Response Message, Display Format: <SOH> I5G8RR JUL 26, 2007 1:36 PM CONTACT NAME CONTACT# NAME Mrs. Lozier MODEM NUMBER 123-4567 MODEM SETUP STRING...
Page 241
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 5G8 Notes: (Continued) SS - Number of Strings to follow mm - Length of string BBB..BBB - String if gg = 01 (Modem) string 1 = Modem Number string 2 = Modem Setup String if gg = 02 (FAX) string 1 = FAX Number string 2 = FAX Setup String...
Page 242
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact FAX Modem Number Command Format: Inquire: Display: <SOH>S5H3RRaaaa....aaaa <SOH>I5H3RR Computer: <SOH>s5H3RRaaaa....aaaa <SOH>i5H3RR Typical Response Message, Display Format: <SOH> I5H3RR JUL 26, 2007 1:36 PM CONTACT FAX NUMBER CONTACT# CONTACT NAME FAX NUMBER Mrs.
Page 243
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact FAX Dial-Out String Command Format: Inquire: Display: <SOH>S5H4RRaaaaa..aaaaa <SOH>I5H4RR Computer: <SOH>s5H4RRaaaaa..aaaaa <SOH>i5H4RR Typical Response Message, Display Format: <SOH> I5H4RR JUL 26, 2007 1:36 PM CONTACT FAX DIAL-OUT STRING CONTACT# NAME : Mrs.
Page 244
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact FAX Communication Device Number Command Format: Inquire: Display: <SOH>S5H5RRDD <SOH>I5H5RR Computer: <SOH>s5H5RRDD <SOH>i5H5RR Typical Response Message, Display Format: <SOH> I5H5RR JUL 26, 2007 1:36 PM CONTACT FAX COMMUNICATION DEVICE DETAILS CONTACT# CONTACT NAME COMM DEVICE Mrs.
Page 245
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact FAX Retry Count Command Format: Inquire: Display: <SOH>S5H6RRnn <SOH>I5H6RR Computer: <SOH>s5H6RRnn <SOH>i5H6RR Typical Response Message, Display Format: <SOH> I5H6RR JUL 26, 2007 1:36 PM CONTACT FAX RETRY COUNT CONTACT# CONTACT NAME RETRY COUNT Mrs.
Page 246
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact FAX Retry Delay Time Command Format: Inquire: Display: <SOH>S5H7RRnnn <SOH>I5H7RR Computer: <SOH>s5H7RRnnn <SOH>i5H7RR Typical Response Message, Display Format: <SOH> I5H7RR JUL 29, 1997 9:06 AM CONTACT FAX RETRY DELAY TIME CONTACT# CONTACT NAME RETRY DELAY Mrs.
Page 247
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Remote TCP/IP Address Command Format: Inquire: Display: <SOH>S5I3RRaaaa....aaaa <SOH>I5I3RR Computer: <SOH>s5I3RRaaaa....aaaa <SOH>i5I3RR Typical Response Message, Display Format: <SOH> I5I3RR JUL 26, 2007 1:36 PM CONTACT REMOTE TCP/IP ADDRESS CONTACT# CONTACT NAME REMOTE TCP/IP ADDRESS Mrs.
Page 248
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Remote TCP/IP Port Number Command Format: Inquire: Display: <SOH>S5I4RRppppp <SOH>I5I4RR Computer: <SOH>s5I4RRppppp <SOH>i5I4RR Typical Response Message, Display Format: <SOH> I5I4RR JUL 26, 2007 1:36 PM CONTACT REMOTE TCP/IP PORT NUMBER CONTACT# CONTACT NAME REMOTE TCP/IP PORT Mrs.
Page 249
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Local TCP/IP Communication Device Number Command Format: Inquire: Display: <SOH>S5I5RRDD <SOH>I5I5RR Computer: <SOH>s5I5RRDD <SOH>i5I5RR Typical Response Message, Display Format: <SOH> I5I5RR JUL 26, 2007 1:36 PM CONTACT LOCAL TCP/IP COMMUNICATION DEVICE CONTACT# CONTACT NAME LOCAL TCP/IP DEVICE...
Page 250
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact TCP/IP Retry Count Command Format: Inquire: Display: <SOH>S5I6RRnn <SOH>I5I6RR Computer: <SOH>s5I6RRnn <SOH>i5I6RR Typical Response Message, Display Format: <SOH> I5I6RR JUL 26, 2007 1:36 PM CONTACT TCP/IP RETRY COUNT CONTACT# CONTACT NAME RETRY COUNT Mrs.
Page 251
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact TCP/IP Retry Delay Time Command Format: Inquire: Display: <SOH>S5I7RRnnn <SOH>I5I7RR Computer: <SOH>s5I7RRnnn <SOH>i5I7RR Typical Response Message, Display Format: <SOH> I5I7RR JUL 29, 1997 9:06 AM CONTACT TCP/IP RETRY DELAY TIME CONTACT# CONTACT NAME RETRY DELAY Mrs.
Page 252
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Satellite Connection String Command Format: Inquire: Display: <SOH>S5J4RRaaa....aaa <SOH>I5J4RR Computer: <SOH>s5J4RRaaa....aaa <SOH>i5J4RR Typical Response Message, Display Format: <SOH> I5J4RR JUL 26, 2007 1:36 PM CONTACT SATELLITE CONNECTION STRING CONTACT# CONTACT NAME CONNECTION STRING Mrs.
Page 253
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Satellite Communication Device Number Command Format: Inquire: Display: <SOH>S5J5RRDD <SOH>I5J5RR Computer: <SOH>s5J5RRDD <SOH>i5J5RR Typical Response Message, Display Format: <SOH> I5J5RR JUL 26, 2007 1:36 PM CONTACT SATELLITE COMMUNICATION DEVICE CONTACT# CONTACT NAME COMM DEVICE Mrs.
Page 254
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Satellite Mode Retry Count Command Format: Inquire: Display: <SOH>S5J6RRnn <SOH>I5J6RR Computer: <SOH>s5J6RRnn <SOH>i5J6RR Typical Response Message, Display Format: <SOH> I5J6RR JUL 26, 2007 1:36 PM CONTACT SATELLITE MODE RETRY COUNT CONTACT# CONTACT NAME RETRY COUNT Mrs.
Page 255
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact Satellite Retry Delay Time Command Format: Inquire: Display: <SOH>S5J7RRnnn <SOH>I5J7RR Computer: <SOH>s5J7RRnnn <SOH>i5J7RR Typical Response Message, Display Format: <SOH> I5J7RR JUL 26, 2007 1:36 PM CONTACT SATELLITE RETRY DELAY TIME CONTACT# CONTACT NAME RETRY DELAY Mrs.
Page 256
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact E-Mail Address Command Format: Inquire: Display: <SOH>S5K3RRaaaaa..aaaaa <SOH>I5K3RR Computer: <SOH>s5K3RRaaaaa..aaaaa <SOH>i5K3RR Typical Response Message, Display Format: <SOH> I5K3RR JUL 26, 2007 1:36 PM CONTACT E-MAIL ADDRESS CONTACT# CONTACT NAME : John Doe...
Page 257
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact E-Mail Mode Retry Count Command Format: Inquire: Display: <SOH>S5K6RRnn <SOH>I5K6RR Computer: <SOH>s5K6RRnn <SOH>i5K6RR Typical Response Message, Display Format: <SOH> I5K6RR JUL 26, 2007 1:36 PM CONTACT E-MAIL MODE RETRY COUNT CONTACT# CONTACT NAME RETRY COUNT Mr.
Page 258
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Contact E-Mail Retry Delay Time Command Format: Inquire: Display: <SOH>S5K7RRnnn <SOH>I5K7RR Computer: <SOH>s5K7RRnnn <SOH>i5K7RR Typical Response Message, Display Format: <SOH> I5K7RR JUL 26, 2007 1:36 PM CONTACT E-MAIL RETRY DELAY TIME CONTACT# CONTACT NAME RETRY DELAY Mrs.
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.5. AUTOMATIC EVENTS SETUP Function Code: Version 1 Function Type: Add/Delete AutoEvent Command Format: Inquire: Display: <SOH>S5P100IIIICTA (C=1) <SOH>I5P100IIII <SOH>S5P100IIIIC (C=3,9) Computer:<SOH>s5P100IIIICTA (C=1) <SOH>i5P100IIII <SOH>s5P100IIIIC (C=3,9) Notes: IIII - AutoEventID For Inquire, 0000 means “all” For Add, only 0000 is valid For Delete, only 0001-9999 is valid For DeleteAll, 0000 should be used...
Page 260
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 5P1: (Continued) EVENT-ID - 0005 EVENT – Gross Test Fail Alarm: T 1: REGULAR, T 2: UNLEADED EVENT – Sudden Loss Alarm: T 1: REGULAR, T 2: UNLEADED, T3: DIESEL REPORT – Alarm History Report, Tank Leak History Report CONTACT –...
Page 261
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 5P1 Notes: (Continued) NN - Alarm Type Number: (see command 5P4) OO - Notification Type (see command 5P4) nn - Number of Devices to follow (see command 5P4) DD – Device Number (see command 5P4) LL - Action Device Type...
Page 262
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get Number of Auto Events Command Format: Display: <SOH>I5P200 Computer: <SOH>i5P200 Typical Response Message, Display Format: <SOH> I5P200 JUL 26, 2007 1:36 PM AUTOMATIC EVENTS – NUMBER OF AUTO EVENTS REPORT Number of Automatic Events = 1234 <ETX>...
Page 263
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Auto Event Trigger: Time Based Command Format: Inquire: Display: <SOH>S5P300IIIITTnnMMWWwwDDhhmmss <SOH>I5P300IIII Computer:<SOH>s5P300IIIITTnnMMWWwwDDhhmmss <SOH>i5P300IIII Typical Response Message, Display Format: <SOH> I5P1RR JUL 26, 2007 1:36 PM AUTOMATIC EVENTS – TIME BASED TRIGGER REPORT ------ EVENT-ID - 0001...
Page 264
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 5P3 Notes: (Continued) WW - Occurrence of day-of-week in month, (01-05, if Task Period choice is Annually by Day of Week [TT=03], Monthly by Day of Week [TT=05]) a. 5 = Last occurrence b.
Page 265
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Auto Event Trigger: Event Based Command Format: Inquire: Display: <SOH>S5P400IIIICTTEAANNnnDD...<CR> (if E=0) <SOH>I5P400IIII VVnnDD...<CR> (if E=1) OOnnDD...<CR> (if E=2) Computer: <SOH>s5P400IIIICTTEAANNnnDD...<CR> (if E=0) <SOH>i5P400IIII VVnnDD...<CR> (if E=1) OOnnDD...<CR>...
Page 266
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 5P4 Notes: (Continued) OO - Notification Type (Valid only when E=2) 01=Delivery Start 02=Delivery Complete 03=BIR Daily Close 04=Inventory Shift Close 05=BOL Pending (not in V1 or V2) 06=SLD Test Start 07=SLD Test Complete 08=CSLD Test Complete 09=PLLD Test Start (obsolete)
Page 267
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Auto Event Action: Device Task Command Format: Inquire: Display: <SOH>S5P500IIIIAADD <SOH>I5P500IIII Computer: <SOH>s5P500IIIIAADD <SOH>i5P500IIII Typical Response Message, Display Format: <SOH> I5P500 JUL 26, 2007 1:36 PM AUTOMATIC EVENTS – DEVICE TASKS REPORT ------ EVENT-ID - 0004...
Page 268
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Auto Event Action: Print Task Command Format: Inquire: Display: <SOH>S5P600IIIIPPnnRRR... <SOH>I5P600IIII Computer: <SOH>s5P600IIIIPPnnRRR... <SOH>i5P600IIII Typical Response Message, Display Format: <SOH> I5P600 JUL 26, 2007 1:36 PM AUTOMATIC EVENTS – PRINT TASKS REPORT ------ EVENT-ID - 0002...
Page 269
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 5P6 Notes: (Continued) RRR - Report Type ID 001 – Current Inventory Report 002 – Inventory History Report 003 – Shift Inventory Report 004 – Delivery Report (for FAX/EMAIL only) 005 – Most Recent Delivery Report 006 –...
Page 270
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Auto Event Action: Auto Connect Task (FAX/E-MAIL/COMPUTER) Command Format: Inquire: Display: <SOH>S5P700IIIIWWnnRRR...NNCC... <SOH>I5P700IIII Computer: <SOH>s5P700IIIIWWnnRRR...NNCC... <SOH>i5P700IIII Typical Response Message, Display Format: <SOH> I5P700 JUL 26, 2007 1:36 PM AUTOMATIC EVENTS –...
Page 271
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Automatic Events: Task Log Command Format: Display: <SOH>I5Q100IIIIAARRRCCTTMMSSnnn (when MM= 00,01,02 or 03) <SOH>I5Q100IIIIAARRRCCTTMMLLDDSSnnn (when MM=04) <SOH>I5Q100IIIIAARRRCCTTMMPPSSnnn (when MM=05) <SOH>I5Q100IIIIAARRRCCTTMMWWSSnnn (when MM=06) Computer: <SOH>i5Q100IIIIAARRRCCTTMMSSnnn Command Notes: Note: All parameters mentioned below are optional following the rules below. IIII - AutoEventID 0000 –...
Page 272
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 5Q1 Notes: (Continued) WW - Connection Mode (when MM=06 i.e. Specific Connection Mode) 01 = Modem (Computer mode connection) 02 = FAX 03 = Satellite (Computer mode connection) 04 = TCP/IP (Computer mode connection) 05 = Email SS - Status (If no Status is given, it assumes request is for “Any Status”)
Page 273
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 5Q1: (Continued) EVENT TIME - 4/15/05 1:23 PM EVENT ID ACTION – LAST TIME ATTEMPTED – 4/15/05 1:28 PM RETRIES – 5 DEVICE - R 1:Relay Tank 1 Sump STATUS - Success MESSAGE –...
Page 274
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 5Q1: (Continued) RRR - Report Type ID See explanation for “RRR” in i5P600 MM – Connection Mode See explanation for “WW” in i5P700 Note: This entry is valid only when A=3 CC - Contact Identification Number (Decimal) See explanation for “RR”...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.6 IN-TANK SETUP Function Code: Version 1 Function Type: Set Tank Configuration Command Format: Inquire: Display: <SOH>S601TTf <SOH>I601TT Computer: <SOH>s601TTf <SOH>i601TT Typical Response Message, Display Format: <SOH> I601TT JAN 22, 1996 3:16 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED...
Page 276
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Label Command Format: Inquire: Display: <SOH>S602TTaaaaaaaaaaaaaaaaaaaa <SOH>I602TT Computer: <SOH>s602TTaaaaaaaaaaaaaaaaaaaa <SOH>i602TT Typical Response Message, Display Format: <SOH> I602TT JAN 22, 1996 3:16 PM TANK LABEL TANK LABEL REGULAR UNLEADED <ETX>...
Page 277
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Product Code Command Format: Inquire: Display: <SOH>S603TTa <SOH>I603TT Computer: <SOH>s603TTa <SOH>i603TT Typical Response Message, Display Format: <SOH> I603TT JAN 22, 1996 3:16 PM TANK PRODUCT CODE TANK LABEL REGULAR UNLEADED...
Page 278
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank 1 Point Full Height Volume Command Format: Inquire: Display: <SOH>S604TTGGGGGG <SOH>I604TT Computer: <SOH>s604TTFFFFFFFF <SOH>i604TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - Full Height Volume, Gallons (Decimal) FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 279
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank 4 Point Full, 3/4, 1/2, 1/4 Volumes Command Format: Inquire: Display: <SOH>S605TTGGGGGGggggggGGGGGGgggggg <SOH>I605TT or: <SOH>S605TTGGGG,gggg,GGGG,ggg Computer: <SOH>s605TTFFFFFFFFffffffffFFFFFFFFffffffff <SOH>i605TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - Full Height Volume, Gallons (Decimal) gggggg - 3/4 Height Volume, Gallons (Decimal)
Page 280
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank 20 Point Full, 95%, 90%,...Volumes Command Format: Inquire: Display: <SOH>S606TTGGGGGGgggggg... <SOH>I606TT or: <SOH>S606TTGGGG,gggg,GGGG,... Computer: <SOH>s606TTFFFFFFFF... <SOH>i606TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGGgggggg - Series of 20 Volumes, Gallons (Decimal) FFFFFFFF - Series of 20 Volumes, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 281
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Diameter Command Format: Inquire: Display: <SOH>S607TTIII.hh <SOH>I607TT Computer: <SOH>s607TTFFFFFFFF <SOH>i607TT Notes: TT - Tank Number (Decimal, 00=all) III.hh - Tank Diameter, Inches and hundredths (Decimal) FFFFFFFF - Tank Diameter, Inches (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 282
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Tilt Command Format: Inquire: Display: <SOH>S608TTIIII.hh <SOH>I608TT Computer: <SOH>s608TTFFFFFFFF <SOH>i608TT Notes: TT - Tank Number (Decimal, 00=all) IIII.hh - Tank Tilt, Inches and hundredths (Decimal, +/- III.hh) FFFFFFFF - Tank Tilt, Inches (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 283
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Thermal Expansion Coefficient Command Format: Inquire: Display: <SOH>S609TTc.cccccc <SOH>I609TT Computer: <SOH>s609TTFFFFFFFF <SOH>i609TT Notes: TT - Tank Number (Decimal, 00=all) c.cccccc - Thermal Expansion Coefficient (decimal) FFFFFFFF - Thermal Expansion Coefficient (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 284
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Linear Calculated Full Volume Command Format: Inquire: Display: <SOH>S60ATTGGGGGG <SOH>I60ATT Computer: <SOH>s60ATTFFFFFFFF <SOH>i60ATT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - Full Height Volume, Gallons (Decimal) FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 285
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Set Tank Stick Height Function Enable Command Format: Inquire: Display: <SOH>S60B00f <SOH>I60B00 Computer: <SOH>s60B00f <SOH>i60B00 Typical Response Message, Display Format: <SOH> I60B00 JUL 29, 2013 9:07 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED <ETX>...
Page 286
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Set Tank Stick Height Offset Command Format: Inquire: Display: <SOH>S60CTTIII.hh <SOH>I60CTT Computer: <SOH>s60CTTFFFFFFFF <SOH>i60CTT Notes: TT - Tank Number (Decimal, 00=all) III.hh - Stick Height Offset, Inches and hundredths (Decimal) FFFFFFFF - Stick Height Offset, Inches (ASCII Hex IEEE float).
Page 287
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Programmable Float Parameters Command Format: Inquire: Display: <SOH>S60ETTIIII.tttIIII.tttIIII.tttIIII.ttt <SOH>I60ETT or: <SOH>S60ETTIII.ttt,III.ttt,III.ttt,III.ttt Computer: <SOH>s60ETTFFFFFFFF...FFFFFFFF <SOH>i60ETT Notes: CUSTOM float size must be chosen (Function Code 62F) for these parameters to be set and used.
Page 288
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Probe Offset Command Format: Inquire: Display: <SOH>S60FTTIII.hh <SOH>I60FTT Computer: <SOH>s60FTTFFFFFFFF <SOH>i60FTT Notes: TT - Tank Number (Decimal, 00=all) III.hh - Probe offset, Inches and hundredths (Decimal) FFFFFFFF - Probe offset, Inches (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 289
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Manual Tank Leak Test Command Format: Inquire: Display: <SOH>S60GTTRCDD <SOH>I60GTT Computer: <SOH>s60GTTRCDD <SOH>i60GTT Typical Response Message, Display Format: <SOH> I60GTT 1, 2000 8:06 AM MANUAL TANK LEAK TEST ---------------------------------------------------------------- TEST TEST...
Page 290
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Probe Number Installed in Tank Command Format: Inquire: Display: <SOH>S60KTTpp <SOH>I60KTT Computer: <SOH>s60KTTpp <SOH>i60KTT Notes: pp - -1 if tank not assigned to probe 00=all, inquiry only Typical Response Message, Display Format: <SOH>...
Page 291
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get Tank Setup Warning Messages Command Format: Display: <SOH>I60LTT Computer: <SOH>i60LTT Typical Response Message, Display Format: <SOH> I60LTT 1, 2000 8:06 AM TANK PARAMETER VALIDATION T 1: ALL PARAMETERS VIABLE T 2: DIAMETER OUT OF RANGE CAPACITY OUT OF RANGE <ETX>...
Page 292
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Product Label Command Format: Inquire: Display: <SOH>S60MPPaaaaaaaaaaaaaaaaaaaa <SOH>I60MPP Computer: <SOH>s60MPPaaaaaaaaaaaaaaaaaaaa <SOH>i60MPP Typical Response Message, Display Format: <SOH> I60M00 JAN 22, 2009 3:17 PM PRODUCT LABEL REGULAR UNLEADED <ETX>...
Page 293
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Product Setup Report Command Format: Display: <SOH>I60NPP Computer: <SOH>i60NPP Typical Response Message, Display Format: <SOH> I60N00 JAN 22, 2009 3:17 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..
Page 294
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Product Available in Tank Command Format: Inquire: Display: <SOH>S60OTTPP <SOH>I60OTT Computer: <SOH>s60OTTPP <SOH>i60OTT Notes: PP - Set to -1 to remove Product assignment Typical Response Message, Display Format: <SOH>...
Page 295
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Delivery Delay Command Format: Inquire: Display: <SOH>S610TTdd <SOH>I610TT Computer: <SOH>s610TTdd <SOH>i610TT Typical Response Message, Display Format: <SOH> I610TT JAN 22, 1996 3:17 PM TANK DELIVERY DELAY TANK LABEL REGULAR UNLEADED...
Page 296
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Leak Test Type & Start Time Command Format: Inquire: Display: <SOH>S611TTDDRMYYMMDDHHmm<CR> (if M=1) <SOH>I611TT MMODHHmm<CR> (if M=2) ODHHmm<CR> (if M=3) DHHmm<CR> (if M=4) HHmm<CR> (if M=5) <CR>...
Page 298
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank SIPHON Manifolded Partners Command Format: Inquire: Display: <SOH>S612TTtt…TTtt <SOH>I612TT Computer: <SOH>s612TTtt…TTtt <SOH>i612TT Typical Response Message, Display Format: <SOH> I612TT JAN 22, 2002 3:17 PM TANK MANIFOLDED PARTNERS TANK LABEL SIPHON MANIFOLDED TANKS...
Page 299
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set CSLD Probability of Detection Command Format: Inquire: Display: <SOH>S613TTf <SOH>I613TT Computer: <SOH>s613TTf <SOH>i613TT Typical Response Message, Display Format: <SOH> I613TT JAN 22, 1996 3:17 PM CSLD PROBABLITY OF DETECTION T 1:REGULAR UNLEADED : Pd=95% <ETX>...
Page 300
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set CSLD Climate Factor Command Format: Inquire: Display: <SOH>S614TTf <SOH>I614TT Computer: <SOH>s614TTf <SOH>i614TT Typical Response Message, Display Format: <SOH> I614TT JAN 22, 1996 3:17 PM CSLD CLIMATE FACTOR T 1:REGULAR UNLEADED : MODERATE <ETX>...
Page 301
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set BIR Meter Data Present Command Format: Inquire: Display: <SOH>S615TTf <SOH>I615TT Computer: <SOH>s615TTf <SOH>i615TT Typical Response Message, Display Format: <SOH> I615TT JAN 22, 1996 3:17 PM TANK LABEL METER DATA REGULAR UNLEADED <ETX>...
Page 302
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Accuchart Update Scheduling Command Format: Inquire: Display: <SOH>S616TTf <SOH>I616TT Computer: <SOH>s616TTf <SOH>i616TT Typical Response Message, Display Format: <SOH> I616TT JAN 22, 1996 3:17 PM TANK LABEL CAL UPDATE REGULAR UNLEADED IMMEDIATE <ETX>...
Page 303
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank CSLD Evaporation Compensation Command Format: Inquire: Display: <SOH>S618TTf <SOH>I618TT Computer: <SOH>s618TTf <SOH>i618TT Notes: 1. Only accepted if both conditions are true for the addressed tank: a. CSLD has been selected as the leak test method (S611TT). b.
Page 304
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Stage II Vapor Recovery Command Format: Inquire: Display: <SOH>S619TTf <SOH>I619TT Computer: <SOH>s619TTf <SOH>i619TT Notes: 1. Only allowed if CSLD Evaporation Compensation is enabled Typical Response Message, Display Format: <SOH>...
Page 305
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set In-Tank Leak Test Early Stop Command Format: Inquire: Display: <SOH>S61ATTf <SOH>I61ATT Computer: <SOH>s61ATTf <SOH>i61ATT Typical Response Message, Display Format: <SOH> I61ATT 1, 2000 8:06 AM IN-TANK LEAK TEST EARLY STOP TANK LABEL TST EARLY STOP:...
Page 306
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set In-Tank Static Gross Test Auto-Confirm Command Format: Inquire: Display: <SOH>S61BTTf <SOH>I61BTT Computer: <SOH>s61BTTf <SOH>i61BTT Typical Response Message, Display Format: <SOH> I61BTT OCT 10, 2000 3:11 PM IN-TANK STATIC GROSS TEST AUTO-CONFIRM: TANK LABEL AUTO-CONFIRM...
Page 307
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Update Apply Accuchart Chart Dates Command Format: Inquire: Display: <SOH>S61HTTDF[data] <SOH>I61HTT Computer: <SOH>s61HTTDF[data] <SOH>i61HTT Notes: TT - Tank Number [01..32], (Decimal, 00=all) D - Date Number [1..4], (Decimal) F - 1.
Page 308
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Maximum Accuchart Calibration Period Days Command Format: Inquire: Display: <SOH>S61ITTDDD <SOH>I61ITT Computer: <SOH>s61ITTDDD <SOH>i61ITT Notes: TT - Tank Number [01..32], (Decimal, 00=all) DDD - Max Duration in Days [014..120], (Decimal) Typical Response Message, Display Format: <SOH>...
Page 309
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Exclude Calibration Dates Command Format: Inquire: Display: <SOH>S61JTTFyyyymmdd <SOH>I61JTT Computer: <SOH>s61JTTFyyyymmdd <SOH>i61JTT Notes: TT - Tank Number [01..32], (Decimal, 00=all) F - 1=Exclude Records on this Date, 2=Include Records on this Date yyy - Year (decimal) mm - Month [01..12] (Decimal)
Page 310
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Enable Accuchart Warnings Command Format: Inquire: Display: <SOH>S61KTTF <SOH>I61KTT Computer: <SOH>s61KTTF <SOH>i61KTT Notes: TT - Tank Number [01..32], (Decimal, 00=all) F - Accuchart Warning (Decimal) 0=Disabled 1=Enabled Typical Response Message, Display Format: <SOH>...
Page 311
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Accuchart Chart Management Command Format: Inquire: Display: <SOH>S61LTT149IIP[data] <SOH>I61LTTii Computer: <SOH>s61LTT149IIP[data] <SOH>i61LTTii Notes: TT - Tank Number [01..32], (Decimal, 00=all) II - Chart ID number [01…99] P - Operation ii - Chart ID number [01…99] 00 = all charts for this tank (Decimal) Chart ID=1 always exists.
Page 312
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 61L: (Continued) Typical Response Message, Display Format: <SOH> I61LTT JAN 24, 2009 2:52 PM TANK CHARTS ------------------------------------------------------------------------------- TANK: DIAMETER: 96.0 CHART ID: CAPACITY: 10000 LABEL: SUMMER 2008 ENDSHAPE: 0.000 TYPE: ONE_POINT OFFSET: -1.50 SOURCE: AUTO DIM METERED CHART...
Page 313
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 61L: (Continued) Notes: • height-volume pairs will be listed in descending height order. • Metric values will show one digit to the right of the decimal point. • English values will show two digits to the right of the decimal point. Typical Response Message, Computer Format: <SOH>i61LTTYYMMDDHHmmTTIIss...sstcyyyymmddEEEEEEEESVN[]JJ[]KKKK[]...
Page 314
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Low Level Limit Command Format: Inquire: Display: <SOH>S621TTGGGGGG <SOH>I621TT Computer: <SOH>s621TTFFFFFFFF <SOH>i621TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - Low Level Limit, Gallons (Decimal) FFFFFFFF - Low Level Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 315
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank High Level Limit Command Format: Inquire: Display: <SOH>S622TTGGGGGG <SOH>I622TT Computer: <SOH>s622TTFFFFFFFF <SOH>i622TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - High Level Limit, Gallons (Decimal) FFFFFFFF - High Level Limit, Gallons (ASCII Hex IEEE float) * Set Tank Maximum Volume Limit (628 cmd) must be set before the High Level Limit.
Page 316
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Overfill Level Limit Command Format: Inquire: Display: <SOH>S623TTGGGGGG <SOH>I623TT Computer: <SOH>s623TTFFFFFFFF <SOH>i623TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - Overfill Level Limit, Gallons (Decimal) FFFFFFFF - Overfill Level Limit, Gallons (ASCII Hex IEEE float) * Set Tank Maximum Volume Limit (628 cmd) must be set before the Overfill Level Limit.
Page 317
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank High Water Level Limit Command Format: Inquire: Display: <SOH>S624TTII.tt <SOH>I624TT Computer: <SOH>s624TTFFFFFFFF <SOH>i624TT Notes: TT - Tank Number (Decimal, 00=all) II.t - High Water Level Limit, Inches and tenths (Decimal, Min=0.75, Max=05.00, NotSet=0) FFFFFFFF - High Water Level Limit, Inches (ASCII Hex IEEE float) Typical Response Message, Display Format:...
Page 318
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Sudden Loss Limit Command Format: Inquire: Display: <SOH>S625TTGGGGGG <SOH>I625TT Computer: <SOH>s625TTFFFFFFFF <SOH>i625TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - Sudden Loss Limit, Gallons (Decimal) FFFFFFFF - Sudden Loss Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 319
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Leak Alarm Limit Command Format: Inquire: Display: <SOH>S626TTGGGGGG <SOH>I626TT Computer: <SOH>s626TTFFFFFFFF <SOH>i626TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - Leak Alarm Limit, Gallons (Decimal) FFFFFFFF - Leak Alarm Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 320
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank High Water Warning Limit Command Format: Inquire: Display: <SOH>S627TTII.tt <SOH>I627TT Computer: <SOH>s627TTFFFFFFFF <SOH>i627TT Notes: TT - Tank Number (Decimal, 00=all) II.t - High Water Warning Limit, Inches and tenths (Decimal, Min=0.75, Max=05.00, NotSet=0) FFFFFFFF - High Water Warning Limit, Inches (ASCII Hex IEEE float) Typical Response Message, Display Format:...
Page 321
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Maximum Volume Limit Command Format: Inquire: Display: <SOH>S628TTGGGGGG <SOH>I628TT Computer: <SOH>s628TTFFFFFFFF <SOH>i628TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - Maximum Volume Limit, Gallons (Decimal) FFFFFFFF - Maximum Volume Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 322
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Delivery Required Limit Command Format: Inquire: Display: <SOH>S629TTGGGGGG <SOH>I629TT Computer: <SOH>s629TTFFFFFFFF <SOH>i629TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - Delivery Required Limit, Gallons (Decimal) FFFFFFFF - Delivery Required Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 323
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Annual Leak Test Minimum Volume Command Format: Inquire: Display: <SOH>S62ATTGGGGGG <SOH>I62ATT Computer: <SOH>s62ATTFFFFFFFF <SOH>i62ATT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - Annual Test Minimum Volume, Gallons (Decimal) FFFFFFFF - Annual Test Minimum Volume, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 324
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Periodic Test Type Command Format: Inquire: Display: <SOH>S62CTTp <SOH>I62CTT Computer: <SOH>s62CTTp <SOH>i62CTT Typical Response Message, Display Format: <SOH> I62CTT JAN 22, 1996 3:19 PM TANK PERIODIC TEST TYPE TANK LABEL PERIODIC TEST TYPE...
Page 325
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Enable/Disable Tank Leak Test Fail Alarms Command Format: Inquire: Display: <SOH>S62DTTgpa <SOH>I62DTT Computer: <SOH>s62DTTgpa <SOH>i62DTT Typical Response Message, Display Format: <SOH> I62DTT JAN 22, 1996 3:19 PM TANK LEAK TEST FAIL ALARMS TANK LABEL...
Page 326
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set MAG Probe Float Size Command Format: Inquire: Display: <SOH>S62FTTf <SOH>I62FTT Computer: <SOH>s62FTTf <SOH>i62FTT Typical Response Message, Display Format: <SOH> I62FTT JAN 22, 1996 3:19 PM MAG PROBE FLOAT SIZE TANK LABEL FLOAT SIZE:...
Page 327
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Accuchart Create Chart Command Format: Inquire: Display: <SOH>S62GTT149 <SOH>I62GTT Computer: <SOH>s62GTT149 <SOH>i62GTT Notes: TT - Tank Number [01..32], (Decimal, 00=all, inquire only) Set operation requires Accuchart to be installed Typical Response Message, Display Format: <SOH>...
Page 328
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Leak Test Notify Command Format: Inquire: Display: <SOH>S630TTf <SOH>I630TT Computer: <SOH>s630TTf <SOH>i630TT Typical Response Message, Display Format: <SOH> I630TT JAN 22, 1996 3:20 PM IN-TANK LEAK TEST NOTIFY TANK LABEL TANK TEST NOTIFY:...
Page 329
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Test Siphon Break Command Format: Inquire: Display: <SOH>S632TTf <SOH>I632TT Computer: <SOH>s632TTf <SOH>i632TT Typical Response Message, Display Format: <SOH> I632TT JAN 22, 1996 3:20 PM TANK TEST SIPHON BREAK TANK LABEL SIPHON BREAK...
Page 330
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: Set Tank HRM Reconciliation Warning Limit Command Format: Inquire: Display: <SOH>S634TTGGGGGG <SOH>I634TT Computer: <SOH>s634TTFFFFFFFF <SOH>i634TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - HRM Reconciliation Warning Limit, Gallons (Decimal) FFFFFFFF - HRM Reconciliation Warning Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format:...
Page 331
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: Set Tank HRM Reconciliation Alarm Limit Command Format: Inquire: Display: <SOH>S635TTGGGGGG <SOH>I635TT Computer: <SOH>s635TTFFFFFFFF <SOH>i635TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - HRM Reconciliation Alarm Limit, Gallons (Decimal) FFFFFFFF - HRM Reconciliation Alarm Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 332
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Periodic Leak Test Minimum Volume Command Format: Inquire: Display: <SOH>S636TTGGGGGG <SOH>I636TT Computer: <SOH>s636TTFFFFFFFF <SOH>i636TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGG - Periodic Test Minimum Volume, Gallons (Decimal) FFFFFFFF - Periodic Test Minimum Volume, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 333
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Tank AccuChart End Shape Type and Factor Command Format: Inquire: Display: <SOH>S639TTSU.t <SOH>I639TT Computer: <SOH>s639TTSFFFFFFFF <SOH>i639TT Notes: TT - Tank Number (Decimal, 00=all) S - End Shape Type 0=None 1=Flat 2=Hemispheric...
Page 334
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Low Level Threshold for Sequential Line Manifold Command Format: Inquire: Display: <SOH>S63ATTPP.hh <SOH>I63ATT Computer: <SOH>s63ATTFFFFFFFF <SOH>i63ATT Notes: TT - Tank Number (Decimal, set for primary tank) PP.hh - Low Level Pump Threshold, Percent and hundredths (Decimal) FFFFFFFF - Low Level Pump Threshold, Percent (ASCII Hex IEEE float) Typical Response Message, Display Format:...
Page 335
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Set Tank Multi Point Full Volume Command Format: Inquire: Display: <SOH>S63CTTGGGGGG <SOH>I63CTT Computer: <SOH>s63CTTVVVVVVVV <SOH>i63CTT Notes: TT - Tank Number (Decimal, 00=All) GGGGGG - Volume, Gallons (Decimal) VVVVVVVV - Volume, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 336
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Set Tank Vapor Loss Factor Command Format: Inquire: Display: <SOH>S63DTTo.oo <SOH>I63DTT Computer: <SOH>s63DTToooooooo <SOH>i63DTT Notes: TT - Tank Number (Decimal, 00=all) o.oo - Vapor Loss Factor, Percent(Decimal, 0.00 B 0.20) oooooooo - Vapor Loss Factor, Percent(ASCII Hex IEEE Float 0.00B0.20) Typical Response Message, Display Format: <SOH>...
Page 337
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Set Tank Multi-Point Heights and Volumes Command Format: Inquire: Display: <SOH>S63ETTfnnIII.tttGGGGGGGGG..III.tttGGGGGGGGG <SOH>I63ATT or: <SOH>S63ETTfnnII.ttt,GGGGGGGG,..II.ttt,GGGGGGGG or: <SOH>S63ETT9149 Computer: <SOH>s63ETTFnnHHHHHHHHVVVVVVVV...HHH <SOH>i63ATT Notes: Set command is only valid if Tank Chart Sescurity is disabled (Future) f - Command Flag (hex) a.
Page 339
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 63E Notes: (Continued) The following 4 fields marked with an asterisk are only present if Tank Chart Security is enabled. cccccccc - * Tank Capacity, Gallons (ASCII Hex IEEE float) x…x - * Console Serial Number (20 ASCII characters [20h-7Eh]) yyyyyy - * Probe Serial Number (Decimal) z…z - * Weights and Measures Office (20 ASCII characters [20h- 7Eh])
Page 340
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Accuchart Delete Chart Command Format: Inquire: Display: <SOH>S63HTT149II <SOH>I63HTT Computer: <SOH>s63HTT149II <SOH>i63HTT Notes: TT - Tank Number [01..32], (Decimal, set for primary tank) II - Chart ID number [02…99] Chart ID=1 always exists.
Page 341
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Set Density Code Command Format: Inquire: Display: <SOH>S641PPSSSSSSSSSSSSSS <SOH>I641PP Computer: <SOH>s641PPSSSSSSSSSSSSSS <SOH>i641PP Notes: SSSSSSSSSSSSSS - Density Code (Entry is 14 characters or empty)) Typical Response Message, Display Format: <SOH>...
Page 342
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Set Tank Water Alarm Filter Level Command Format: Inquire: Display: <SOH>S642TTf <SOH>I642TT Computer: <SOH>s642TTf <SOH>i642TT Notes: TT - Tank Number (Decimal, 00=all) f - Water alarm filter level Typical Response Message, Display Format: <SOH>...
Page 343
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Set Probe Density Float Serial Number Command Format: Inquire: Display: <SOH>S644PPSSSSSSSS <SOH>I644PP Computer: <SOH>s644PPSSSSSSSS <SOH>i644PP Notes: PP - Probe Number (Decimal, 00=all, inquiry only) Typical Response Message, Display Format: <SOH>...
Page 344
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Set Tank GOST Volume Coreection Enable Command Format: Inquire: Display: <SOH>S645TTf <SOH>I645TT Computer: <SOH>s645TTf <SOH>i645TT Typical Response Message, Display Format: <SOH> I64500 JUN 29, 2011 3:16 PM TANK GOST VOLUME CORRECTION ENABLE TANK PROCDUCT LABEL GOST VOLUME CORRECTION...
Page 345
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 33 Function Type: Set Probe Water Minimum Command Format: Inquire: Display: <SOH>S648TTI.hhh <SOH>I648TT Computer: <SOH>s648TTFFFFFFFF <SOH>i648TT Notes: TT - Tank Number (Decimal, 00=all) I.hhh - Water Minimum, Inches and thousandths (Decimal) FFFFFFFF - Tank Number (Decimal, 00=all) Typical Response Message, Display Format: <SOH>...
Page 346
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 33 Function Type: Set Tank Water Alarm Filter Delay Command Format: Inquire: Display: <SOH>S64BTTf <SOH>I64BTT Computer: <SOH>s64BTTf <SOH>i64BTT Notes: TT - Tank Number (Decimal, 00=all) f - Water alarm delay level The set command is only operational for the water alarm filter level OFF.
Page 347
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Set Tank Density High Limit Command Format: Inquire: Display: <SOH>S671TTdd.ddd <SOH>I671TT Computer: <SOH>s671TTFFFFFFFF <SOH>i671TT Notes: TT - Tank Number (Decimal, 00=all) dd.ddd - Density High Limit (Decimal) Value Range = [42.139, 56.185] [US] Value Range = [675.00, 900.00] [Metric] FFFFFFFF - Density High Limit (ASCII Hex IEEE float) Typical Response Message, Display Format:...
Page 348
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Set Tank Density Low Limit Command Format: Inquire: Display: <SOH>S672TTdd.ddd <SOH>I672TT Computer: <SOH>s672TTFFFFFFFF <SOH>i672TT Notes: TT - Tank Number (Decimal, 00=all) dd.ddd - Density Low Limit (Decimal) Value Range = [42.139, 56.185] [US] Value Range = [675.00, 900.00] [Metric] FFFFFFFF - Density Low Limit (ASCII Hex IEEE float) Typical Response Message, Display Format:...
Page 349
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank 1 Point Full Height Volume for Tall Tanks Command Format: Inquire: Display: <SOH>S6A4TTGGGGGGGGGGGG <SOH>I6A4TT Computer: <SOH>s6A4TTFFFFFFFF <SOH>i6A4TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGGGGGGGG - Full Height Volume, Gallons (Decimal) FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 350
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank 4 Point Full, 3/4, 1/2, 1/4 Volumes for Tall Tanks Command Format: Inquire: Display: <SOH>S6A5TTGGGGGGGGGGGGgggggggggggg... <SOH>I6A5TT or: <SOH>S6A5TTGGGGG,gggg,GGGG,ggg Computer: <SOH>s6A5TTFFFFFFFFffffffffFFFFFFFFffffffff <SOH>i6A5TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGGGGGGGG - Full Height Volume, Gallons (Decimal) gggggggggggg - 3/4 Height Volume, Gallons (Decimal)
Page 351
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank 20 Point Full, 95%, 90%,...Volumes for Tall Tanks Command Format: Inquire: Display: <SOH>S6A6TTGGGGGGGGGGGGgggggggggggg... <SOH>I6A6TT or: <SOH>S6A6TTGGGGG,gggg,GGGG,... Computer: <SOH>s6A6TTFFFFFFFF... <SOH>i6A6TT Notes: TT - Tank Number (Decimal, 00=all) 2.GGGGGGGGGGGGgggggggggggg - Series of 20 Volumes, Gallons (Decimal) FFFFFFFF -...
Page 352
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Diameter for Tall Tanks Command Format: Inquire: Display: <SOH>S6A7TTIIII.hh <SOH>I6A7TT Computer: <SOH>s6A7TTFFFFFFFF <SOH>i6A7TT Notes: TT - Tank Number (Decimal, 00=all) IIII.hh - Tank Diameter, Inches and hundredths (Decimal) FFFFFFFF - Tank Diameter, Inches (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 353
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Linear Calculated Full Volume for Tall Tanks Command Format: Inquire: Display: <SOH>S6AATTGGGGGGGGGGGG <SOH>I6AATT Computer: <SOH>s6AATTFFFFFFFF <SOH>i6AATT Notes: TT - Tank Number (Decimal, 00=all) GGGGGGGGGGGG - Full Height Volume, Gallons (Decimal) FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 354
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Probe Offset for Tall Tanks Command Format: Inquire: Display: <SOH>S6AFTTIIII.hh <SOH>I6AFTT Computer: <SOH>s6AFTTFFFFFFFF <SOH>i6AFTT Notes: TT - Tank Number (Decimal, 00=all) IIII.hh - Probe offset, Inches and hundredths (Decimal) FFFFFFFF - Probe offset, Inches (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 355
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Low Level Limit for Tall Tanks Command Format: Inquire: Display: <SOH>S6C1TTGGGGGGGGGGGG <SOH>I6C1TT Computer: <SOH>s6C1TTFFFFFFFF <SOH>i6C1TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGGGGGGG - Low Level Limit, Gallons (Decimal) FFFFFFFF - Low Level Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 356
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank High Level Limit for Tall Tanks Command Format: Inquire: Display: <SOH>S6C2TTGGGGGGGGGGGG <SOH>I6C2TT Computer: <SOH>s6C2TTFFFFFFFF <SOH>i6C2TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGGGGGGGG - High Level Limit, Gallons (Decimal) FFFFFFFF - High Level Limit, Gallons (ASCII Hex IEEE float) * Set Tank Maximum Volume Limit (628 or 6C8 cmd) must be set before the High Level Limit.
Page 357
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Overfill Level Limit for Tall Tanks Command Format: Inquire: Display: <SOH>S6C3TTGGGGGGGGGGGG <SOH>I6C3TT Computer: <SOH>s6C3TTFFFFFFFF <SOH>i6C3TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGGGGGGGG - Overfill Level Limit, Gallons (Decimal) FFFFFFFF - Overfill Level Limit, Gallons (ASCII Hex IEEE float) * Set Tank Maximum Volume Limit (628 cmd) must be set before the Overfill Level Limit.
Page 358
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Sudden Loss Limit for Tall Tanks Command Format: Inquire: Display: <SOH>S6C5TTGGGGGGGGGGGG <SOH>I6C5TT Computer: <SOH>s6C5TTFFFFFFFF <SOH>i6C5TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGGGGGGGG - Sudden Loss Limit, Gallons (Decimal) FFFFFFFF - Sudden Loss Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 359
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Maximum Volume Limit for Tall Tanks Command Format: Inquire: Display: <SOH>S6C8TTGGGGGGGGGGGG <SOH>I6C8TT Computer: <SOH>s6C8TTFFFFFFFF <SOH>i6C8TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGGGGGGG - Maximum Volume Limit, Gallons (Decimal) FFFFFFFF - Maximum Volume Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 360
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Delivery Required Limit for Tall Tanks Command Format: Inquire: Display: <SOH>S6C9TTGGGGGGGGGGGG <SOH>I6C9TT Computer: <SOH>s6C9TTFFFFFFFF <SOH>i6C9TT Notes: TT - Tank Number (Decimal, 00=all) GGGGGGGGGGGG - Delivery Required Limit, Gallons (Decimal) FFFFFFFF - Delivery Required Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 361
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Printout Tank Setup Tabs Command Format: Display: <SOH>I6SUttTT Computer: not supported Notes: tt - Tank Number (Decimal, [01..32] 00=all tanks) TT - tab number 00=All tabs 01=General 02=Limits 03=Environmental Tests 04=All Tanks 05=Product...
Page 362
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 6SU: (Continued) DIAMETER: 96.0 INCHES TILT: 0.0 INCHES THERMAL COEFFICIENT: 0.0007 METER DATA PRESENT: PUMP THRESHOLD: 200 GALLONS STICK OFFSET FUEL: 0.0 INCHES STICK OFFSET WATER: 0.0 INCHES DELIVERY DELAY: 5.0 MINUTES GROSS TEST FAIL: ALARMS ENABLED PERIODIC TEST FAIL:...
Page 363
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 6SU: (Continued) TYPE: MULTI POINT SOURCE: METERED DROP CHART LAST CHANGE: yyyy-mm-dd STATUS: INCOMPLETE CHART VOLUME ENTRY: ABSOLUTE VOLUME HEIGHT VOLUME HEIGHT VOLUME --- ------- --------- --- ------- --------- 001 hhhh.hh vvvvvv.vv 003 hhhh.hh vvvvvv.vv 002 hhhh.hh vvvvvv.vv 004 hhhh.hh vvvvvv.vv...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.7 SENSOR SETUP Function Code: Version 1 Function Type: Set Liquid Sensor Configuration Command Format: Inquire: Display: <SOH>S701SSf <SOH>I701SS Computer: <SOH>s701SSf <SOH>i701SS Typical Response Message, Display Format: <SOH> I701SS JAN 28, 1995 10:39 AM LIQUID CONFIGURATION DEVICE LABEL...
Page 365
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Liquid Sensor Location Label Command Format: Inquire: Display: <SOH>S702SSaaaaaaaaaaaaaaaaaaaa <SOH>I702SS Computer: <SOH>s702SSaaaaaaaaaaaaaaaaaaaa <SOH>i702SS Typical Response Message, Display Format: <SOH> I702SS JAN 28, 1995 10:39 AM LIQUID LABEL DEVICE LABEL LIQUID SENSOR #1...
Page 366
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Liquid Sensor Type Command Format: Inquire: Display: <SOH>S703SSt <SOH>I703SS Computer: <SOH>s703SSt <SOH>i703SS Typical Response Message, Display Format: <SOH> I703SS JAN 28, 1995 10:40 AM LIQUID TYPE SENSOR LOCATION TYPE LIQUID SENSOR #1...
Page 367
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Liquid Sensor Category Command Format: Inquire: Display: <SOH>S704SSc <SOH>I704SS Computer: <SOH>s704SSc <SOH>i704SS Typical Response Message, Display Format: <SOH> I704SS JAN 28, 1995 10:40 AM LIQUID CATEGORY SENSOR LOCATION TYPE LIQUID SENSOR #1...
Page 368
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Vapor Sensor Configuration Command Format: Inquire: Display: <SOH>S706SSf <SOH>I706SS Computer: <SOH>s706SSf <SOH>i706SS Typical Response Message, Display Format: <SOH> I706SS JAN 28, 1995 10:40 AM VAPOR CONFIGURATION DEVICE LABEL CONFIGURED VAPOR SENSOR #1...
Page 369
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Vapor Sensor Location Label Command Format: Inquire: Display: <SOH>S707SSaaaaaaaaaaaaaaaaaaaa <SOH>I707SS Computer: <SOH>s707SSaaaaaaaaaaaaaaaaaaaa <SOH>i707SS Typical Response Message, Display Format: <SOH> I707SS JAN 28, 1995 10:40 AM VAPOR LABEL DEVICE LABEL VAPOR SENSOR #1...
Page 370
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Vapor Sensor Alarm Threshold Command Format: Inquire: Display: <SOH>S708SSVVVVVV <SOH>I708SS Computer: <SOH>s708SSFFFFFFFF <SOH>i708SS Notes: SS - Vapor Sensor Number (Decimal, 00=all) VVVVVV - Vapor alarm threshold (Decimal) FFFFFFFF - Vapor alarm threshold (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 371
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Vapor Sensor Category Command Format: Inquire: Display: <SOH>S709SSt <SOH>I709SS Computer: <SOH>s709SSt <SOH>i709SS Typical Response Message, Display Format: <SOH> I709SS JAN 28, 1995 10:40 AM VAPOR CATEGORY SENSOR LOCATION CATEGORY VAPOR SENSOR #1...
Page 372
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Groundwater Sensor Configuration Command Format: Inquire: Display: <SOH>S711SSf <SOH>I711SS Computer: <SOH>s711SSf <SOH>i711SS Typical Response Message, Display Format: <SOH> I711SS JAN 28, 1995 10:41 AM GROUNDWATER CONFIGURATION DEVICE LABEL CONFIGURED GROUNDWATER #1...
Page 373
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Groundwater Sensor Location Label Command Format: Inquire: Display: <SOH>S712SSaaaaaaaaaaaaaaaaaaaa <SOH>I712SS Computer: <SOH>s712SSaaaaaaaaaaaaaaaaaaaa <SOH>i712SS Typical Response Message, Display Format: <SOH> I712SS JAN 28, 1995 10:41 AM GROUNDWATER LABEL DEVICE LABEL GROUNDWATER #1...
Page 374
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Groundwater Sensor Category Command Format: Inquire: Display: <SOH>S713SSt <SOH>I713SS Computer: <SOH>s713SSt <SOH>i713SS Typical Response Message, Display Format: <SOH> I713SS JAN 28, 1995 10:41 AM GROUNDWATER CATEGORY SENSOR LOCATION CATEGORY GROUNDWATER #1...
Page 375
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set MAG Sensor Alarm Upgrade Delay Command Format: Inquire: Display: <SOH>S727SSHHHH <SOH>I727SS Computer: <SOH>s727SSHHHH <SOH>i727SS Notes: Only responds to Smart Sensors that are of type MAG Sensor. SS - Smart Sensor Number (Decimal, 00=all) HHHH - MAG Sensor Alarm Upgrade Delay, Hours (ASCII Decimal) Typical Response Message, Display Format: <SOH>...
Page 376
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set MAG Sensor Alarm Threshold Command Format: Inquire: Display: <SOH>S728SSAAxxx.xx <SOH>I728SS Computer: <SOH>s728SSAAFFFFFFFF <SOH>i728SS Notes: Only responds when the Smart Sensor is a MAG Sensor type. SS - Smart Sensor Number (ASCII Decimal, 00=all) AA - Alarm Definition Record ID, (ASCII Decimal) xxx.xx - Alarm Threshold, Inches or Deg.
Page 377
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set MAG Sensor Label Command Format: Inquire: Display: <SOH>S72ESSaaaaaaaaaaaaaaaaaaaa <SOH>I72ESS Computer: <SOH>s72ESSaaaaaaaaaaaaaaaaaaaa <SOH>i72ESS Notes: MAG Sensor card must be installed If SS=00, only configured sensors are used SS - MAG Sensor number, 00=all sensors a - 20 ASCII characters [20h-7Eh] Typical Response Message, Display Format: <SOH>...
Page 378
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set MAG Sensor Configuration Command Format: Inquire: Display: <SOH>S72FSSc <SOH>I72FSS Computer: <SOH>s72FSSc <SOH>i72FSS Notes: MAG Sensor card must be installed SS - MAG Sensor number, 00=all sensors c - configured 0=off 1=on Typical Response Message, Display Format:...
Page 379
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Type A (2 Wire CL) Sensor Configuration Command Format: Inquire: Display: <SOH>S741SSf <SOH>I741SS Computer: <SOH>s741SSf <SOH>i741SS Typical Response Message, Display Format: <SOH> I741SS JAN 28, 1995 10:41 AM 2 WIRE CL CONFIGURATION DEVICE LABEL...
Page 380
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Type A (2 Wire CL) Sensor Location Label Command Format: Inquire: Display: <SOH>S742SSaaaaaaaaaaaaaaaaaaaa <SOH>I742SS Computer: <SOH>s742SSaaaaaaaaaaaaaaaaaaaa <SOH>i742SS Typical Response Message, Display Format: <SOH> I742SS JAN 28, 1995 10:41 AM 2 WIRE CL LABEL DEVICE LABEL...
Page 381
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Type A (2 Wire CL) Sensor Type Command Format: Inquire: Display: <SOH>S743SSt <SOH>I743SS Computer: <SOH>s743SSt <SOH>i743SS Typical Response Message, Display Format: <SOH> I743SS JAN 28, 1995 10:41 AM 2 WIRE CL TYPE SENSOR LOCATION...
Page 382
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Type A (2 Wire CL) Sensor Category Command Format: Inquire: Display: <SOH>S744SSa <SOH>I744SS Computer: <SOH>s744SSa <SOH>i744SS Typical Response Message, Display Format: <SOH> I743SS JAN 28, 1995 10:41 AM 2 WIRE CL CATEGORY SENSOR LOCATION...
Page 383
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Type B (3 Wire CL) Sensor Configuration Command Format: Inquire: Display: <SOH>S746SSf <SOH>I746SS Computer: <SOH>s746SSf <SOH>i746SS Typical Response Message, Display Format: <SOH> I746SS JAN 28, 1995 10:41 AM 3 WIRE CL CONFIGURATION DEVICE LABEL...
Page 384
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Type B (3 Wire CL) Sensor Location Label Command Format: Inquire: Display: <SOH>S747SSaaaaaaaaaaaaaaaaaaaa <SOH>I742SS Computer: <SOH>s747SSaaaaaaaaaaaaaaaaaaaa <SOH>i742SS Typical Response Message, Display Format: <SOH> I747SS JAN 28, 1995 10:41 AM 3 WIRE CL LABEL DEVICE LABEL...
Page 385
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Type B (3 Wire CL) Sensor Type Command Format: Inquire: Display: <SOH>S748SSt <SOH>I748SS Computer: <SOH>s748SSt <SOH>i748SS Typical Response Message, Display Format: <SOH> I748SS JAN 28, 1995 10:41 AM 3 WIRE CL TYPE SENSOR LOCATION...
Page 386
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Type B (3 Wire CL) Sensor Category Command Format: Inquire: Display: <SOH>S749SSa <SOH>I749SS Computer: <SOH>s749SSa <SOH>i749SS Typical Response Message, Display Format: <SOH> I749SS JAN 28, 1995 10:41 AM 3 WIRE CL CATEGORY SENSOR LOCATION...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.8 PUMP SENSOR SETUP Function Code: Version 1 Function Type: Set Pump configured Command Format: Inquire: Display: <SOH>SP01QQf <SOH>IP01QQ Computer: <SOH>sP01QQf <SOH>iP01QQ Typical Response Message, Display Format: <SOH> IP01QQ JAN 24, 1996 2:54 PM PUMP CONFIGURATION DEVICE LABEL...
Page 388
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pump Label Command Format: Inquire: Display: <SOH>SP02QQaaaaaaaaaaaaaaaaaaaa <SOH>IP02QQ Computer: <SOH>sP02QQaaaaaaaaaaaaaaaaaaaa <SOH>iP02QQ Typical Response Message, Display Format: <SOH> IP02QQ JAN 24, 1996 2:54 PM PUMP LABEL DEVICE LABEL REGULAR UNLEADED <ETX>...
Page 389
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pump Mode Command Format: Inquire: Display: <SOH>SP03QQf <SOH>IP03QQ Computer: <SOH>sP03QQf <SOH>iP03QQ Typical Response Message, Display Format: <SOH> IP03QQ JAN 24, 1996 2:54 PM PUMP MODE PUMP MODE Pm 1:REGULAR UNLEADED TLS Pump Control <ETX>...
Page 390
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pump Tank Number Command Format: Inquire: Display: <SOH>SP04QQtt <SOH>IP04QQ Computer: <SOH>sP04QQtt <SOH>iP04QQ Typical Response Message, Display Format: <SOH> IP04QQ JAN 24, 1996 2:54 PM PUMP TANK NUMBER PUMP TANK NUMBER Q 1:...
Page 391
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pump Control Devices Command Format: Inquire: Display: <SOH>SP05QQttff <SOH>IP05QQ Computer: <SOH>sP05QQttff <SOH>iP05QQ Notes: Unassigned - To de-assign the Pump Control Device the user must set both tt = 00 and ff = 00 for the operation to be valid.
Page 392
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pump – Pump Sense Device Command Format: Inquire: Display: <SOH>SP06QQttff <SOH>IP06QQ Computer: <SOH>sP06QQttff <SOH>iP06QQ Notes: Unassigned - To de-assign the Pump Sense Device the user must set both tt = 00 and ff = 00 for the operation to be valid.
Page 393
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Set Pump – Pump Monitor Device Command Format: Inquire: Display: <SOH>SP07QQttff <SOH>IP07QQ Computer: <SOH>sP07QQttff <SOH>iP07QQ Notes: QQ - Pump ID tt - Device Type ff - Device ID Unassigned - To de-assign the Pump Sense Device the user must set both tt = 00 and ff = 00 for the operation to be valid.
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.9 PRESSURE LINE LEAK SETUP Function Code: Version 1 Function Type: Set Line Leak Lockout Schedule (All Types) Command Format: Inquire: Display: <SOH>S75A00SHHmmHHmm<CR> (if S=0) <SOH>I75A00 NsHHmmeHHmm<CR> (if S=1) N<CR> (if S=2) Computer: <SOH>s75A00SHHmmHHmm<CR> (if S=0) <SOH>i75A00 NsHHmmeHHmm<CR>...
Page 395
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Continuous Handle Alarm Timeout Command Format: Inquire: Display: <SOH>S774QQtt <SOH>I774QQ Computer: <SOH>s774QQtt <SOH>i774QQ Notes: QQ - Pressure Line Leak sensor number (Decimal, 00=All) tt - Continuous Handle Alarm Timeout (Decimal, in hours, 1-16) Typical Response Message, Display Format: <SOH>...
Page 396
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Profile Line Test Leak Rate Command Format: Inquire: Display: <SOH>S775QQrr.rr <SOH>I775QQ Computer: <SOH>s775QQFFFFFFFF <SOH>i775QQ Notes: QQ - Pressure Line Leak Sensor Number (Decimal, 00 = all) rr.rr - Profile Line Test Leak Rate, GPH (Decimal) FFFFFFFF - Profile Line Test Leak Rate, GPH (ASCII Hex IEEE float) Typical Response Message, Display Format:...
Page 397
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Profile Line Test Reference Pressure Command Format: Inquire: Display: <SOH>S776QQppp.pp <SOH>I776QQ Computer: <SOH>s776QQFFFFFFFF <SOH>i776QQ Notes: QQ - Pressure Line Leak Sensor Number (Decimal, 00 = all) ppp.pp - Profile Line Test Reference Pressure, PSI (Decimal) FFFFFFFF - Profile Line Test Reference Pressure, PSI (ASCII Hex IEEE float)
Page 398
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Primary Pipe Diameter Command Format: Inquire: Display: <SOH>S777QQI.hh <SOH>I777QQ Computer: <SOH>s777QQFFFFFFFF <SOH>i777QQ Notes: QQ - Pressure Line Leak Sensor Number (Decimal, 00=all) I.hh - Pipe Diameter, Inches and hundredths (Decimal) FFFFFFFF - Pipe Diameter, Inches (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 399
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Secondary Pipe Diameter Command Format: Inquire: Display: <SOH>S778QQI.hh <SOH>I778QQ Computer: <SOH>s778QQFFFFFFFF <SOH>i778QQ Notes: QQ - Pressure Line Leak Sensor Number (Decimal, 00=all) I.hh - Pipe Diameter, Inches and hundredths (Decimal) FFFFFFFF - Pipe Diameter, Inches (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 400
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Primary Pipe Bulk Modulus Command Format: Inquire: Display: <SOH>S779QQBBBBBB <SOH>I779QQ Computer: <SOH>s779QQFFFFFFFF <SOH>i779QQ Notes: QQ - Pressure Line Leak Sensor Number (Decimal, 00=all) BBBBBB - Pipe Bulk Modulus, PSI (Decimal) FFFFFFFF - Pipe Bulk Modulus, PSI (ASCII Hex IEEE float) Set to Default - To set Bulk Modulus to default enter 0 Typical Response Message, Display Format:...
Page 401
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Secondary Pipe Bulk Modulus Command Format: Inquire: Display: <SOH>S77AQQBBBBBB <SOH>I77AQQ Computer: <SOH>s77AQQFFFFFFFF <SOH>i77AQQ Notes: QQ - Pressure Line Leak Sensor Number (Decimal, 00=all) BBBBBB - Pipe Bulk Modulus, PSI (Decimal) FFFFFFFF - Pipe Bulk Modulus, PSI (ASCII Hex IEEE float) Set to Default - To set Bulk Modulus to default enter 0 Typical Response Message, Display Format:...
Page 402
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Thermal Expansion Coefficient Command Format: Inquire: Display: <SOH>S77BQQc.cccccc <SOH>I77BQQ Computer: <SOH>s77BQQFFFFFFFF <SOH>i77BQQ Notes: QQ - Pressure Line Leak Sensor Number (Decimal, 00=all) c.cccccc - Thermal Expansion Coefficient (Decimal) FFFFFFFF - Thermal Expansion Coefficient (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 403
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Low Pressure Shutoff Command Format: Inquire: Display: <SOH>S77CQQf <SOH>I77CQQ Computer: <SOH>s77CQQf <SOH>i77CQQ Typical Response Message, Display Format: <SOH> I77CQQ JAN 24, 2000 2:54 PM PRESSURE LINE LEAK LOW PRESSURE SHUTOFF LINE LP SHUTOFF...
Page 404
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Altitude Pressure Offset Command Format: Inquire: Display: <SOH>S77DQQII.p <SOH>I77DQQ Computer: <SOH>s77DQQFFFFFFFF <SOH>i77DQQ Notes: QQ - Pressure Line Leak sensor number (Decimal, 00=All) II.p - Altitude Pressure Offset, PSI or KPA (Decimal) FFFFFFFF - Altitude Pressure Offset, PSI or KPA (ASCII Hex IEEE float) Value must be within the range of +5.0 to -5.0 PSI or 34.4 to -34.4 KPA...
Page 405
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Passive 0.10 GPH Test Enable Flag Command Format: Inquire: Display: <SOH>S77EQQf <SOH>I77EQQ Computer: <SOH>s77EQQf <SOH>i77EQQ Typical Response Message, Display Format: <SOH> I77EQQ JUL 14, 2004 10:15 PM PRESSURE LINE LEAK PASSIVE 0.10 GPH LINE...
Page 406
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Secondary Pipe Length Only used for the larger diameter line in dual diameter piping configurations Command Format: Inquire: Display: <SOH>S77FQQLLLL <SOH>I77FQQ Computer: <SOH>s77FQQFFFFFFFF <SOH>i77FQQ Notes: QQ - Pressure Line Leak Sensor Number (Decimal, 00=all) LLLL - Pipe Length, Feet (Decimal)
Page 407
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Fuel out limit Command Format: Inquire: Display: <SOH>S77GQQI.hh <SOH>I77GQQ Computer: <SOH>s77GQQFFFFFFFF <SOH>i77GQQ Typical Response Message, Display Format: <SOH> I77GQQ JAN 24, 1996 2:54 PM PRESSURE LINE LEAK FUEL OUT LIMIT LINE LIMIT...
Page 408
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak General Setup Inquiry Command Format: Display: <SOH>I780QQ Computer: not supported Typical Response Message, Display Format: <SOH> I780QQ JAN 14, 1995 10:15 PM PRESSURE LINE LEAK SETUP Q 1:UNLEADED REGULAR PIPE TYPE: FIBERGLASS...
Page 409
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Configuration Command Format: Inquire: Display: <SOH>S781QQf <SOH>I781QQ Computer: <SOH>s781QQf <SOH>i781QQ Typical Response Message, Display Format: <SOH> I781QQ JAN 24, 1996 2:54 PM PRESSURE LLD CONFIGURATION DEVICE LABEL CONFIGURED...
Page 410
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Label Command Format: Inquire: Display: <SOH>S782QQaaaaaaaaaaaaaaaaaaaa <SOH>I782QQ Computer: <SOH>s782QQaaaaaaaaaaaaaaaaaaaa <SOH>i782QQ Typical Response Message, Display Format: <SOH> I782QQ JAN 24, 1996 2:54 PM PRESSURE LLD LABEL DEVICE LABEL REGULAR UNLEADED...
Page 411
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak 0.10 GPH Test Schedule Command Format: Inquire: Display: <SOH>S783QQf <SOH>I783QQ Computer: <SOH>s783QQf <SOH>i783QQ Typical Response Message, Display Format: <SOH> I783QQ JAN 24, 1996 2:54 PM PRESSURE LINE LEAK 0.10 TEST SCHEDULE LINE 0.10 GPH TEST...
Page 412
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Shutdown Rate Command Format: Inquire: Display: <SOH>S784QQrr <SOH>I784QQ Computer: <SOH>s784QQrr <SOH>i784QQ Typical Response Message, Display Format: <SOH> I784QQ JAN 24, 2000 2:54 PM PRESSURE LINE LEAK SHUTDOWN RATE LINE SHUTDOWN RATE Q 1:REGULAR UNLEADED...
Page 413
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Dispense Mode Command Format: Inquire: Display: <SOH>S786QQf <SOH>I786QQ Computer: <SOH>s786QQf <SOH>i786QQ Note: See L06 if setting line leak dispensing mode to pump sense. Typical Response Message, Display Format: <SOH>...
Page 414
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Piping Material Command Format: Inquire: Display: <SOH>S788QQtt <SOH>I788QQ Computer: <SOH>s788QQtt <SOH>i788QQ Typical Response Message, Display Format: <SOH> I788QQ JUN 14, 2001 10:15 PM PRESSURE LINE LEAK PIPE TYPE LINE PIPE TYPE: Q 1:UNLEADED REGULAR...
Page 415
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Primary Pipe Length Also used for the smaller diameter line in dual diameter piping configurations Command Format: Inquire: Display: <SOH>S789QQLLLL <SOH>I789QQ Computer: <SOH>s789QQFFFFFFFF <SOH>i789QQ Notes: QQ - Pressure Line Leak Sensor Number (Decimal, 00=all) LLLL - Pipe Length, Feet (Decimal)
Page 416
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak 0.20 GPH Test Schedule Command Format: Inquire: Display: <SOH>S78CQQf <SOH>I78CQQ Computer: <SOH>s78CQQf <SOH>i78CQQ Typical Response Message, Display Format: <SOH> I78CQQ JAN 24, 1996 2:54 PM PRESSURE LINE LEAK 0.20 TEST SCHEDULE LINE 0.20 GPH TEST...
Page 417
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak 0.10 GPH Auto Test Enable Command Format: Inquire: Display: <SOH>S78EQQf <SOH>I78EQQ Computer: <SOH>s78EQQf <SOH>i78EQQ Typical Response Message, Display Format: <SOH> I78EQQ JAN 24, 1996 2:54 PM PRESSURE LINE LEAK 0.10 GPH AUTO ENABLE LINE...
Page 418
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Shutoff value (in TLS350 this command was Pressure Line Leak dispense threshold) Command Format: Inquire: Display: <SOH>S78FQQppppp <SOH>I78FQQ Computer: <SOH>s78FQQFFFFFFFF <SOH>i78FQQ Notes: QQ - Pressure Line Leak Sensor Number (Decimal, 00=all) ppppp - Shutoff Value, PSI or KPA (Decimal) FFFFFFFF - Shutoff Value, PSI or KPA (ASCII Hex IEEE float) Value must be within the range of 0.0 to 25.0 PSI or 0.0 to 172.0 KPA...
Page 419
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set controlling pump Command Format: Inquire: Display: <SOH>S78GQQnn <SOH>I78GQQ Computer: <SOH>s78GQQnn <SOH>i78GQQ Typical Response Message, Display Format: <SOH> I78GQQ JAN 24, 1996 2:54 PM PRESSURE LINE LEAK CONTROLLING PUMP LINE CONTROLLING PUMP Q 1:REGULAR UNLEADED...
Page 420
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Line Configuration Command Format: Inquire: Display: <SOH>SL01QQf <SOH>IL01QQ Computer: <SOH>sL01QQf <SOH>iL01QQ Typical Response Message, Display Format: <SOH> IL01QQ JAN 24, 1996 2:54 PM PRESSURE LLD CONFIGURATION DEVICE LABEL CONFIGURED REGULAR UNLEADED...
Page 421
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Leak Monitoring Command Format: Inquire: Display: <SOH>SL03QQf <SOH>IL03QQ Computer: <SOH>sL03QQf <SOH>iL03QQ Typical Response Message, Display Format: <SOH> IL03QQ JAN 24, 1996 2:54 PM PRESSURE LINE LEAK MONITORING LINE MONITORING Q 1:REGULAR UNLEADED...
Page 422
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Pressure Line Sensor Command Format: Inquire: Display: <SOH>SL04QQff <SOH>IL04QQ Computer: <SOH>sL04QQff <SOH>iL04QQ Typical Response Message, Display Format: <SOH> IL04QQ JAN 24, 1996 2:54 PM PRESSURE LINE LEAK LINE LPR Sensor Q 1:REGULAR UNLEADED...
Page 423
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Line Manifolded Command Format: Inquire: Display: <SOH>SL05LLf <SOH>IL05LL Computer: <SOH>sL05LLf <SOH>iL05LL Typical Response Message, Display Format: <SOH> IL05LL JAN 24, 1996 2:54 PM IS LINE MANIFOLDED DEVICE MANIFOLDED Q 1:REGULAR UNLEADED <ETX>...
Page 424
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Line Dispense Mode Command Format: Inquire: Display: <SOH>SL06QQf <SOH>IL06QQ Computer: <SOH>sL06QQf <SOH>iL06QQ Typical Response Message, Display Format: <SOH> IL06QQ JAN 24, 1996 2:54 PM PRESSURE LINE LEAK DISPENSE MODE LINE DISPENSE MODE Q 1:REGULAR UNLEADED...
Page 425
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Line Associated Pump Numbers Command Format: Inquire: Display: <SOH>SL07LLpppp… <SOH>IL07LL Computer: <SOH>sL07LLpppp… <SOH>iL07LL Notes: pp - A sequence of one or more 2-digit-wide zero-padded Pump numbers. If a unique zero entry (00) is given for Pump Numbers then all current Pump assignments for the Line will be removed.
Page 426
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set LPR Sensor Configuration Command Format: Inquire: Display: <SOH>SS51QQf <SOH>IS51QQ Computer: <SOH>sS51QQf <SOH>iS51QQ Typical Response Message, Display Format: <SOH> IS51QQ JAN 24, 1996 2:54 PM LINE_PRESSURE_SENSOR CONFIGURATION DEVICE LABEL CONFIGURED REGULAR UNLEADED...
Page 427
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set LPR Sensor Label Command Format: Inquire: Display: <SOH>SS53QQaaaaaaaaaaaaaaaaaaaa <SOH>IS53QQ Computer: <SOH>sS53QQaaaaaaaaaaaaaaaaaaaa <SOH>iS53QQ Typical Response Message, Display Format: <SOH> IS53QQ JAN 24, 1996 2:54 PM LINE_PRESSURE_SENSOR LABEL DEVICE LABEL REGULAR UNLEADED <ETX>...
Page 428
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get LPR Sensor Serial Number Command Format: Display: <SOH>IS54QQ Computer: <SOH>iS54QQ Typical Response Message, Display Format: <SOH> IS54QQ OCT 09, 2008 01:36 PM LINE PRESSURE SENSOR SENSOR LABEL SERIAL NUMBER LINE LABEL 1 1179401887...
Page 429
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Line Pressure Sensor Alarm History Report Command Format: Display: <SOH>IS55QQ Computer: <SOH>iS55QQ Typical Response Message, Display Format: <SOH> IS55SS JAN 22, 2003 3:07 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 430
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get Pressure LPR Sensor Sample Data Command Format: Display: <SOH>IS56QQ Computer: <SOH>iS56QQ Typical Response Message, Display Format: <SOH> IS56QQ JAN 24, 1996 2:54 PM LINE PRESSURE SENSOR SAMPLES DEVICE TIME SAMPLES...
Page 431
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get Line Pressure Sensor Status Command Format: Display: <SOH>ISA1SS Computer: <SOH>iSA1SS Typical Response Message, Display Format: <SOH> ISA100 MAY 12, 2008 3:06 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.10 Reconciliation Setup Function Code: Version 2 Function Type: Set LV/MDIM Configuration Command Format: Inquire: Display: <SOH>S51NIIf <SOH>I51NII Computer: <SOH>s51NIIf <SOH>i51NII Typical Response Message, Display Format: <SOH> I51NII JUN 22, 2009 3:12 PM MDIM CONFIGURATION DEVICE LABEL CONFIGURED...
Page 433
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set LV/MDIM Setup Configuration Command Format: Inquire: Display: <SOH>S51PNNUUppQQQQ <SOH>I51P00 Computer: <SOH>s51PNNUUppQQQQ <SOH>i51P00 Notes: NN - DIM Device Number (Decimal) UU - Unit Conversion (Decimal) pp - Pulse Conversion (Decimal) QQQQ - Custom Pulse Conversion (Decimal) QQQQ is optional when PP is not custom.
Page 434
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set LV/MDIM Label Command Format: Inquire: Display: <SOH>S51QIIaaaaaaaaaaaaaaaaaaaa <SOH>I51QII Computer: <SOH>s51QIIaaaaaaaaaaaaaaaaaaaa <SOH>i51QII Typical Response Message, Display Format: <SOH> I51QII JUN 22, 2009 3:12 PM LV/MDIM LABEL DEVICE LABEL MDIM #1 <ETX>...
Page 435
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: DIM Software Revision Command Format: Display: <SOH>I790PP Computer: <SOH>i790PP Notes: PP - Communication Port Number (Decimal, 00=all) Typical Response Message, Display Format: <SOH> I790PP 1, 2000 8:00 AM EDIM: 7VR:GILBARCO 001.ATD:Jan 4 2010 <ETX>...
Page 436
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Electronic Dispenser Interface String Command Format: Display: <SOH>I792NN Computer: <SOH>i792NN Typical Response Message, Display Format: <SOH> I792NN JUN 22, 2009 3:12 PM DISP. MODULE DATA STRING EDIM 1: aaaaaaaaaaaa <ETX>...
Page 437
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Reconciliation Auto Daily Closing Time Command Format: Inquire: Display: <SOH>S79300HHmm <SOH>I79300 Computer: <SOH>s79300HHmm <SOH>i79300 Typical Response Message, Display Format: <SOH> I79300 JAN 22, 2009 3:24 PM AUTOMATIC DAILY CLOSING TIME: 2:00 AM <ETX>...
Page 438
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Auto Shift Closing Time 1, 2, 3, 4 Command Format: Inquire: Display: <SOH>S794SSHHmm <SOH>I794SS Computer: <SOH>s794SSHHmm <SOH>i794SS Typical Response Message, Display Format: <SOH> I794SS JAN 22, 2009 3:24 PM AUTO SHIFT #1 CLOSING TIME:...
Page 439
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Periodic Reconciliation Mode Command Format: Inquire: Display: <SOH>S79500ss <SOH>I79500 Computer: <SOH>s79500ss <SOH>i79500 Typical Response Message, Display Format: <SOH> I79500 JAN 22, 2009 3:24 PM PERIODIC RECONCILIATION MODE: MONTHLY <ETX>...
Page 440
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Periodic Reconciliation Report Length Command Format: Inquire: Display: <SOH>S79600dd <SOH>I79600 Computer: <SOH>s79560dd <SOH>i79600 Typical Response Message, Display Format: <SOH> I79600 JAN 22, 2009 3:24 PM PERIODIC RECONCILIATION LENGTH: 31 DAYS <ETX>...
Page 441
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Periodic Reconciliation Alarm Flag Command Format: Inquire: Display: <SOH>S79700ss <SOH>I79700 Computer: <SOH>s79700ss <SOH>i79700 Typical Response Message, Display Format: <SOH> I79700 JAN 22, 2009 3:24 PM PERIODIC RECONCILIATION ALARM: DISABLED <ETX>...
Page 442
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Periodic Reconciliation Alarm Threshold Command Format: Inquire: Display: <SOH>S79800PP.hh <SOH>I79800 Computer: <SOH>s79800FFFFFFFF <SOH>i79800 Notes: PP.hh - Alarm Threshold, Percent and hundredths (Decimal) FFFFFFFF - Alarm Threshold, Percent (ASCII Hex IEEE float) Typical Response Message, Display Format: i) When per-tank alarm threshold is disabled (using 7C1 command) <SOH>...
Page 443
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Periodic Reconciliation Alarm Offset Command Format: Inquire: Display: <SOH>S79900GGGGGG <SOH>I79900 Computer: <SOH>s79900FFFFFFFF <SOH>i79900 Notes: GGGGGG - Alarm Offset, Gallons (Decimal) FFFFFFFF - Alarm Threshold, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 444
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Shift Manual Adjustment Value Command Format: Inquire: Display: <SOH>S79BTTssGGGGGG <SOH>I79BTTss Computer: <SOH>s79BTTssFFFFFFFF <SOH>i79BTTss Notes: TT - Tank Number ss - Shift Mode 01=Current 02=Previous GGGGGG - Adjustment Value, Gallons (Decimal) FFFFFFFF - Adjustment Value, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 445
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Daily Manual Adjustment Value Command Format: Inquire: Display: <SOH>S79CTTMMDDGGGGGG <SOH>I79CTTMMDD Computer: <SOH>s79CTTMMDDFFFFFFFF <SOH>i79CTTMMDD Notes: TT - Tank Number MMDD - Month and Day GGGGGG - Adjustment Value, Gallons (Decimal) FFFFFFFF - Adjustment Value, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 446
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Close Current Reconciliation Shift Command Format: Inquire: Display: <SOH>S79D00ff <SOH>I79D00 Computer: <SOH>s79D00ff <SOH>i79D00 Typical Response Message, Display Format: <SOH> I79D00 JAN 22, 1996 3:23 PM MANUAL SHIFT CLOSE RECONCILIATION SHIFT CLOSE STATUS: STATION IS BUSY *** CLOSE SHIFT PENDING ***...
Page 447
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Clear Tank Map Table Command Format: Display: <SOH>S79E00149 Computer: <SOH>s79E00149 Notes: 149 - This verification code must be sent to confirm the command Typical Response Message, Display Format: <SOH>...
Page 448
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set BIR Temperature Compensation Flag Command Format: Inquire: Display: <SOH>S79F00f <SOH>I79F00 Computer: <SOH>s79F00f <SOH>i79F00 Typical Response Message, Display Format: <SOH> I79F00 JAN 22, 2009 3:24 PM TEMP COMPENSATION STANDARD <ETX>...
Page 449
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Meter Tank Map Command Format: Inquire: Display: <SOH>S79G00 Bxx.Sx FP MM F NN <SOH>I79G00 <SOH>S79G00 Cxx FP MM F NN <SOH>I79G00 Computer: <SOH>s79G00 Bxx.Sx FP MM F NN <SOH>i79G00 <SOH>s79G00 Cxx FP MM F NN <SOH>i79G00...
Page 450
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Meter Map Lock/Unlock by Position Command Format: Inquire: Display: <SOH>S79H00 Bxx.Sx FP MM L <SOH>I79H00 <SOH>S79H00 Cxx FP MM L <SOH>I79H00 Computer: <SOH>s79H00 Bxx.Sx FP MM L <SOH>i79H00 <SOH>s79H00 Cxx FP MM L <SOH>i79H00...
Page 451
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Meter Map Lock/Unlock All Position Command Format: Inquire: Display: <SOH>S79I00L <SOH>I79I00 Computer: <SOH>s79I00L <SOH>i79I00 Typical Response Message, Display Format: <SOH> I79I00 JAN 22, 2009 3:24 PM SOURCE REAL REAL ADDRESS METER LOCKED...
Page 452
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Daily Manual Adjustment Value (Date Range) Command Format: Inquire: Display: <SOH>S79JTTYYMMDDGGGGGG <SOH>I79JTTYYMMDD Computer: <SOH>s79JTTYYMMDDFFFFFFFF <SOH>i79JYYTTMMDD Notes: TT - Tank Number YYMMDD - Date GGGGGG - Manual Adjustment Volume, Gallons (Decimal) FFFFFFFF - Manual Adjustment Volume, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 453
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set BIR Status Warning Enable Command Format: Inquire: Display: <SOH>S79K00s <SOH>I79K00 Computer: <SOH>s79K00s <SOH>i79K00 Typical Response Message, Display Format: <SOH> I79K00 JAN 22, 2009 3:24 PM BIR STATUS WARNING: ENABLED <ETX>...
Page 454
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Reconciliation Report Close Day Command Format: Inquire: Display: <SOH>S79L00D <SOH>I79L00 Computer: <SOH>s79L00D <SOH>i79L00 Typical Response Message, Display Format: <SOH> I79L00 JAN 22, 2009 3:24 PM PERIODIC RECONCILIATION CLOSE DAY: SUNDAY <ETX>...
Page 455
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Alarm Threshold Delivery Type Command Format: Inquire: Display: <SOH>S79M00d <SOH>I79M00 Computer: <SOH>s79M00d <SOH>i79M00 Typical Response Message, Display Format: <SOH> I79M00 JAN 22, 2009 3:24 PM ALARM THRESHOLD DELIVERY TYPE: STANDARD <ETX>...
Page 456
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Shift Manual Adjustment Value (Date Range/Shift Number) Command Format: Inquire: Display: <SOH>S79NTTSSYYMMDDGGGGGG <SOH>I79NTTSSYYMMDD Computer: <SOH>s79NTTSSYYMMDDFFFFFFFF <SOH>i79NTTSSYYMMDD Notes: TT - Tank Number (Decimal, 00=all) SS - Shift Number (Decimal, 00=all) YYMMDD - Date GGGGGG - Manual Adjustment Volume, Gallons (Decimal) FFFFFFFF - Manual Adjustment Volume, Gallons (ASCII Hex IEEE float)
Page 457
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Meter Calibration Offset by Meter Command Format: Inquire: Display: <SOH>S79P00 Bxx.Sx FP MM 0.0000 <SOH>I79P00 <SOH>S79P00 Cxx FP MM 0.0000 <SOH>I79P00 Computer: <SOH>s79H00 Bxx.Sx FP MM FFFFFFFF <SOH>i79P00 <SOH>s79H00 Cxx FP MM FFFFFFFF <SOH>i79P00...
Page 458
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set User Fueling Position Command Format: Inquire: Display: <SOH>S79Q00 Bxx.Sx FF BB <SOH>I79Q00 <SOH>S79Q00 Cxx FP BB <SOH>I79Q00 Computer: <SOH>s79Q00 Bxx.Sx FF BB <SOH>i79Q00 <SOH>s79Q00 Cxx FP BB <SOH>i79Q00 Notes: Bxx.Sx - VR BUS and Slot...
Page 459
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Get Tank Map Command Format: Display: <SOH>I79S00 Computer: <SOH>i79S00 Typical Response Message, Display Format: <SOH> I79S00 JAN 22, 2009 3:16 PM SOURCE USER REAL REAL TANK / LAST REPORT ADDRESS METER BLEND LOCKED...
Page 460
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Meter Calibration Offset Command Format: Inquire: Display: <SOH>S7B200pp.ppp <SOH>I7B200 Computer: <SOH>s7B200FFFFFFFF <SOH>i7B200 Notes: pp.ppp - Meter Calibration Offset, Percent (Decimal) FFFFFFFF - Meter Calibration Offset, Percent (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 461
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Individual Meter Offset Command Format: Inquire: Display: <SOH>S7B400 FF MM TT +0.00 <SOH>I7B400 Computer: not supported <SOH>i7B400 Notes: FF - Fueling Position (Decimal) MM - Meter Number (Decimal) TT - Tank Number (Decimal) o.oo - Meter Offset, percent (Decimal +/-9.99) Typical Response Message, Display Format:...
Page 462
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Ticketed Delivery Command Format: Display: <SOH>S7B5TTeeYYMMDDHHmmGGGGGG Computer: <SOH>s7B5TTeeYYMMDDHHmmFFFFFFFF Notes: TT - Tank Number (Decimal, 00=all) ee - edit function 01=Edit Ticket (enter, modify) 02=Insert Ticket Delivery YYMMDDHHmm - Delivery Date/Time (End Time) GGGGGG - Ticket Volume, Gallons (Decimal) FFFFFFFF - Ticket Volume, Gallons (ASCII Hex IEEE float) Entering 0 volume will cancel ticketed delivery warning.
Page 463
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 7B5: (Continued) Typical Response Message, Computer Format: <SOH>i7B5TTYYMMDDHHmmTTpPPRRYYMMDDHHmmNNFFFFFFFF... TTpPPRRYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal) p - Product Code (one ASCII character [20h-7Eh]) PP - Probe type (Decimal) RR - Result code - if an error occurs, just error code will be returned (Decimal) 00=OK and data will follow...
Page 464
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set BOL number Command Format: Inquire: Display: <SOH>S7B6TTeeYYMMDDHHmmaa..aa <SOH>I7B6TT Computer: <SOH>s7B6TTeeYYMMDDHHmmaa..aa <SOH>i7B6TT Notes: TT - Tank Number (Decimal) ee - edit function 01=Edit Ticket (enter, modify) 02=Insert Ticketed Delivery YYMMDDHHmm - Delivery Date/Time (End Time) aa..aa - Bill of Lading Number Typical Response Message, Display Format:...
Page 465
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 7B6 Notes: (Continued) Typical Response Message, Computer Format: <SOH>i7B6TTYYMMDDHHmmTTpPPRRYYMMDDHHmmAAaa..aaNNFFFFFFFF...FFFFFFFF... TTpPPRRYYMMDDHHmmAAaa..aaNNFFFFFFFF...FFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal) p - Product Code (Decimal) PP - Probe type (Decimal) RR - Result code (Decimal) - if error occurs, only error code is returned 00=OK and data will follow...
Page 466
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Ticketed Delivery Info Command Format: Display: <SOH>S7BGTTeeYYMMDDHHmmGGGGGG, gggggg,TTT.TT, aa.aa,DD..DD Computer: <SOH>s7BGTTeeYYMMDDHHmmFFFFFFFF gggggg,TTT.TT, aa.aa,DD..DD Notes: TT - Tank Number (Decimal, 00=all) ee - edit function 01=Edit Ticket (enter, modify) 02=Insert Ticket Delivery YYMMDDHHmm - Delivery Date/Time (End Time) GGGGGG - Ticket Volume, Gallons (Decimal)
Page 467
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 7BG: (Continued) Typical Response Message, Computer Format: <SOH>i7BGTTYYMMDDHHmmeeTTpPPRRYYMMDDHHmmNNFFFFFFFFaa.aaDD..DD... TTpPPRRYYMMDDHHmmNNFFFFFFFFaa.aaDD..DD...&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time ee - edit function 01=Edit Ticket (enter, modify) 02=Insert Ticket Delivery TT - Tank Number (Decimal) p - Product Code (one ASCII character [20h-7Eh]) PP - Probe type (Decimal) RR - Result code - if an error occurs, just error code will be...
Page 468
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Tank Periodic Reconciliation Alarm Threshold Enable Command Format: Inquire: Display: <SOH>S7C100f <SOH>I7C100 Computer: <SOH>s7C100f <SOH>i7C100 Typical Response Message, Display Format: <SOH> I7C100 JUN 22, 2009 3:12 PM TANK PERIODIC RECONCILIATION ALARM THRESHOLD: DISABLED <ETX>...
Page 469
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Tank Periodic Reconciliation Alarm Threshold Command Format: Inquire: Display: <SOH>S7C2TTPP.hh <SOH>I7C2TT Computer: <SOH>s7C2TTFFFFFFFF <SOH>i7C2TT Notes: TT - Tank Number (Decimal, 00 = all) PP.hh - Tank Alarm Threshold, Percent and hundredths (Decimal) FFFFFFFF - Tank Alarm Threshold, Percent (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 470
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: Set HRM Maximum Volume Limit Command Format: Inquire: Display: <SOH>S7C3TTGGGGGG <SOH>I7C3TT Computer: <SOH>s7C3TTFFFFFFFF <SOH>i7C3TT Notes: TT - Tank Number (Decimal, 00 = all) GGGGGG - HRM Maximum Volume Limit, Gallons (Decimal) FFFFFFFF - HRM Maximum Volume Limit, Gallons (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 471
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Accuchart Operating Height Span Command Format: Inquire: Display: <SOH>S7D6TTaabb <SOH>I7D6TT Computer: <SOH>s7D6TTaabb <SOH>i7D6TT Notes: TT - Tank Number [01..32] (Decimal, 00 = all) aa - Max operating level in percent of diameter [50-99] (Decimal) bb - Min operating level in percent of diameter [00-45] (Decimal) Typical Response Message, Display Format: <SOH>...
Page 472
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: BIR Multiple Threshold Setup Report Command Format: Display: <SOH>I7H0TT Computer: not supported Typical Response Message, Display Format: <SOH> I7H0TT JUN 22, 2009 3:12 PM BIR MULTIPLLE THRESHOLD SETUP REPORT TEST TEST THRESHOLD...
Page 473
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set BIR Multiple Threshold Test Type Command Format: Inquire: Display: <SOH>S7H1TTff <SOH>I7H1TT Computer: <SOH>s7H1TTff <SOH>i7H1TT Typical Response Message, Display Format: <SOH> I7H1TT JUN 22, 2009 3:12 PM TEST TYPE MONTHLY ROLLING DAYS...
Page 474
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set BIR Multiple Threshold Rolling Days Command Format: Inquire: Display: <SOH>S7H2TTdd <SOH>I7H2TT Computer: <SOH>s7H2TTdd <SOH>i7H2TT Notes: dd - Only valid when Test Type is 02 – Rolling or 03 – Rolling Consecutive Typical Response Message, Display Format: <SOH>...
Page 475
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set BIR Multiple Threshold Type Enable Command Format: Inquire: Display: <SOH>S7H3TTttf <SOH>I7H3TT Computer: <SOH>s7H3TTttf <SOH>i7H3TT Typical Response Message, Display Format: <SOH> I7H3TT JUN 22, 2009 3:12 PM BIR MULTIPLE THRESHOLD TYPE ENABLE TEST TEST THRESHOLD...
Page 476
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set BIR Multiple Threshold Percentage Command Format: Inquire: Display: <SOH>S7H4TTttxx.xx <SOH>I7H4TT Computer: <SOH>s7H4TTttxx.xx <SOH>i7H4TT Typical Response Message, Display Format: <SOH> I7H4TT JUN 22, 2009 3:12 PM BIR MULTIPLE THRESHOLD PERCENTAGE TEST TEST THRESHOLD...
Page 477
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set BIR Multiple Threshold Offset Value Command Format: Inquire: Display: <SOH>S7H5TTttxxxxxx <SOH>I7H5TT Computer: <SOH>s7H5TTttEEEEEEEE <SOH>i7H5TT Typical Response Message, Display Format: <SOH> I7H5TT JUN 22, 2009 3:12 PM BIR MULTIPLE THRESHOLD OFFSET VALUE TEST TEST THRESHOLD...
Page 478
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.11 PUMP MONITOR RELAY SETUP Function Code: Version 5 Function Type: Set Pump Relay Monitor Stuck Relay Command Format: Inquire: Display: <SOH>S7C7QQSSS <SOH>I7C7QQ Computer: <SOH>s7C7QQFFFFFFFF <SOH>i7C7QQ Notes: SSS - Stuck Relay, Seconds (Decimal, 5 - 600 seconds) FFFFFFFF - Stuck Relay, Seconds (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Page 479
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Set Pump Relay Monitor Max Run Time Command Format: Inquire: Display: <SOH>S7C8QQhh <SOH>I7C8QQ Computer: <SOH>s78CQQFFFFFFFF <SOH>i7C8QQ Notes: hh - Max Run Time, Hours (Decimal, 1 - 8 hours) FFFFFFFF - Max Run Time, Hours (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.12 I/O DEVICE SETUP Function Code: Version 1 Function Type: Set Input Configuration Command Format: Inquire: Display: <SOH>S801IIf <SOH>I801II Computer: <SOH>s801IIf <SOH>i801II Typical Response Message, Display Format: <SOH> I801II MAR 26, 1996 1:50 PM EXTERNAL INPUT CONFIGURATION DEVICE LABEL...
Page 481
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Input Location Label Command Format: Inquire: Display: <SOH>S802IIaaaaaaaaaaaaaaaaaaaa <SOH>I802II Computer: <SOH>s802IIaaaaaaaaaaaaaaaaaaaa <SOH>i802II Typical Response Message, Display Format: <SOH> I802II MAR 26, 1996 1:50 PM EXTERNAL INPUT LABEL DEVICE LABEL aaaaaaaaaaaaaaaaaaaa...
Page 482
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Relay Configuration Command Format: Inquire: Display: <SOH>S806RRf <SOH>I806RR Computer: <SOH>s806RRf <SOH>i806RR Typical Response Message, Display Format: <SOH> I806RR MAR 26, 1996 1:51 PM RELAY CONFIGURATION DEVICE LABEL CONFIGURED OUTPUT RELAY #1 <ETX>...
Page 483
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Relay Location Label Command Format: Inquire: Display: <SOH>S807RRaaaaaaaaaaaaaaaaaaaa <SOH>I807RR Computer: <SOH>s807RRaaaaaaaaaaaaaaaaaaaa <SOH>i807RR Typical Response Message, Display Format: <SOH> I807RR MAR 26, 1996 1:51 PM RELAY LABEL DEVICE LABEL aaaaaaaaaaaaaaaaaaaa <ETX>...
Page 484
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Relay Orientation Command Format: Inquire: Display: <SOH>S809RRs <SOH>I809RR Computer: <SOH>s809RRs <SOH>i809RR Typical Response Message, Display Format: <SOH> I809RR MAR 26, 1996 1:51 PM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 EXTERNAL RELAY #1 NORMALLY OPEN...
Page 485
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Relay Type Command Format: Inquire: Display: <SOH>S80ARRt <SOH>I80ARR Computer: <SOH>s80ARRt <SOH>i80ARR Notes: RR - Relay number (Decimal, 00=all relays) t - type 1=Standard 2=Pump Control Output 3=Momentary 4=Pump Comm Control 5=Vapor Processor (only one relay can be of this type) (future)
Page 486
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set External Input Orientation Command Format: Inquire: Display: <SOH>S80DQQf <SOH>I80DQQ Computer: <SOH>s80DQQf <SOH>i80DQQ Typical Response Message, Display Format: <SOH> I80DQQ JAN 24, 1996 2:54 PM EXTERNAL INPUT ORIENTATION INPUT NAME ORIENTATION...
Page 487
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Input Type Command Format: Inquire: Display: <SOH>S80FIIt <SOH>I80FII Computer: <SOH>s80FIIt <SOH>i80FII Typical Response Message, Display Format: <SOH> I80FII MAR 26, 1996 1:51 PM EXTERNAL INPUT TYPE INPUT NAME TYPE EXTERNAL INPUT #1...
Page 488
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Probe Configuration Command Format: Inquire: Display: <SOH>S821PPf <SOH>I821PP Computer: <SOH>s821PPf <SOH>i821PP Typical Response Message, Display Format: <SOH> I821PP MAR 26, 2007 1:50 PM PROBE CONFIGURATION PROBE LABEL CONFIGURED PROBE #1 PROBE #2...
Page 489
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Probe Label Command Format: Inquire: Display: <SOH>S822PPaaaaaaaaaaaaaaaaaaaa <SOH>I822PP Computer: <SOH>s822PPaaaaaaaaaaaaaaaaaaaa <SOH>i822PP Typical Response Message, Display Format: <SOH> I822PP MAR 26, 2007 1:50 PM PROBE LABEL PROBE LABEL MAG PROBE 1 MAG PROBE 2 <ETX>...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.3.13 MISCELLANEOUS SETUP Function Code: Version 1 Function Type: Setup Communication Card Command Format: Inquire: Display: <SOH>S871PPMMSSQQ <SOH>I871PP Computer: <SOH>s871PPMMSSQQ <SOH>i871PP Typical Response Message, Display Format: <SOH> I871PP NOV 5, 2007 12:00 AM COMMUNICATION CARD SETUP COMM # SLOT # PORT #...
Page 491
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Communication Card Configuration Flag Command Format: Inquire: Display: <SOH>S872ppf <SOH>I872pp Computer: <SOH>s872ppf <SOH>i872pp Typical Response Message, Display Format: <SOH> I872pp 1, 2007 8:10 AM COMMUNICATION CARD CONFIGURATION COMM # SLOT # PORT #...
Page 492
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Communication Port Data Command Format: Inquire: Display: <SOH>S873PPBBDPSH <SOH>I873PP Computer: <SOH>s873PPBBDPSH <SOH>i873PP Notes: PP - Communication Port Number (Decimal) Typical Response Message, Display Format: <SOH> I873PP 1, 2007 8:10 AM PORT SETTINGS: COMM PORT...
Page 493
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 873 Notes: (Continued) Typical Response Message, Computer Format: <SOH>i873PPYYMMDDHHmmppBBDPSH&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time pp – Comm Number (Decimal) BB - Baud Rate (Decimal) 00=Unknown 01=Proprietary 02=300 03=600 04=1200 05=2400 06=4800 07=9600 08=19200...
Page 494
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Communication Card Location Label Command Format: Inquire: Display: <SOH>S874ppaaaaaaaaaaaaaaaaaaaa <SOH>I874pp Computer: <SOH>s874ppaaaaaaaaaaaaaaaaaaaa <SOH>i874pp Notes: pp - Communication Number (Decimal) Typical Response Message, Display Format: <SOH> I874pp 1, 2007 8:10 AM COMMUNICATION CARD LABEL COMM #...
Page 495
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Communication Device Type Command Format: Inquire: Display: <SOH>S877ppdd <SOH>I877pp Computer: <SOH>s877ppdd <SOH>i877pp Typical Response Message, Display Format: <SOH> I87701 JAN 22, 2007 3:16 PM COMM LABEL COMM DEVICE TYPE OFFICE USB MODEM <ETX>...
Page 496
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Modem Dial Type Command Format: Inquire: Display: <SOH>S87B00f <SOH>I87B00 Computer: <SOH>s87B00f <SOH>i87B00 Typical Response Message, Display Format: <SOH> I87B00 JAN 22, 2007 3:16 PM COMM LABEL DIAL TYPE OFFICE TONE <ETX>...
Page 497
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Modem Answer-On Interval Command Format: Inquire: Display: <SOH>S87D00f <SOH>I87D00 Computer: <SOH>s87D00f <SOH>i87D00 Typical Response Message, Display Format: <SOH> I87D00 JAN 22, 2007 3:16 PM COMM LABEL ANSWER-ON OFFICE 4 RINGS <ETX>...
Page 498
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Modem Dial-In String Command Format: Inquire: Display: <SOH>S87ERRaaaaaaaaaaaaaaaaaaaa… <SOH>I87ERR Computer: <SOH>s87ERRaaaaaaaaaaaaaaaaaaaa… <SOH>i87ERR Typical Response Message, Display Format: <SOH> I87ERR JAN 22, 2007 3:14 PM MODEM DIAL-IN STRING RCVR LABEL DIAL-IN STRING...
Page 499
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Modem Dial-Out String Command Format: Inquire: Display: <SOH>S87FRRaaaaaaaaaaaaaaaaaaaa… <SOH>I87FRR Computer: <SOH>s87FRRaaaaaaaaaaaaaaaaaaaa… <SOH>i87FRR Typical Response Message, Display Format: <SOH> I87FRR JAN 22, 2007 3:14 PM MODEM DIAL-OUT STRING RCVR LABEL DIAL-OUT STRING...
Page 500
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set DIM Units Reported Command Format: Inquire: Display: <SOH>S87JppU <SOH>I87Jpp Computer: <SOH>s87JppU <SOH>i87Jpp Typical Response Message, Display Format: <SOH> I87Jpp JAN 22, 2007 3:14 PM DIM UNITS REPORTED COMM # LOCATION UNITS...
Page 501
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Suppress DIM Comm Alarms Command Format: Inquire: Display: <SOH>S87QPPf <SOH>I87QPP Computer: <SOH>s87QPPf <SOH>i87QPP Notes: PP - Port number (Decimal, 00 = All ports) Port is a BIR DIM. f - Alarms Suppression Setting Flag (Decimal) 0 = Disable Alarm Suppression 1 = Enable Alarm Suppression...
Page 502
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Dial Tone Validation Interval Command Format: Inquire: Display: S887PPHHHH I887PP Computer: s887PPHHHH i887PP Notes: PP - Modem or SiteLink Board Number (Port #) (Decimal 01..06) Typical Response Message, Display Format: <SOH>...
Page 503
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: DTR Normal State for Serial Satellite Boards Command Format: Inquire: Display: <SOH>S889PPs <SOH>I889PP Computer: <SOH>s889PPs <SOH>i889PP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> I889PP AUG 22, 2000 4:49 PM...
Page 504
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Satellite Connection String Command Format: Inquire: Display: <SOH>S88ERRaaaaaaaaaaaaaaaaaaaa… <SOH>I88ERR Computer: <SOH>s88ERRaaaaaaaaaaaaaaaaaaaa… <SOH>i88ERR Typical Response Message, Display Format: <SOH> I88ERR JAN 22, 2007 3:14 PM SATELLITE CONNECTION STRING RCVR LOCATION LABEL CONNECTION STR...
Page 505
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set IP Assignment Command Format: Inquire: Display: <SOH>S88GPPf <SOH>I88GPP Computer: <SOH>s88GPPf <SOH>i88GPP Notes: PP - Communication Port Number For Setup Changes to take effect this command must be followed by 88Y Typical Response Message, Display Format: <SOH>...
Page 506
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get IP Address Command Format: Display: <SOH>I88HPP Computer: <SOH>i88HPP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> I88H00 JAN 22, 2007 3:16 PM IP ADDRESS COMM LOCATION IP ADDRESS...
Page 507
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Static IP Address Command Format: Inquire: Display: <SOH>S88IPPxxxxxxxxxxxxxxx <SOH>I88IPP Computer: <SOH>s88IPPxxxxxxxxxxxxxxx <SOH>i88IPP Notes: PP - Communication Port Number 2. xxxxxxxxxxxxxxx - IP Address with dotted-decimal notation For Setup Changes to take effect this command must be followed by 88Y Typical Response Message, Display Format: <SOH>...
Page 508
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Serial Command Port Command Format: Inquire: Display: <SOH>S88JPPxxxxx <SOH>I88JPP Computer: <SOH>s88JPPxxxxx <SOH>i88JPP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> I88J00 JAN 22, 2007 3:16 PM SERIAL COMMAND PORT COMM...
Page 509
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Static Subnet Mask Command Format: Inquire: Display: <SOH>S88KPPxxxxxxxxxxxxxxx <SOH>I88KPP Computer: <SOH>s88KPPxxxxxxxxxxxxxxx <SOH>i88KPP Notes: PP - Communication Port Number 2. xxxxxxxxxxxxxxx - IP Address with dotted-decimal notation For Setup Changes to take effect this command must be followed by 88Y Typical Response Message, Display Format: <SOH>...
Page 510
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Static Gateway IP Command Format: Inquire: Display: <SOH>S88LPPxxxxxxxxxxxxxxx <SOH>I88LPP Computer: <SOH>s88LPPxxxxxxxxxxxxxxx <SOH>i88LPP Notes: PP - Communication Port Number 2. xxxxxxxxxxxxxxx - IP Address with dotted-decimal notation For Setup Changes to take effect this command must be followed by 88Y Typical Response Message, Display Format: <SOH>...
Page 511
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set SSH Port Command Format: Inquire: Display: <SOH>S88MPPxxxxx <SOH>I88MPP Computer: <SOH>s88MPPxxxxx <SOH>i88MPP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> I88M00 JAN 22, 2007 3:16 PM SSH PORT COMM...
Page 512
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set HTTP Port Command Format: Inquire: Display: <SOH>S88NPPxxxxx <SOH>I88NPP Computer: <SOH>s88NPPxxxxx <SOH>i88NPP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> I88N00 JAN 22, 2007 3:16 PM HTTP PORT COMM...
Page 513
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set HTTPS Port Command Format: Inquire: Display: <SOH>S88OPPxxxxx <SOH>I88OPP Computer: <SOH>s88OPPxxxxx <SOH>i88OPP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> I88O00 JAN 22, 2007 3:16 PM HTTPS PORT COMM...
Page 514
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Host Name Command Format: Inquire: Display: <SOH>S88Pppxxxxxxxxxxxxxxx <SOH>I88Ppp Computer: <SOH>s88Pppxxxxxxxxxxxxxxx <SOH>i88Ppp Notes: pp - Communication Port Number 2. xxxxxxxxxxxxxxx - Host Name (30 Chars Max). The Host Name is not a Fully Qualified Domain Name.
Page 515
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Static Primary DNS Server Command Format: Inquire: Display: <SOH>S88QPPxxxxxxxxxxxxxxx <SOH>I88QPP Computer: <SOH>s88QPPxxxxxxxxxxxxxxx <SOH>i88QPP Notes: PP - Communication Port Number 2. xxxxxxxxxxxxxxx - IP Address with dotted-decimal notation For Setup Changes to take effect this command must be followed by 88Y Typical Response Message, Display Format:...
Page 516
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Static Secondary DNS Server Command Format: Inquire: Display: <SOH>S88RPPxxxxxxxxxxxxxxx <SOH>I88RPP Computer: <SOH>s88RPPxxxxxxxxxxxxxxx <SOH>i88RPP Notes: PP - Communication Port Number 2. xxxxxxxxxxxxxxx - IP Address with dotted-decimal notation For Setup Changes to take effect this command must be followed by 88Y Typical Response Message, Display Format:...
Page 517
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get MAC Address Command Format: Display: <SOH>I88SPP Computer: <SOH>i88SPP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> I88S00 JAN 22, 2007 3:16 PM MAC ADDRESS COMM LOCATION MAC ADDRESS...
Page 518
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Default Gateway Command Format: Inquire: Display: <SOH>S88TPPf <SOH>I88TPP Computer: <SOH>s88TPPf <SOH>i88TPP Notes: PP - Communication Port Number f - Default Gateway 0=No 1=Yes - For Setup Changes to take effect, this command must be followed by 88Y Typical Response Message, Display Format: <SOH>...
Page 519
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get Subnet Mask Command Format: Display: <SOH>I88UPP Computer: <SOH>i88UPP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> I88U00 JAN 22, 2007 3:16 PM SUBNET MASK COMM LOCATION SUBNET MASK...
Page 520
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get Gateway IP Command Format: Display: <SOH>I88VPP Computer: <SOH>i88VPP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> I88V00 JAN 22, 2007 3:16 PM GATEWAY IP COMM LOCATION GATEWAY IP...
Page 521
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get Primary DNS Server Command Format: Display: <SOH>I88WPP Computer: <SOH>i88WPP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> I88W00 JAN 22, 2007 3:16 PM PRIMARY DNS SERVER COMM LOCATION...
Page 522
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get Secondary DNS Server Command Format: Display: <SOH>I88XPP Computer: <SOH>i88XPP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> I88X00 JAN 22, 2007 3:16 PM SECONDARY DNS SERVER COMM LOCATION...
Page 523
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: TCP/IP Commit Setup Command Format: Display: <SOH>S88YPP149 Computer: <SOH>S88YPP149 Notes: PP - Communication Port Number 149 - code must be sent to confirm the command Typical Response Message, Display Format: <SOH>...
Page 524
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set TCP/IP DIM Port Command Format: Inquire: Display: <SOH>S88ZPPxxxxx <SOH>I88ZPP Computer: <SOH>s88ZPPxxxxx <SOH>i88ZPP Notes: PP - Communication Port Number Typical Response Message, Display Format: <SOH> S88Z00 JAN 22, 2007 3:16 PM TCP/IP DIM PORT COMM...
Page 525
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Accuchart Calibration Restart Command Format: Inquire: Display: <SOH>S891TT149 <SOH>I891TT Computer: <SOH>s891TT149 <SOH>i891TT Notes: TT - Tank Number (valid only for single tank) 149 - Verification code must be sent to confirm the command Typical Response Message, Display Format: <SOH>...
Page 526
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Acknowledge Tank Event Ready Status Command Format: Inquire: Display: <SOH>S893TT149 <SOH>I893TT Computer: <SOH>s893TT149 <SOH>i893TT Notes: TT - Tank Number (decimal) 149 - Verification code must be sent to confirm the command Typical Response Message, Display Format: <SOH>...
Page 527
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Set Accuchart Calibration Stop Command Format: Inquire: Display: <SOH>S894TT149 <SOH>I894TT Computer: <SOH>s894TT149 <SOH>i894TT Notes: TT - Tank Number (valid only for single tank) 149 - Verification code must be sent to confirm the command Typical Response Message, Display Format: <SOH>...
Page 528
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: Set Email Relay Command Format: Inquire: Display: <SOH>S89A00f <SOH>I89A00 Computer: <SOH>s89A00f <SOH>i89A00 Typical Response Message, Display Format: <SOH> S89A00 MAR 29, 2011 6:27 PM EMAIL RELAY:ENABLED <ETX> Typical Response Message, Computer Format: <SOH>s89A00YYMMDDHHmmf&&CCCC<ETX>...
Page 529
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: Set Email Sender Address Command Format: Inquire: Display: <SOH>S89B00aaaaa..aaaaa <SOH>I89B00 Computer: <SOH>s89B00aaaaa..aaaaa <SOH>i89B00 Typical Response Message, Display Format: <SOH> I89B00 MAR 29, 2011 6:27 PM EMAIL SENDER ADDRESS johndoe@veeder.com <ETX>...
Page 530
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: Set Relayhost/Smarthost Command Format: Inquire: Display: <SOH>S89C00aaaaa..aaaaa <SOH>I89C00 Computer: <SOH>s89C00aaaaa..aaaaa <SOH>i89C00 Typical Response Message, Display Format: <SOH> I89C00 MAR 29, 2011 6:27 PM Relayhost/Smarthost anywhere.com <ETX> Typical Response Message, Computer Format: <SOH>i89C00YYMMDDHHmmnnnaaaaa...aaaaa&&CCCC<ETX>...
Page 531
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: Set Sender Hostname Command Format: Inquire: Display: <SOH>S89D00aaaaa..aaaaa <SOH>I89D00 Computer: <SOH>s89D00aaaaa..aaaaa <SOH>i89D00 Typical Response Message, Display Format: <SOH> I89D00 MAR 29, 2011 6:27 PM Sender Hostname Tls450@veeder.com <ETX> Typical Response Message, Computer Format: <SOH>i89D00YYMMDDHHmmnnnaaaaa...aaaaa&&CCCC<ETX>...
Page 532
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Get Printer Setup and Status Command Format: Display: <SOH>I8CG00 Computer: <SOH>i8CG00 Typical Response Message, Display Format: <SOH> I8CG00 MAR 26, 2011 1:54 PM PRINTER SETUP - STATUS - - - - - - - - - - - - NAME: TLSIntegralPrinter CONFIGURED: True...
Page 533
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 8CG Notes: (Continued) Typical Response Message, Computer Format: <SOH>i8CG00YYMMDDHHmmNNaaa...aaafEMMmmm...mmmTNPHGNJDCSSsss...sss... NNaaa...aaafEMMmmm...mmmTNPHGNJDCSSsss...sss&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time NN – Number of characters to follow for Name (Hex) a...a - Name (ASCII characters [20h-7Eh]) f - Configured 0=False 1=True...
Page 534
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Push Site ID Command Format: Display: This command is sent out by the TLS-450 Computer: Typical Response Message, Display Format: Computer format only Typical Response Message, Computer Format: <SOH>iD0100YYMMDDHHmmDDDDDD000000&&CCCC<ETX>...
Page 535
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Server Heartbeat Command Format: Display: Computer: <SOH>iD0200cccc Typical Response Message, Display Format: Computer format only Typical Response Message, Computer Format: <SOH>iD0200YYMMDDHHmmcccc&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time cccc - Heartbeat Characters (ASCII characters [20h-7Eh]) &&...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.4 DIAGNOSTIC REPORTS 7.4.1 SYSTEM DIAGNOSTIC REPORTS Function Code: (Obsolete V2) Version 1 Function Type: System Revision Level Report Command Format: Display: <SOH>I90200 (Obsolete for Display Format) Computer: <SOH>i90200 (CONTAINS HARDCODED STRING FOR INFORM) Typical Response Message, Display Format: <SOH>...
Page 537
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: System Revision Level Report II Command Format: Display: <SOH>I90500 (Obsolete for Display Format) Computer: <SOH>i90500 (CONTAINS HARDCODED STRING FOR INFORM) Typical Response Message, Display Format: <SOH> I90500 JUL 29, 1997 9:08 AM SOFTWARE REVISION LEVEL VERSION 115.00 TEST #05...
Page 538
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 905 Notes: (Continued) vv - Language 00=English/Spanish 01=English/French 02=English/German 03=English/Swedish 04=English/Portuguese 05=English/Polish 06=English/Finnish 07=English/Japanese 08=English/Greek 09=English/Russian 10=English/Turkish 11=English/Dutch 12=English/Italian 99=English only rrr - Revision level (eg revision "AX1") YY.MM.DD.HH.mm - Date and time of software creation nn - number of 2 byte values to follow (Hex) AA - PERIODIC IN-TANK TESTS (00=DISABLE, 01=ENABLE) BB - ANNUAL IN-TANK TESTS (00=DISABLE, 01=ENABLE)
Page 539
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get “About Screen” Information Command Format: Display: <SOH>I90700 Computer: <SOH>i90700 Typical Response Message, Display Format: <SOH> I90700 JAN 22, 2007 3:24 PM Software: Part# 342002.A.121.2 CREATED: Feb 21 2010 15:58:17 Serial Hardware Description Numbers...
Page 540
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code 907 Notes: (Continued) 5=CustomOnBoardHelp, 6=CustomAlarms, 7=CustomDashboard, 8=ContinuousStatisticalLeakDetection, 9=UltimateTestingLeakDetectionForDPLLD, 0A=RiskManagementLeakDetectionForDPLLD, 0B=BaseComplianceLineLeakDetectionForDPLLD, 0C=Business Inventory Reconciliation 0D=AccuChartII, 0E=ExtendedStorageL1, 0F=ExtendedStorageL2, 10=3.0 GPH Testing 11=ATG Functionality 12=DataLogger Functionality 13=Statistical Leak Detection && - Data Termination Flag CCCC - Message Checksum Part No.
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.4.2 IN-TANK DIAGNOSTIC REPORTS Function Code: Version 1 Function Type: Probe Type and Serial Number Command Format: Display: <SOH>IA01TT Computer: <SOH>iA01TT Typical Response Message, Display Format: <SOH> IA01TT JAN 22, 2009 3:25 PM TYPE CODE LENGTH SERIAL NO.
Page 542
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Probe Reference Distance Diagnostic Command Format: Display: <SOH>IA07TT Computer: <SOH>iA07TT Typical Response Message, Display Format: <SOH> IA07TT JAN 22, 1996 3:25 PM PROBE 1 REGULAR TANK REGULAR UNLEADED MAG7 PROBE SERIAL NUMBER 0000123456...
Page 543
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Probe Diagnostics - General Command Format: Display: <SOH>IA0XPP Computer: <SOH>iA0XPP Typical Response Message, Display Format: <SOH> IA0XTT JAN 22, 2007 3:25 PM PROBE 1: - TANK Serial Date Type Code Length...
Page 544
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Probe Last Sample Buffers Command Format: Display: <SOH>IA10TT Computer: <SOH>iA10TT Typical Response Message, Display Format: <SOH> IA10TT JAN 22, 1996 3:25 PM TANK REGULAR UNLEADED NUMBER OF SAMPLES=44520 694.000 8587.000 8587.000...
Page 545
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: MAG Probe Option Table Command Format: Display: <SOH>IA14PP Computer: <SOH>iA14PP Typical Response Message, Display Format: <SOH> IA14PP 1, 2000 8:15 AM MAG PROBE OPTIONS TABLE LEAK LEAK LEAK TEMP WATER --------------------------------------------...
Page 546
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Diagnostic Printout Command Format: Display: <SOH>IA1500 Computer: <SOH>iA1500 Typical Response Message, Display Format: <SOH> IA1500 3, 2002 8:07 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..
Page 547
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code A15 Notes: (Continued) Typical Response Message, Computer Format: <SOH>iA15TTYYMMDDHHmmTTppppssssssllllllllddddYYMMDDHHmm ggggggggzzzzoonnnnNNcccccccc...cccccccc rrrrrrrruuuuuuuueeeeeeeeYYMMDDHHmm AAaaaaaaaa...aaaaaaaa YYMMDDhhhhhhhhYYMMDDkkkkkkkk... TTppppssssssllllllllddddYYMMDDHHmm ggggggggzzzzoonnnnNNcccccccc...cccccccc rrrrrrrruuuuuuuueeeeeeeeYYMMDDHHmm AAaaaaaaaa...aaaaaaaa YYMMDDhhhhhhhhYYMMDDkkkkkkkk&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=all) pppp - Probe Type (Hex) ssssss - Serial Number (Decimal) llllllll - Probe Length (ASCII Hex IEEE float) dddd - Date Code (Hex)
Page 548
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Probe Communication Command Format: Display: <SOH>IA17PP Computer: <SOH>iA17PP Typical Response Message, Display Format: <SOH> IA17PP MAR 26, 2007 1:50 PM PROBE DIAGNOSTIC – COMMUNICATION REPORT -------------------------------------------------------------------- PROBE Probe Label (PROBE 1) TANK Samples Samples Comm...
Page 549
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: Probe Diagnostic Printout Command Format: Display: <SOH>IA1800 Computer: <SOH>iA1800 Typical Response Message, Display Format: <SOH> IA1800 08-28-08 14:13 Diagnostics SOFTWARE REVISION TANK PROBE TYPE MAG1 SERIAL NUMBER 168809 PROBE ID 0XC000 PROBE LENGTH...
Page 550
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code A18 Notes: (Continued) COUNTS 17 017460 COUNTS 18 044370 OPTIONS CODE 0X0000 <ETX> Typical Response Message, Computer Format: <SOH>iA18TTYYMMDDHHmmTTppppsssssszzzzllllllllggggggggSSSSSSSS rrrrrrruuuuuuuuYYMMDDhhhhhhhhYYMMDDkkkkkkkk AAaaaaaaaa...aaaaaaaaBBbbbbbbbb...bbbbbbbb NNcccccccc...ccccccccKKKKKKKK TTppppsssssszzzzllllllllggggggggSSSSSSSS rrrrrrruuuuuuuuYYMMDDhhhhhhhhYYMMDDkkkkkkkk AAaaaaaaaa...aaaaaaaaBBbbbbbbbb...bbbbbbbb NNcccccccc...ccccccccKKKKKKK&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=all) pppp - Probe Type (Hex) ssssss - Serial Number (Decimal)
Page 551
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Probe Leak Test Flags - Present Test Command Format: Display: <SOH>IA20TT Computer: <SOH>iA20TT Typical Response Message, Display Format: <SOH> IA20TT JAN 28, 1995 10:15 AM TANK REGULAR UNLEADED PRESENT LEAK TEST ANALYSIS REPORT 0.1 GAL/HR FLAGS: 0.2 GAL/HR FLAGS:...
Page 552
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Probe Leak Test Flags - Stored Test Command Format: Display: <SOH>IA21TT Computer: <SOH>iA21TT Typical Response Message, Display Format: <SOH> IA21TT JAN 28, 1995 10:15 AM TANK REGULAR UNLEADED STORED LEAK TEST ANALYSIS REPORT 0.1 GAL/HR FLAGS: 0.2 GAL/HR FLAGS:...
Page 553
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Probe Leak Test Flags - Gross Test Command Format: Display: <SOH>IA22TT Computer: <SOH>iA22TT Typical Response Message, Display Format: <SOH> IA22TT APR 14, 1995 9:05 AM TANK REGULAR UNLEADED GROSS LEAK TEST ANALYSIS REPORT GROSS LEAK TEST FLAGS: TANK...
Page 554
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: CSLD Diagnostics: Rate Table Command Format: Display: <SOH>IA51TT Computer: <SOH>iA51TT Typical Response Message, Display Format: <SOH> IA51TT JAN 22, 1996 3:26 PM CSLD DIAGNOSTICS: RATE TABLE T 1:REGULAR UNLEADED TIME ST LRT AVTMP TPTMP BDTMP TMRT DSPNS...
Page 555
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: CSLD Diagnostics: Rate Test Command Format: Display: <SOH>IA52TT Computer: <SOH>iA52TT Typical Response Message, Display Format: <SOH> IA52TT JAN 22, 1996 3:27 PM CSLD DIAGNOSTICS: RATE TEST DATE LRATE INTVL ST AVLRTE C3 FDBK ACPT THPUT EVAP 9601220417 -0.024...
Page 556
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: CSLD Diagnostics: Volume History Table Command Format: Display: <SOH>IA53TT Computer: <SOH>iA53TT Typical Response Message, Display Format: <SOH> IA53TT MAR 26, 1996 1:48 PM CSLD DIAGNOSTICS: VOLUME TABLE T 1:REGULAR UNLEADED LAST HOUR=229957 3141.9 3297.9...
Page 557
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: 30-Second Inventory Samples Command Format: Display: <SOH>IA54TT Computer: <SOH>iA54TT Typical Response Message, Display Format: <SOH> IA54TT MAR 26, 1996 1:48 PM 30-SECOND INVENTORY SAMPLES T 1:REGULAR UNLEADED TIME SMPLS TCVOL HEIGHT...
Page 558
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: CSLD Diagnostics: Leak Test Status Command Format: Display: <SOH>IA55TT Computer: <SOH>iA55TT Typical Response Message, Display Format: <SOH> IA55TT MAR 26, 1996 1:49 PM CSLD DIAGNOSTICS: LEAK TEST STATUS TANK LABEL TEST STATUS...
Page 559
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: CSLD Monthly Report Command Format: Display: <SOH>IA56TTt Computer: <SOH>iA56TTt NOTE: The most current record from the previous month (if available) will be returned if a record doesn’t exist for the current month. Typical Response Message, Display Format: <SOH>...
Page 560
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Tank Test Diagnostics - CSLD Monthly Report Command Format: Display: <SOH>IA57TTRRyymmddhhmmYYMMDDHHMMnnn Computer: <SOH>iA57TTRRyymmddhhmmYYMMDDHHMMnnn Notes: TT - Device Number (Decimal, 00=all) RR - Report Type (Report Type should always be given. The rest of the parameters are optional following the rules below.) 00=CSLD Monthly Report (for CSLD information for specified time period)
Page 561
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code A57: (Continued) NOTE: The most current record from a previous date (if available) will be returned if a record doesn’t exist for the selected date range. Typical Response Message, Display Format: <SOH> IA57TT OCT 25, 2000 10:00 AM Selected Range:...
Page 562
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: CSLD Diagnostics: Moving Average Table Command Format: Display: <SOH>IA58TT Computer: <SOH>iA58TT Typical Response Message, Display Format: <SOH> IA58TT MAR 26, 1996 1:48 PM CSLD DIAGNOSTICS: AGGREGATE ATG DATA QUEUE T 1:REGULAR UNLEADED SMPL AGGREG...
Page 563
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: HRM Diagnostic Report Command Format: Display: <SOH>IA61TT Computer: <SOH>iA61TT Typical Response Message, Display Format: <SOH> IA61TT MAR 26, 2011 1:48 PM T 1:REGULAR UNLEADED TIME STAMP ENDTEMP ENDVOL SALES STAT HR VAR 9707240757...
Page 564
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: HRM Daily History Report Command Format: Display: <SOH>IA62TT Computer: <SOH>iA62TT Typical Response Message, Display Format: <SOH> IA62TT MAR 26, 2011 1:48 PM DAILY HRM HISTORY T 1:REGULAR UNLEADED DATE/TIME RECORDS STATUS...
Page 565
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 4 Function Type: Extended HRM Diagnostic Report Command Format: Display: <SOH>IA63TT Computer: <SOH>iA63TT Typical Response Message, Display Format: <SOH> IA63TT MAR 26, 2011 1:48 PM T 1:REGULAR UNLEADED TIME STAMP ENDTEMP ENDVOL SALES STAT HR VAR...
Page 566
240 records will be returned. Typical Response Message, Display Format: <SOH> IA64TT APR 20, 2011 1:48 PM TLS_450 UST VEEDER-ROOT TEST LAB 125 POWDER FOREST DR SIMSBURY, CT 06070 Volume=GALLONS Height=INCHES HRM Diagnostic Report Temp=FAHRENHEIT Selected Range:...
Page 567
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code A64 Notes: (Continued) Typical Response Message, Computer Format: <SOH>iA64TTYYMMDDHHmmTTpRRRRYYMMDDHHmmFFEEEEEEEESSSSSSSSVVVVVVVV... TTpRRRRYYMMDDHHmmFFEEEEEEEESSSSSSSSVVVVVVVV&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=All Tanks) p – Product Code (ASCII character [20h-7Eh]) RRRR – Number of Records to follow (ASCII hex) YYYYMMDDHHmm –...
Page 568
31 records will be returned. Typical Response Message, Display Format: <SOH> IA65TT MAR 26, 2011 1:48 PM TLS_450 UST VEEDER-ROOT TEST LAB 125 POWDER FOREST DR SIMSBURY, CT 06070 Volume=GALLONS Height=INCHES DAILY HRM HISTORY Temp=FAHRENHEIT T 1:REGULAR UNLEADED...
Page 569
240 records will be returned. Typical Response Message, Display Format: <SOH> IA66TT APR 20, 2011 1:48 PM TLS_450 UST VEEDER-ROOT TEST LAB 125 POWDER FOREST DR SIMSBURY, CT 06070 Volume=GALLONS Height=INCHES Extended HRM Diagnostic Report Temp=FAHRENHEIT Selected Range:...
Page 570
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code A66 Notes: (Continued) Typical Response Message, Computer Format: <SOH>iA66TTYYMMDDHHmmTTpRRRRYYMMDDHHmmFFNNEEEEEEEESSSSSSSSVVVVVVVVTTTTTTTT... TTpRRRRYYMMDDHHmmFFNNEEEEEEEESSSSSSSSVVVVVVVV TTTTTTTT&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - Tank Number (Decimal, 00=All Tanks) p – Product Code (ASCII character [20h-7Eh]) RRRR –...
Page 571
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Accuchart Data Sufficiency Command Format: Display: <SOH>IA71TT Computer: <SOH>iA71TT Notes: TT - Tank Number [01..32], (Decimal, 00=all) Typical Response Message, Display Format: <SOH> IA71TT JAN 24, 2009 2:52 PM ACCUCHART DATA SUFFICIENCY |--SUFFICIENCY--| DAYS...
Page 572
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Accuchart Data Sufficiency Histogram Command Format: Display: <SOH>IA72TT Computer: <SOH>iA72TT Notes: TT - Tank Number [01..32], (Decimal, 00=all) Typical Response Message, Display Format: <SOH> IA72TT JAN 24, 2009 2:52 PM TANK nn ACCUCHART DATA SUFFICIENCY HISTOGRAM HEIGHT%...
Page 573
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Force Accuchart Calibration Command Format: Inquire: Display: <SOH>SA73TT149 <SOH>IA73TT Computer: <SOH>sA73TT149 <SOH>iA73TT Notes: TT - Tank Number [01..32], (Decimal, 00=all) Set command forces Accuchart to attempt to calibrate Typical Response Message, Display Format: <SOH>...
Page 574
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Accuchart Calibration Feedback Report Command Format: Display: <SOH>IA74TT Computer: <SOH>iA74TT Notes: TT - Tank Number [01..32], (Decimal, 00=all) Typical Response Message, Display Format: <SOH> IA74TT JAN 24, 2009 2:52 PM ACCUCHART FEEDBACK REPORT TANK...
Page 575
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Accuchart Delivery Instructions Command Format: Display: <SOH>IA75TT Computer: <SOH>iA75TT Notes: TT - Tank Number [01..32], (Decimal, 00=all) Typical Response Message, Display Format: <SOH> IA75TT JAN 24, 2009 2:52 PM ACCUCHART DELIVERY INSTRUCTIONS TANK DATE...
Page 576
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Get Application Log Information Command Format: Display: <SOH>IA76TTYYMMDDyymmdd Computer: <SOH>iA76TTYYMMDDyymmdd Notes: TT - Tank Number [01..32], (Decimal, 00=all) YYMMDD - Start Date (optional) yymmdd - End date (optional) Typical Response Message, Display Format: <SOH>...
Page 577
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Power Outage Report Command Format: Display: <SOH>IA91TT Computer: <SOH>iA91TT Typical Response Message, Display Format: <SOH> IA91TT JAN 24, 1996 2:56 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..
Page 578
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Power Outage Inventory Report Date/Time Based Command Format: Display: <SOH>IA9GTTyymmddYYMMDDnnn Computer: <SOH>iA9GTTyymmddYYMMDDnnn Notes: yymmdd - Starting date (000000 = no starting date) YYMMDD - Ending Date (000000 = no ending date)) nnn - Maximum Records [001…999] (10 = default) (decimal) If no data is entered or zeros are entered for the starting date, ending date and maximum records, the last 10 records...
Page 579
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Power Outage Delivery Diagnostic Report Date/Time Based Command Format: Display: <SOH>IA9HTTyymmddYYMMDDnnn Computer: <SOH>iA9HTTyymmddYYMMDDnnn Notes: yymmdd - Starting date (000000 = no starting date) YYMMDD - Ending Date (000000 = no ending date)) nnn - Maximum Records [001…999] (10 = default) (decimal) If no data is entered or zeros are entered for the starting date, ending date and maximum records, the last 10 records...
Page 580
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Power Reset History Report Date/Time Based Command Format: Display: <SOH>IA9J00yymmddYYMMDDnnn Computer: <SOH>iA9J00yymmddYYMMDDnnn Notes: yymmdd - Starting date (000000 = no starting date) YYMMDD - Ending Date (000000 = no ending date)) nnn - Maximum Records [001…999] (10 = default) (decimal) If no data is entered or zeros are entered for the starting date, ending date and maximum records, the last 10 records...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.4.3 SENSOR DIAGNOSTIC REPORTS Function Code: Version 1 Function Type: Liquid Sensor Diagnostic Report Command Format: Display: <SOH>IB01SS Computer: <SOH>iB01SS Typical Response Message, Display Format: <SOH> IB01SS JAN 24, 1996 2:56 PM SENSOR DIAGNOSTIC – LIQUID SENSOR INFORMATION REPORT SINGLE SENSOR SAMPLE SENSOR...
Page 582
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Vapor Sensor Diagnostic Report Command Format: Display: <SOH>IB06SS Computer: <SOH>iB06SS Typical Response Message, Display Format: <SOH> IB06SS JAN 24, 1996 2:56 PM SENSOR DIAGNOSTIC – VAPOR SENSOR INFORMATION REPORT SINGLE SENSOR SAMPLE VAPOR...
Page 583
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Vapor Sensor Concentration (PPM) Report Command Format: Display: <SOH>IB07SS Computer: <SOH>iB07SS Typical Response Message, Display Format: <SOH> IB07SS JAN 24, 1996 2:56 PM VAPOR DIAGNOSTIC REPORT - VAPOR CONCENTRATION SENSOR <ETX>...
Page 584
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Groundwater Sensor Diagnostic Report Command Format: Display: <SOH>IB11SS Computer: <SOH>iB11SS Typical Response Message, Display Format: <SOH> IB11SS JAN 28, 1995 10:16 AM SENSOR DIAGNOSTIC – GROUNDWATER SENSOR INFORMATION REPORT SINGLE SENSOR SAMPLE SENSOR...
Page 585
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Ground Temperature Sensor Diagnostic Report Command Format: Display: <SOH>IB21SS Computer: <SOH>iB21SS Typical Response Message, Display Format: <SOH> IB21SS JAN 24, 1996 2:56 PM GROUNDTEMP DIAGNOSTIC REPORT SAMPLE HIGH SENSOR COUNTER VALUE 1086...
Page 586
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: MAG Sensor Diagnostic Report Command Format: Display: <SOH>IB33SS Computer: <SOH>iB33SS Typical Response Message, Display Format: <SOH> IB33SS JAN 22, 2003 3:06 PM MAG SENSOR DIAGNOSTIC REPORT Sensor 1: T1 SUMP TOTAL HT 15.0 IN.
Page 587
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: MAG Sensor Comm Data Command Format: Display: <SOH>IB3AQQ Computer: <SOH>iB3AQQ Typical Response Message, Display Format: <SOH> IB3AQQ MAR 26, 1996 1:47 PM MAG Sensor Diagnostic Report - Communication Samples Samples Parity...
Page 588
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: MAG Sensor Type and Serial Number Command Format: Display: <SOH>IB3BSS Computer: <SOH>iB3BSS Typical Response Message, Display Format: <SOH> IB3B01 MAY 11, 2007 5:36 PM MAG SENSOR TYPE AND SERIAL NUMBER SENSOR LABEL TYPE...
Page 589
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: MAG Sensor Constant Data Command Format: Display: <SOH>IB3CSS Computer: <SOH>IB3CSS Typical Response Message, Display Format: <SOH> IB3CSS 1, 2000 8:15 AM MAG SENSOR DIAGNOSTIC REPORT - CONSTANTS Sensor 1: SUMP UNLEADED MAG SENSOR SERIAL NUMBER 123456...
Page 590
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: MAG Sensor Last Sample Diagnostic (Hex Format) Command Format: Display: <SOH>IB3DSS Computer: <SOH>IB3DSS Typical Response Message, Display Format: <SOH> IB3DSS JAN 22, 2003 3:25 PM MAG Sensor Diagnostic Report - Channel Data Sensor 1: Serial Number: 3534 Time: DEC 30, 2007...
Page 591
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: MAG Sensor Last Sample Diagnostic (Decimal Format) Command Format: Display: <SOH>IB3ESS Computer: <SOH>IB3ESS Typical Response Message, Display Format: <SOH> IB3ESS JAN 22, 2003 3:25 PM MAG Sensor Diagnostic Report - Channel Data Sensor 1: Serial Number: 3534 Time: DEC 30, 2007...
Page 592
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Type A Sensor (2 Wire CL) Diagnostic Report Command Format: Display: <SOH>IB41SS Computer: <SOH>iB41SS Typical Response Message, Display Format: <SOH> IB41SS MAR 26, 1996 1:45 PM SENSOR DIAGNOSTIC – 2-WIRE CL SENSOR INFORMATION REPORT SINGLE SENSOR SAMPLE SENSOR...
Page 593
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Type B Sensor (3 Wire CL) Diagnostic Report Command Format: Display: <SOH>IB46SS Computer: <SOH>iB46SS Typical Response Message, Display Format: <SOH> IB46SS JAN 28, 1995 10:16 AM SENSOR DIAGNOSTIC – 3-WIRE CL SENSOR INFORMATION REPORT SINGLE SENSOR SAMPLE SENSOR...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.4.4 LINE LEAK DIAGNOSTIC REPORTS B61 (obsolete V3E use B6G) Function Code: Version 1 Function Type: LPR Sensor General Report Command Format: Display: <SOH>IB61QQ Computer: <SOH>iB61QQ Typical Response Message, Display Format: <SOH> IB61QQ MAR 26, 1996 1:47 PM LPR Sensor Diagnostic Report - General Serial...
Page 595
Serial Interface Manual TLS4/TLS-450 Monitoring Systems B62 (obsolete V3E use B6H) Function Code: Version 1 Function Type: LPR Sensor Constants Report Command Format: Display: <SOH>IB62QQ Computer: <SOH>iB62QQ Typical Response Message, Display Format: <SOH> IB62QQ MAR 26, 1996 1:47 PM LPR Sensor Diagnostic Report - Constants Serial Firmware Date...
Page 596
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: LPR Sensor Comm Data Command Format: Display: <SOH>IB63QQ Computer: <SOH>iB63QQ Typical Response Message, Display Format: <SOH> IB63QQ MAR 26, 1996 1:47 PM LPR Sensor Diagnostic Report - Communication Samples Samples Parity...
Page 597
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: LPR Sensor Channel Data Command Format: Display: <SOH>IB64QQ Computer: <SOH>iB64QQ Typical Response Message, Display Format: <SOH> IB64QQ MAR 26, 1996 1:47 PM LPR Sensor Diagnostic Report - Channel Data Sensor 1: Line P Sensor 1 Serial Number: 000114 Time: Jun 24, 2008 12:20 PM...
Page 598
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: LPR Sensor Channel Data (Decimal Format) Command Format: Display: <SOH>IB65QQ Computer: <SOH>iB65QQ Typical Response Message, Display Format: <SOH> IB64QQ MAR 26, 1996 1:47 PM LPR Sensor Diagnostic Report - Channel Data Sensor 1: Line P Sensor 1 Serial Number: 000114 Time: Jun 24, 2008 12:20 PM...
Page 599
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: LPR Sensor General Report Command Format: Display: <SOH>IB6GQQ Computer: <SOH>iB6GQQ Typical Response Message, Display Format: <SOH> IB6GQQ MAR 26, 1996 1:47 PM LPR Sensor Diagnostic Report - General Serial Type Status...
Page 600
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 3 Function Type: LPR Sensor Constants Report Command Format: Display: <SOH>IB6HQQ Computer: <SOH>iB6HQQ Typical Response Message, Display Format: <SOH> IB6HQQ MAR 26, 1996 1:47 PM LPR Sensor Diagnostic Report - Constants Serial Firmware Date...
Page 601
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Pump Relay Monitor Diagnostic Command Format: Display: <SOH>IB72QQ Computer: <SOH>iB72QQ Typical Response Message, Display Format: <SOH> IB72QQ JUN 22, 2014 3:12 PM PUMP RELAY MONITOR DIAGNOSTIC PUMP PUMP RELAY STUCK DEVICE LABEL...
Page 602
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Profile Line Test Command Format: Display: <SOH>IB7BQQ Computer: <SOH>iB7BQQ Typical Response Message, Display Format: <SOH> IB7BQQ JUL 15, 2001 1:27 PM PRESSURE LINE LEAK PROFILE LINE TEST Q 1:REGULAR UNLEADED LAST PROFILE LINE TEST: NOV 15, 2001 10:15 AM BULK MODULUS:...
Page 603
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code B7B Notes: (Continued) Typical Response Message, Computer Format: <SOH>iB7BQQYYMMDDHHmmQQaYYMMDDHHmmttNNFFFFFFFF...FFFFFFFF... QQaYYMMDDHHmmttNNFFFFFFFF...FFFFFFFF&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time QQ - Pressure Line Leak sensor number (Decimal, 00=All) a - Valid profile line test flag 0=profile line test invalid 1=profile line test valid YYMMDDHHmm - Date and Time of Last Profile Line Test...
Page 604
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Pressure Offset Test Command Format: Display: <SOH>IB7CQQ Computer: <SOH>iB7CQQ Typical Response Message, Display Format: <SOH> IB7CQQ 1, 2000 6:27 PM PRESSURE LINE LEAK PRESSURE OFFSET TEST Q 1:REGULAR UNLEADED LAST PRESSURE OFFSET TEST: +2.5 PSI 1, 1999...
Page 605
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Pressure Offset Monitor Report Command Format: Display: <SOH>IB7EQQ Computer: <SOH>iB7EQQ Typical Response Message, Display Format: <SOH> IB7EQQ 1, 2000 2:56 PM PRESSURE LINE LEAK PRESSURE OFFSET MONITORS REPORT Q 1:REGULAR UNLEADED P0: PASS LAST UPDATE:...
Page 606
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Diagnostic Report Command Format: Display: <SOH>IB81QQ Computer: <SOH>iB81QQ Typical Response Message, Display Format: <SOH> IB81QQ JAN 24, 1996 2:56 PM PRESSURE LINE LEAK DIAGNOSTIC REPORT LINE DISPENSING TEST STATUS...
Page 607
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak 3.00 GPH Test Diagnostic Command Format: Display: <SOH>IB87QQ Computer: <SOH>iB87QQ Typical Response Message, Display Format: <SOH> IB87QQ OCT 15, 1996 4:29 PM PRESSURE LINE LEAK DIAGNOSTIC REPORT Ln 1:PLLD NUMBER 1 3.0 TEST PASSES DATE/TIME...
Page 608
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak Mid-range Test Diagnostic Command Format: Display: <SOH>IB88QQ Computer: <SOH>iB88QQ Typical Response Message, Display Format: <SOH> IB88QQ 1, 1996 8:24 AM PRESSURE LINE LEAK DIAGNOSTIC REPORT Q 1:PLLD NUMBER 1 MID TEST PASSES DATE/TIME...
Page 609
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak 0.20 GPH Test Diagnostic Command Format: Display: <SOH>IB89QQ Computer: <SOH>iB89QQ Notes: For User Defined Pipe Types PUMP ON will be PMID Typical Response Message, Display Format: <SOH>...
Page 610
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Pressure Line Leak 0.10 GPH Test Diagnostic Command Format: Display: <SOH>IB8AQQ Computer: <SOH>iB8AQQ Notes: For User Defined Pipe Types PUMP ON will be PMID (Version 23) Typical Response Message, Display Format: <SOH>...
Page 611
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: No-Vent (No_Spike) Test Reports Command Format: Display: <SOH>IB8FQQ Computer: <SOH>iB8FQQ Typical Response Message, Display Format: <SOH> IB8FQQ JAN 24, 1996 2:52 PM PRESSURE LINE NO-VENT TEST REPORT LINE TEST ABORTS TOTAL TESTS Q 1:REGULAR UNLEADED...
Page 612
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: PLLD Last Test Result Command Format: Display: <SOH>IB8IQQ Computer: <SOH>iB8IQQ Typical Response Message, Display Format: <SOH> IB8IQQ 1, 2007 8:26 AM PRESSURE LINE LEAK DIAGNOSTIC LAST TEST RESULT Q 1:PLLD NUMBER 1 0.20 GAL/HR RESULT : JUL 10, 2007 9:33 AM...
Page 613
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: PLLD Diagnostic - Manual Test Command Format: Display: <SOH>IB8JQQ Computer: <SOH>iB8JQQ Typical Response Message, Display Format: <SOH> IB8JQQ 1, 2007 8:26 AM PLLD DIAGNOSTIC - MANUAL TEST LINE:LINE LABEL TEST STATUS 1:PRESSURE LLD #1 test aborted...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.4.5 RECONCILIATION DIAGNOSTIC REPORTS Function Code: Version 2 Function Type: MDIM Totalizer Report Command Format: Display: <SOH>IBA000 Computer: <SOH>iBA000 Typical Response Message, Display Format: <SOH> IBA000 4, 1995 6:25 AM MDIM TOTALIZER 0.000 0.000 0.000 0.000 <ETX>...
Page 615
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Get Reconciliation Status Command Format: Display: <SOH>ICA100 Computer: <SOH>iCA100 Typical Response Message, Display Format: <SOH> ICA100 1, 2009 8:26 AM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..STATION HEADER 4..
Page 616
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Reconciliation Diagnostics Report Command Format: Display: <SOH>ICA2PPyymmddYYMMDD Computer: <SOH>ICA2PPyymmddYYMMDD Notes: PP - Product Number (Decimal, 00=all) yymmdd - Starting Date (000000 = no starting date=first of the month) YYMMDD - Ending Date (000000 = no ending date=current date)
Page 617
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code CA2 Notes: (Continued) Typical Response Message, Computer Format: <SOH>iCA2PPYYMMDDHHmmPPYYMMDDHHmmMMMMMMMMVVVVVVVVNNRR... PPYYMMDDHHmmMMMMMMMMVVVVVVVVNNRR&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Number (Decimal, 00=All) YYMMDDHHmm - Date and Time MMMMMMMM - Meter Sales (ASCII Hex IEEE float) VVVVVVVV - Variance (ASCII Hex IEEE float) NN - Number of decimal Data Fields to follow (Hex) RR - Reasons (Decimal)
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.5 RECONCILIATION REPORTS Function Code: Version 2 Function Type: Basic Inventory Reconciliation Daily "Row" Report Command Format: Display: <SOH>IC01PPMMDD Computer: <SOH>iC01PPMMDD Notes: MMDD - Month and Day for Daily Report Typical Response Message, Display Format: <SOH>...
Page 619
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Basic Inventory Reconciliation Daily "Column" Report Command Format: Display: <SOH>IC0200MMDD Computer: <SOH>iC0200MMDD Notes: MMDD - Month and Day for Daily Report Typical Response Message, Display Format: <SOH> IC0200 MAR 26, 2009 1:43 PM STATION HEADER 1..
Page 620
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C02: (Continued) Typical Response Message, Computer Format: <SOH>iC02PPYYMMDDHHmmGGPPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... PPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time GG - Number of product Groupings to follow (Hex) PP - Product Number (Decimal, 00=All Products) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank numbers mapped to product YYMMDDHHmm - Opening Date and Time...
Page 621
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Basic Inventory Reconciliation Shift "Row" Report Command Format: Display: <SOH>IC03PPtt Computer: <SOH>iC03PPtt Notes: tt - Shift Type (01=Current, 02=Previous) Typical Response Message, Display Format: <SOH> IC03PP MAR 26, 2009 1:44 PM STATION HEADER 1..
Page 622
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Basic Inventory Reconciliation Shift "Column" Report Command Format: Display: <SOH>IC0400tt Computer: <SOH>iC0400tt Notes: tt - Shift Type (01=Current, 02=Previous) Typical Response Message, Display Format: <SOH> IC0400 MAR 26, 2009 1:44 PM STATION HEADER 1..
Page 623
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C04: (Continued) Typical Response Message, Computer Format: <SOH>iC04PPYYMMDDHHmmGGPPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... PPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time GG - Number of product Groupings to follow (Hex) PP - Product Number (Decimal, 00=All Products) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank numbers mapped to product YYMMDDHHmm - Opening Date and Time...
Page 624
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Basic Inventory Reconciliation Periodic "Row" Report Command Format: Display: <SOH>IC05PP Computer: <SOH>iC05PP Typical Response Message, Display Format: <SOH> IC05PP MAR 26, 2009 1:42 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 625
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C05: (Continued) Typical Response Message, Computer Format: <SOH>iC05PPYYMMDDHHmmPPnnTT...ddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... PPnnTT...ddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Number (Decimal, 00=All Products) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank numbers mapped to product dd - Number of reconciliation days to follow (Hex) YYMMDDHHmm - Opening Date and Time...
Page 626
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Basic Inventory Reconciliation Periodic "Column" Report Command Format: Display: <SOH>IC0600 Computer: <SOH>iC0600 Typical Response Message, Display Format: <SOH> IC0600 MAR 26, 2009 1:42 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
Page 627
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C06: (Continued) Typical Response Message, Computer Format: <SOH>iC06PPYYMMDDHHmmGGPPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... PPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time GG - Number of product Groupings to follow (Hex) PP - Product Number (Decimal, 00=All Products) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank numbers mapped to product YYMMDDHHmm - Opening Date and Time...
Page 628
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Basic Inventory Reconciliation Periodic "Row" Report (Current/Previous) Command Format: Display: <SOH>IC07PPtt Computer: <SOH>iC07PPtt Notes: PP - Product Number (00=all products) tt - Report type 00=Current Period 01=Previous Period Typical Response Message, Display Format: <SOH>...
Page 629
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C07: (Continued) Typical Response Message, Computer Format: <SOH>iC07PPYYMMDDHHmmPPnnTT...ddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... PPnnTT...ddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Number (Decimal, 00=All Products) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank numbers mapped to product dd - Number of reconciliation days to follow (Hex) YYMMDDHHmm - Opening Date and Time...
Page 630
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Basic Inventory Reconciliation Periodic "Column" Report (Current/Previous) Command Format: Display: <SOH>IC0800tt Computer: <SOH>iC0800tt Notes: tt - Report type 00=Current Period 01=Previous Period Typical Response Message, Display Format: <SOH> IC0800 MAR 26, 2009 1:42 PM...
Page 631
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C08: (Continued) Typical Response Message, Computer Format: <SOH>iC08PPYYMMDDHHmmGGPPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... PPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time GG - Number of product Groupings to follow (Hex) PP - Product Number (Decimal, 00=All Products) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank numbers mapped to product YYMMDDHHmm - Opening Date and Time...
Page 632
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Individual Basic Reconciliation Daily History Diagnostic Command Format: Display: <SOH>IC09TTD Computer: <SOH>iC09TTD Notes: TT - Tank Number (Decimal; 00=all) D - If 1, will use ticketed delivery else if not entered, default will use gauged delivery Typical Response Message, Display Format: <SOH>...
Page 633
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Periodic Book Variance Command Format: Display: <SOH>IC10PPtt Computer: <SOH>iC10PPtt Notes: PP - Product Number (Decimal, 00=all) tt - Report Type (if not entered will default to current) 01=current 02=previous Typical Response Message, Display Format: <SOH>...
Page 634
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C10: (Continued) Typical Response Message, Computer Format: <SOH>iC10PPYYMMDDHHmmPPnnTT...rrYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... PPnnTT...rrYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Number (Decimal, 00=all) nn - Number of tanks mapped to product (Decimal) TT - Tank Number(s) (Decimal) rr - Number of records to follow (decimal) if 0, no more data for this tank will follow YYMMDDHHmm - Opening Date and Time...
Page 635
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Weekly Book Variance Command Format: Display: <SOH>IC11PPtt Computer: <SOH>iC11PPtt Notes: PP - Product Number (Decimal, 00=all) tt - Report Type (if not entered will default to current) 01=current 02=previous Typical Response Message, Display Format: <SOH>...
Page 636
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C11 Notes: (Continued) Typical Response Message, Computer Format: <SOH>iC11PPYYMMDDHHmmPPnnTT...rrYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... PPnnTT...rrYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Number (Decimal), 00=all) nn - Number of tanks mapped to product (Decimal) TT - Tank Number(s) mapped to product (Decimal) rr - Number of records to follow...
Page 637
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Daily Book Variance Command Format: Display: <SOH>IC12PPMMDD Computer: <SOH>iC12PPMMDD Notes: PP - Product Number (Decimal, 00=all) MMDD - Month and day for report (if not entered, will default to current day) Typical Response Message, Display Format: <SOH>...
Page 638
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Book Variance Daily Report Command Format: Display: <SOH>IC15PPSyymmddYYMMDDnnn Computer: <SOH>IC15PPSyymmddYYMMDDnnn Notes: PP - Product S - Show Records by Type 0=Records and Summaries (default) 1=Records Only 2=Summaries Only yymmdd - Starting Date (000000=no starting date = first of the month) YYMMDD - Ending Date (000000=no ending date = current date)
Page 639
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C15 Notes: (Continued) Typical Response Message, Computer Format: <SOH>iC15PPYYMMDDHHmmPPnnTT...TTRRRRYYMMHHmmYYMMHHmmNNFFFFFFFF... PPnnTT...TTRRRRYYMMHHmmYYMMHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Number (Decimal, 00=All Products) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank Numbers mapped to product RRRR - Number of Records to Follow (Decimal –...
Page 640
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Periodic Variance Analysis Report Command Format: Display: <SOH>IC20PPtt Computer: <SOH>iC20PPtt Notes: PP - Product Number (Decimal, 00=all) tt - Report Type (if not entered will default to current) 01=current 02=previous Typical Response Message, Display Format:...
Page 641
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C20 Notes: (Continued) Typical Response Message, Computer Format: <SOH>iC20PPYYMMDDHHmmPPnnTTddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll NNFFFFFFFF... PPnnTTddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll NNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Number (Decimal) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank Number (Decimal, 00=all) dd - Number of reconciliation records to follow YYMMDDHHmm - Opening Date and Time for period...
Page 642
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Weekly Variance Analysis Report Command Format: Display: <SOH>IC21PPtt Computer: <SOH>iC21PPtt Notes: PP - Product Number (Decimal, 00=all) tt - Report Type (if not entered will default to current) 01=current 02=previous Typical Response Message, Display Format:...
Page 643
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C21 Notes: (Continued) Typical Response Message, Computer Format: <SOH>iC21PPYYMMDDHHmmPPnnTTddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll NNFFFFFFFF... PPnnTTddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll NNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Number (Decimal, 00=all products) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank Number (Decimal, 00=all) dd - Number of reconciliation records to follow YYMMDDHHmm - Open date and time...
Page 644
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Daily Variance Analysis Report Command Format: Display: <SOH>IC22PPMMDD Computer: <SOH>iC22PPMMDD Notes: PP - Product Number (Decimal, 00=all) MMDD - Month and day for report (if not entered, will default to current day) Typical Response Message, Display Format: <SOH>...
Page 645
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C22 Notes: (Continued) Typical Response Message, Computer Format: <SOH>iC22PPYYMMDDHHmmPPnnTTYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll NNFFFFFFFF... PPnnTTYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll NNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Number (Decimal, 00=all products) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank Number (Decimal, 00=all) YYMMDDHHmm - Open date and time YYMMDDHHmm - Close date and...
Page 646
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 5 Function Type: Periodic Variance Analysis Daily Report Command Format: Display: <SOH>IC25PPtt Computer: <SOH>iC25PPtt Notes: PP - Product Number (Decimal, 00=all Products) tt - Report Type 01=current 02=previous Typical Response Message, Display Format: <SOH>...
Page 647
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C25 Notes: (Continued) Typical Response Message, Computer Format: <SOH>iC25PPYYMMDDHHmm... PPnnTTYddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllllNNFFFFFFFF... PpnnTTYddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllllNNFFFFFFFF...&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Code (Decimal) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank Number (Decimal, 0=all) dd - Number of reconciliation records to follow YYMMDDHHmm - Opening Date and Time for period...
Page 648
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Reconciliation Daily Report Command Format: Display: <SOH>IC0GPPSyymmddYYMMDDnnn Computer: <SOH>iC0GPPSyymmddYYMMDDnnn Notes: PP - Product S - Show Records by Type 0=Records and Summaries (default) 1=Records Only 2=Summaries Only yymmdd - Starting Date (000000=no starting date = first of the month) YYMMDD - Ending Date (000000=no ending date = current date) nnn - Maximum Records [001...366] (100=default) (decimal) Typical Response Message, Display Format:...
Page 649
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code C0G Notes: (Continued) Typical Response Message, Computer Format: <SOH>iC0GPPYYMMDDHHmmPPnnTT...TTRRRRYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF... PPnnTT...TTRRRRYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Number (Decimal, 00=All Products) nn - Number of tanks that are mapped to the product (Decimal) TT - Tank Numbers mapped to product RRRR - Number of Records to Follow (Decimal) YYMMDDHHmm - Opening Date and Time...
Page 650
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Reconciliation Shift Report Command Format: Display: <SOH>IC0JPPSSyymmddYYMMDDnnn Computer: <SOH>IC0JPPSSyymmddYYMMDDnnn Notes: PP - Product S - Shift Number (00=All, Decimal) yymmdd - Starting Date (000000=no starting date = first of the month) YYMMDD - Ending Date (000000=no ending date = current date) nnn - Maximum Records [001...366] (100=default) (decimal)
Page 651
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Reconciliation Test Result Report Command Format: Display: <SOH>ICA3PPyymmddYYMMDDnnn Computer: <SOH>ICA3PPyymmddYYMMDDnnn Notes: PP - Product yymmdd - Starting Date (000000=no starting date = first of the month) YYMMDD - Ending Date (000000=no ending date = current date) nnn - Maximum Records [001...366] (100=default) (decimal) Typical Response Message, Display Format:...
Page 652
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code CA3: (Continued) Typical Response Message, Computer Format: <SOH>iCA3PPYYMMDDHHmmPPnnnnYYMMDDyymmDDssttRRvvNNFFFFFFFF... YYMMDDyymmddssttRRvvNNFFFFFFFF&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time PP - Product Number (Decimal, 00=All Products) nnnn - Number of Records to follow (Decimal) YYMMDD - End Date yymmdd - Start Date SS - Test Number (Decimal) tt - Test Type...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.6 GUI DISPLAY SETUP Function Code: Version 1 Function Type: Set Display Setup - System Status Configuration Command Format: Inquire: Display: <SOH>SG0100TTc <SOH>IG0100TT Computer: <SOH>sG0100TTc <SOH>iG0100TT Notes: TT - Tab, 00=all Tabs 01=All Tanks Tab 02=All Sensors Tab 03=’User Defined 1’...
Page 654
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – All Tanks Configuration Command Format: Inquire: Display: <SOH>SG0200FFc <SOH>IG0200FF Computer: <SOH>sG0200FFc <SOH>iG0200FF Notes: FF - Field, 00=all Fields, but only valid for Inquiry 01=Icon Shape 02=Product Label 03=Fuel Volume 04=Ullage 100%...
Page 655
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code G02 Notes: (Continued) Typical Response Message, Computer Format: <SOH>iG0200YYMMDDHHmmNNFFc...FFc&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time NN - Number of Fields To Follow FF - Field c - Configuration - If FF=01 (Icon Shape) 0=Circle 1=Rectangle - If FF=02 (Product Label)
Page 656
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – Tank Fuel Fill Configuration Command Format: Inquire: Display: <SOH>SG03TTff <SOH>IG03TT Computer: <SOH>sG03TTff <SOH>iG03TT Notes: TT - Tank Number ff - Fuel Fill Configuration (see available entries below) Typical Response Message, Display Format: <SOH>...
Page 657
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – All Liquid Sensors Configuration Command Format: Inquire: Display: <SOH>SG0400FFc <SOH>IG0400FF Computer: <SOH>sG0400FFc <SOH>iG0400FF Notes: FF - Field, 00=all Fields 01=Sensor Label 02=Alarm Condition Icon 03=Model 04=Category c - Configuration...
Page 658
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – All Type-A (2-Wire CL) Sensors Configuration Command Format: Inquire: Display: <SOH>SG0500FFc <SOH>IG0500FF Computer: <SOH>sG0500FFc <SOH>iG0500FF Notes: FF - Field, 00=all Fields 01=Sensor Label 02=Alarm Condition Icon 03=Model 04=Category c - Configuration...
Page 659
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – All Type-B (3-Wire CL) Sensors Configuration Command Format: Inquire: Display: <SOH>SG0600FFc <SOH>IG0600FF Computer: <SOH>sG0600FFc <SOH>iG0600FF Notes: FF - Field, 00=all Fields 01=Sensor Label 02=Alarm Condition Icon 03=Model 04=Category c - Configuration...
Page 660
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – All MAG Sensors Configuration Command Format: Inquire: Display: <SOH>SG0700FFc <SOH>IG0700FF Computer: <SOH>sG0700FFc <SOH>iG0700FF Notes: FF - Field, 00=all Fields 01=Sensor Label 02=Alarm Condition Icon 03=Fuel Height 04=Water Height 05=Temperature...
Page 661
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – All Ground Water Sensors Configuration Command Format: Inquire: Display: <SOH>SG0800FFc <SOH>IG0800FF Computer: <SOH>sG0800FFc <SOH>iG0800FF Notes: FF - Field, 00=all Fields 01=Sensor Label 02=Alarm Condition Icon 03=Category c - Configuration 0=Disabled...
Page 662
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – All Vapor Sensors Configuration Command Format: Inquire: Display: <SOH>SG0900FFc <SOH>IG0900FF Computer: <SOH>sG0900FFc <SOH>iG0900FF Notes: FF - Field, 00=all Fields 01=Sensor Label 02=Alarm Condition Icon 03=Category c - Configuration 0=Disabled...
Page 663
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – All Line Pressure Sensors Configuration Command Format: Inquire: Display: <SOH>SG0A00FFc <SOH>IG0A00FF Computer: <SOH>sG0A00FFc <SOH>iG0A00FF Notes: FF - Field, 00=all Fields 01=Sensor Label 02=Alarm Condition Icon 03=Pressure c - Configuration 0=Disabled...
Page 664
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – User Defined Tab Label Command Format: Inquire: Display: <SOH>SG0B00TTaaaaaaaaaaaaaaa <SOH>IG0B00TT Computer: <SOH>sG0B00TTaaaaaaaaaaaaaaa <SOH>iG0B00TT Notes: TT - User Defined Tab Number (01 – 03) a - 15 ASCII characters [20h-7Eh] Typical Response Message, Display Format: <SOH>...
Page 665
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set Display Setup – User Defined Tab Configuration Command Format: Inquire: Display: <SOH>SG0C00TTpiDDdd <SOH>IG0C00TT Computer: <SOH>sG0C00TTpiDDdd <SOH>iG0C00TT Notes: TT - User Defined Tab Number (01 – 03) p - Page Number (from 1 – 3, following the specified fill rules for User Defined Tabs) i - Index Position of Widget on Page (1 –...
Page 666
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code G0C Notes: (Continued) Typical Response Message, Computer Format: <SOH>iG0C00YYMMDDHHmmTTPpWiDDdd...iDDdd pWiDDdd...iDDdd&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - User Defined Tab Number (01 – 03) P - Number of Pages to Follow p - Page Number (from 1 –...
Page 667
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Set System Status – User Defined Tab Status Report Command Format: Display: <SOH>SG0D00TT Computer: <SOH>sG0D00TT Notes: TT - User Defined Tab Number (01 – 03) Typical Response Message, Display Format: <SOH>...
Page 668
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code G0D Notes: (Continued) Typical Response Message, Computer Format: <SOH>iG0D00TTYYMMDDHHmmPpWiDDdd...iDDdd pWiDDdd...iDDdd&&CCCC<ETX> Notes: YYMMDDHHmm - Current Date and Time TT - User Defined Tab Number (01 – 03) P - Number of Pages to Follow p - Page Number (from 1 –...
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 7.7 DEVICE VR-BUS CONFIGURATION Function Code: Version 1 Function Type: Set Device VR-BUS Address Command Format: Inquire: Display: <SOH>SN01TTDDaaaaaaaaaaaaaaaaaaaa... <SOH>IN01TTDD Computer: <SOH>sN01TTDDaaaaaaaaaaaaaaaaaaaa... <SOH>iN01TTDD Notes: TT - Device Number (Decimal) Set command 00=clear all devices Inquire command 00=read all devices DD - Device Type (Decimal) Set command valid for single device type only...
Page 670
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code N01 Notes: (Continued) Device Secondary Type Address Description ------ --------- ------------------------------------------------------------ All Device Types LIQUID_DEV_TYPE, Legacy Liquid Sensor VAPOR_DEV_TYPE, Legacy Vapor Sensor INPUT_DEV_TYPE, Power Side Input – External GRND_H2O_DEV_TYPE, 3 WIRE RESISTANCE COSENS_DEV_TYPE, 2 WIRE CURRENT LOOP RELAY_DEV_TYPE,...
Page 671
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get Available VR-BUS Addresses Command Format: Display: <SOH>IN02TTDD Computer: <SOH>iN02TTDD Notes: 1. TT - Device Number (00=all devices) 2. DD - Device Type (decimal – Must enter Device Type) Typical Response Messages, Display Format: <SOH>...
Page 672
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 1 Function Type: Get All Device Directory Command Format: Display: <SOH>IN0300 Computer: <SOH>iN0300 Typical Response Messages, Display Format: <SOH> IN0300 SEP 26, 2008 09:45 AM All Device Directory ADDRESS DEVICE TYPE ENABLED B1.S1 INPUT/OUTPUT MODULE...
Page 673
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Get Hardware Configuration Command Format: Display: <SOH>IN0400 Computer: <SOH>iN0400 Typical Response Messages, Display Format: <SOH> IN0400 SEP 26, 2008 09:45 AM HARDWARE CONFIGURATION BOARD SERIAL FIRMWARE ADDRESS MODULE TYPE PART NUMBER NUMBER BUILD DATE VERSION...
Page 674
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Get Extended Device Directory Command Format: Display: <SOH>IN0500 Computer: <SOH>iN0500 Typical Response Messages, Display Format: <SOH> IN0500 SEP 26, 2008 09:45 AM EXTENDED DEVICE DIRECTORY SERIAL DATE ADDRESS MODULE/DEVICE TYPE NUMBER CODE...
Page 675
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Get Device Assignments Command Format: Display: <SOH>IN0600 Computer: <SOH>iN0600 Typical Response Messages, Display Format: <SOH> IN0600 SEP 26, 2008 09:45 AM DEVICE ASSIGNMENTS MOD/DEV PRIMARY SECONDARY M/ER ADDRESS TYPE ASSIGNMENT ASSIGNMENT...
Page 676
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Function Code: Version 2 Function Type: Comm Diagnostics Counters Command Format: Inquire: Display: <SOH>SN07PP149 <SOH>IN07PP Computer: <SOH>sN07PP149 <SOH>iN07PP Notes: 1. The Inquiry portion of the command returns all counter information. The Set portion will reset the counters. 2.
Serial Interface Manual TLS4/TLS-450 Monitoring Systems 8.0 FUNCTION CODE SUMMARY CONTROL FUNCTIONS (7.1) Code Version Feature Function 450Plus N/A N/A Clear Power Reset Flag (obsolete) Remote Alarm Reset Cancel Autodial Computer Mode Session N/A N/A Confirm Clear Function (obsolete) N/A N/A Clear In-Tank Delivery Reports (obsolete) 5 SLD Start In-Tank Leak Detect Test...
Page 678
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus Extended Alarm Reports – Date/Time Based Extended Alarm Reports II – Date/Time Based Extended Sensor Status Report – Date/Time Based Setup Warning Detailed Information IN-TANK REPORTS (7.2.2) Code Version Feature Function 450Plus...
Page 679
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus Tank Profile In-Tank Inventory Report With 90/95% Ullage 5 BIR BIR Extended Adjusted Delivery Report In-Tank Most Recent Delivery Report with Manifolded Results In-Tank Current Siphon Manifolded Total Volumes Hourly Inventory Volume Manual Shift Inventory Snapshot Volume Tank Height Status...
Page 680
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus In-Tank Inventory History Report Extended In-Tank Inventory Report – Date/Time Based SENSOR REPORTS (7.2.3) Code Version Feature Function 450Plus Liquid Sensor Status Report Liquid Sensor Alarm History Report Vapor Sensor Status Report Vapor Sensor Alarm History Report Groundwater Sensor Status Report Groundwater Sensor Alarm History Report...
Page 681
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus 1 N/A 5 PLLD Pressure Line Leak Alarm History Report 1 N/A 5 PLLD Pressure Line Leak Test Results (0.10 test data only) 1 N/A 5 PLLD Pressure Line Leak Test History (0.10 test data only) 1 N/A 5 PLLD Pressure Line Leak Test Results (0.20 test data listed...
Page 682
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus Set Display Setup - Number Format Set Display Setup – Date & Time Format Set Inventory Maximum Number of Shifts per Day Inventory Shift Close Setup Report Delivery Setup Report 5 BIR Reconciliation Setup Report 5 BIR...
Page 683
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus 5G3 or 5H3) Set Receiver Dialing Destination Type (obsolete) Set Receiver Port Number to Dial (obsolete use 5G5, 5H5, 5I5, or 5J5) Set Receiver Retry Number (obsolete use 5G6, 5H6, 5I6, 5J6, or 5K6) Set Receiver Retry Delay Time (obsolete use 5G7, 5H7, 5I7, 5J7, or 5K7)
Page 684
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus 5 PLLD Set Days Before Line Periodic Test Needed Alarm 5 PLLD Set Line Annual Test Needed Warning 5 PLLD Set Days Before Line Annual Test Needed Warning 5 PLLD Set Days Before Line Annual Test Needed Alarm Set Ullage Set Manual Close Timeout in Minutes...
Page 685
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus Set Contact TCP/IP Retry Count Set Contact TCP/IP Retry Delay Time Set Contact Satellite Connection String Set Contact Satellite Communication Device Number Set Contact Satellite Mode Retry Count Set Contact Satellite Retry Delay Time Set Contact E-Mail Address Set Contact E-Mail Mode Retry Count Set Contact E-Mail Retry Delay Time...
Page 686
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus Set Probe Number Installed in Tank Get Tank Setup Warning Messages Set Product Label Product Setup Set Product Available in Tank Set Tank Delivery Delay 5 SLD/ Set Tank Leak Test Type & Start Time CSLD Set Tank SIPHON Manifolded Partners 5 CSLD...
Page 687
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus Set MAG Probe Float Size Create Tank Chart 5 SLD Set Tank Leak Test Notify N/A SLD Set Tank Leak Test Averaging (obsolete) 5 SLD Set Tank Test Siphon Break Set Leak Test Report Type (obsolete) 5 BIR Set Tank HRM Reconciliation Warning Limit...
Page 688
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus Set Tank Maximum Volume Limit for Tall Tank Set Tank Delivery Required Limit for Tall Tank Printout Tank Setup Tabs SENSOR SETUP (7.3.7) Code Version Feature Function 450Plus Set Liquid Sensor Configuration Set Liquid Sensor Location Label Set Liquid Sensor Type Set Liquid Sensor Category...
Page 689
Serial Interface Manual TLS4/TLS-450 Monitoring Systems PUMP SENSOR SETUP (7.3.8) Code Version Feature Function 450Plus Set Pump Sensor Configuration (obsolete use P06) Set Pump Sensor Tank Number (obsolete use P04) Set Pump Sensor Dispense Mode (obsolete use L06) Set Pump Configured Set Pump Label Set Pump Mode Set Pump Associated Tank...
Page 690
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus N/A PLLD Set Pressure Line Leak Tank Number (obsolete use P04) Set Pressure Line Leak Dispense Mode (use L06 for 5 PLLD pump sense) N/A PLLD Set Pressure Line Leak Disable Alarm Assignments (obsolete) 5 PLLD Set Pressure Line Leak Piping Material...
Page 691
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus 5 BIR Set HRM Enable Flag 5 DIM DIM Software Revision N/A DIM Set Mechanical Dispenser Interface String N/A N/A 5 DIM Set Electronic Dispenser Interface String 5 BIR Set Reconciliation Auto Daily Closing Time Set Auto Shift Closing Time 1, 2, 3, 4 5 BIR...
Page 692
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus 5 BIR Set Ticketed Delivery Information 5 BIR Set Tank Periodic Reconcilaiton Alarm Threshold Enable 5 BIR Set Tank Periodic Reconcilaition Alarm Threshold 5 BIR Set HRM Maximum Volume Limit Accuchart Operating Volume Span Accuchart 5 BIR...
Page 693
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus Set Relay Orientation Set Relay Type Set Relay Tank Assignment (obsolete use P04) N/A N/A Set External Input Type (obsolete use 80F) N/A N/A Set External Input Orientation Set External Input Tank Number (obsolete use P04) N/A N/A Set Input Type Set Probe Configuration...
Page 694
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus Set Static IP Address Set Serial Command Port Set Static Subnet Mask Set Static Gateway IP Set SSH Port Set HTTP Port Set HTTPS Port Set Host Name Set Static Primary DNS Server Set Static Secondary DNS Server Get MAC Address Set Default Gateway...
Page 695
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus 1 N/A System Revision Level Report II (obsolete) Get “About” screen information IN-TANK DIAGNOSTIC REPORTS (7.4.2) Code Version Feature Function 450Plus Probe Type and Serial Number Probe Reference Distance Diagnostic Probe Diagnostics General Probe Last Sample Buffers MAG Probe Option Table...
Page 696
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus Accuchart Application Log Accuchart Power Outage Diagnostic Report Power Outage Diagnostic Report Date/Time Based Power Outage Delivery Diagnostic Report Date/Time Based Power Reset History Report SENSOR DIAGNOSTIC REPORTS (7.4.3) Code Version Feature...
Page 697
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus 1 N/A 5 PLLD LPR Sensor Comm Data 1 N/A 5 PLLD LPR Sensor Channel Data (Hex Format) 1 N/A 5 PLLD LPR Sensor Channel Data (Decimal Format) 3 N/A 5 PLLD LPR Sensor General Report 3 N/A...
Page 698
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus 5 BIR Basic Inventory Reconciliation Daily "Row" Report 5 BIR Basic Inventory Reconciliation Daily "Column" Report 5 BIR Basic Inventory Reconciliation Shift "Row" Report 5 BIR Basic Inventory Reconciliation Shift "Column" Report 5 BIR Basic Inventory Reconciliation Periodic "Row"...
Page 699
Serial Interface Manual TLS4/TLS-450 Monitoring Systems Code Version Feature Function 450Plus 1 N/A Set Display Setup –All Vapor Sensors Configuration 1 N/A N/A PLLD Set Display Setup –All Line Pressure Sensors Configuration 1 N/A Set Display Setup – User Defined Tab Labels 1 N/A Set Display Setup –...
Need help?
Do you have a question about the TLS4 Series and is the answer not in the manual?
Questions and answers