Panasonic U-4LE1E5 Service Manual page 45

Mini vrf system
Hide thumbs Also See for U-4LE1E5:

Advertisement

1. Outdoor Unit Control PCB
Table 4-1. Setting the System Address [S002: Rotary switch (yellow), S003: 2P DIP (black)]
Outdoor system
address No.
1 refrigerant
1
system only
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Link wiring
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Table 4-2. Setting the Number of Indoor Units [S004: Rotary switch (gray)]
Number of
Indoor Units
1
2
3
9
10
11
12
13
14
15
S002 setting (system
address switch)
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
S004 Setting
1
2
3
9
A
B
C
D
E
F
4-5
Mini VRF SYSTEM
S003 setting
1P (10s digit)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
PCB Settings
2P (20s digit)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
4
ON