Wiring Diagram #1 (Suggested):
lighting in a space. Upon loss of normal power, the emergency lighting comes on at full brightness regard-
less of dimmer position.
20A
EMERGENCY
HOT
EMERGENCY
PANEL
OR
INVERTER
EMERGENCY
NEUTRAL
Wiring Diagram #2 (Shunt):
lighting in a space. Upon loss of normal power, the emergency lighting comes on at full brightness regard-
less of dimmer position.
20A
EMERGENCY
HOT
EMERGENCY
PANEL
OR
INVERTER
EMERGENCY
NEUTRAL
FREQUENTLY ASKED QUESTIONS:
Can I power more than 1 light from the EPC-2-D-FM?
It is recommended that the EPC-2-D-FM power only one fixture/luminaire. If you want to
control more than one fixture/luminaire, use the higher rated EPC-2-D.
Do I need a separate normal and emergency ballast/driver?
NO, the emergency light only needs a single ballast/driver.
Can I use the EPC-2-D-FM with 3-way dimmers?
YES
Why is my EPC-2-D-FM buzzing/humming/chattering?
This can occur with some dimmers when they do not have enough load on them. Changing
to Wiring Diagram #2 should eliminate this issue, contact LVS for further assistance.
How do I wire the EPC-2-D-FM with DALI/EcoSystem loads?
Please check this link: http://www.lvscontrols.com/assets/EPC2DDALI.pdf
4
#6 BLUE
Connect to gray
from dimmer
#5 YELLOW
GRAY
VIOLET
EMERGENCY LIGHT
#4 WHITE/BLUE
A dedicated dimmer (fed by emergency power) controls emergency
YELLOW
(CAP)
#6 BLUE
VIOLET
DIMMER
GRAY
YELLOW
GRAY
VIOLET
EMERGENCY LIGHT
#4 WHITE/BLUE
A dimmer (fed by normal power) controls emergency
VIOLET
ORANGE
YELLOW
(CAP)
#1 BLACK
EMERGENCY
POWER
#2 RED
TEST
UTILITY
POWER
#3 WHITE
Optional normally open occupancy sensor/power pack/relay panel.
VIOLET
ORANGE
#1 BLACK
EMERGENCY
POWER
#5
#2 RED
TEST
UTILITY
POWER
#3 WHITE
Connect to violet
from dimmer
NORMAL
HOT
DIMMER/ROOM
CONTROLLER
GRAY
VIOLET
NORMAL
NEUTRAL
NORMAL
HOT
(CAP OFF)
NORMAL
NEUTRAL
20A
NORMAL
(UTILITY)
PANEL
20A
NORMAL
(UTILITY)
PANEL