Operation behavior
● Input signal type
The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB.
DIP switch [SET2 SW2]
Edge
OFF (Factory setting)
Pulse
ON
● When function setting is "Operation/Stop" mode.
Input
Connector
Ch1 of CNA01 or
Edge
CNA02
Ch1
CNA01 or
Pulse
CNA02
Ch2
* The last command has priority.
* The indoor units within the same remote controller group operates in the same mode.
● When function setting is "Emergency stop" mode.
Input
Connector
Ch1 of CNA01 or
Edge
CNA02
Ch1
CNA01 or
Pulse
CNA02
Ch2
* All indoor units of same refrigerant system stops when Emergency stop operates.
● When function setting is "Forced stop" mode.
Input
Connector
Ch1 of CNA01 or
Edge
CNA02
Ch1
CNA01 or
Pulse
CNA02
Ch2
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
"Operation/Stop" mode or "Emergency stop" mode, "Forced stop" mode can be selected
with function setting of indoor unit.
● Forced thermostat off function ("Edge" input only)
*If function setting "60" is set to "00"
Input
Connector
Ch1 of CNA01 or
Edge
CNA02
(2) External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
● When indicator etc. are connected directly
Indicator 1
Indicator 2
Indicator 3
Indicator 4
Connected unit
● When connecting with unit equipped with a power supply
Connected
device 1
Connected
device 2
Connected
device 3
Connected
device 4
Connected unit
Relay (locally purchased)
En-11
Edge
Input signal type
Pulse
The width of pulse must be
longer than 200 msec.
Input signal
Command
OFF → ON
Operation
ON → OFF
Stop
OFF → ON
Operation
OFF → ON
Stop
Input signal
Command
OFF → ON
Emergency stop
ON → OFF
Normal
OFF → ON
Emergency stop
OFF → ON
Normal
Input signal
Command
OFF → ON
Forced stop
ON → OFF
Normal
OFF → ON
Forced stop
OFF → ON
Normal
Input signal
Command
OFF → ON
Thermostat off
ON → OFF
Normal
Operation behavior
* If function setting "60" is set to "00"
Connector
External output 1
Pins 1-2
External output 2
Pins 1-3
CNB01
External output 3
Pins 1-4
External output 4
Pins 1-5
● Indoor unit fan setting for external heater
Fan setting when turning ON output to the connected external heater can be set by
changing Dip switch on PC board.
Dip switch
[SET2 SW3]
OFF
(Factory setting)
ON

6.7. Remote sensor (optional parts)

For the installation method, please refer to the INSTALLATION MANUAL of remote sen-
sor.
Connection method
• Remove the existing connector and replace it with the remote sensor connector (ensure
that the correct connector is used).
• The original connector should be insulated to ensure that it does not come into contact
with other electrical circuitry.
• Use conduit hole when external output cable is used.
Setting for room temperature correction
When a remote sensor is connected, set the function setting of indoor unit as indicated
below.
• Function Number "30":
Set the Setting Number to "00". (Default)
• Function Number "31":
Set the Setting Number to "02".
* Refer to "7.4. Function setting" for details about Function Number and Setting Number

6.8. IR receiver unit (optional parts)

Connection method
• For the installation method, please refer to the INSTALLATION MANUAL of IR receiver
unit.
(1) Use 9 pins for receiver unit cable.
(2) At first, connect the receiver unit cable to the controller PCB.
(3)
Attach the core that comes between controller PCB and the clamp.
(4) Use conduit hole when external output cable is used.

6.9. Drain pump unit (optional parts)

• For the installation method, please refer to the INSTALLATION MANUAL of drain pump
unit.
P.C.B
CNB
01
P.C.B
CNB
01
Output voltage
0 V
Stop
DC 12 V
Operation
0 V
Normal
DC 12 V
Error
0 V
Indoor unit fan stop
DC 12 V
Indoor unit fan operation
0 V
External heater OFF
DC 12 V
External heater ON
Fan setting when
ON is output to the
external heater
OFF
For the fan setting details, see the
Design & Technical Manual.
ON
Status
Explanation