Toshiba MMW-UP0271LQ-E Installation Manual page 31

Hot water module (multi type)
Hide thumbs Also See for MMW-UP0271LQ-E:
Table of Contents

Advertisement

 Wiring for Flow selector unit (FS unit) for SHRM-e
Connect communication wire of FS unit to terminal A, B (no polarity) of Hot Water Module.
when the Hot water module connects to SHRM-e system.
FAN
CN083
CN041
CN100
CN101
CN102
CN030
CN103
CN104
TA
CN060
L401
RY008
RY007
RY006
RY005
CN074
CN022
IC501
C140
C150
C170
CN075
CN067
CN040
COM
S1
S2
S3
S4
S5
NOTE
In case of connecting at least one Hot Water Module in SHRM-e system, all of FS units in the system should be
Single port type FS unit (long piping model) or Multiport type FS unit.
 Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
▼Wiring diagram
Terminal block for
remote controller wiring
of hot water module
A
B
Remote controller wire
(Locally procured)
 Output signal function wiring
Connect the following output signals from the hot water module.
Terminal
Function
block No.
COM
DC12 V (COM)
S1
Defrosting output (COM-S1)
S2
Line heater output (COM-S2)
S3
-
S4
Heating thermostat ON output (COM-S4)
S5
Pump output (COM-S5)
59-EN
Power supply wire
Communication wire (FS unit)
Remote controller wire
Control wire
Terminal block
A
Remote controller unit
B
Comments
Common for connector S2 ~ S5
DC12 V
Relay coil is less than 16 mA.
DC12 V
Relay coil is less than 16 mA.
-
DC12 V
Relay coil is less than 16 mA.
DC12 V
Relay coil is less than 16 mA.
COM
S1
Hot water module
S2
output signal
function terminal
S3
block (CN60)
S4
S5
NOTE
Auxiliary relays (locally procured) must be connected to output signal function wirings to allow connection to the
hot water module output signal functions. The maximum current output signal, from each of the output signal
function wirings, is 16 mA. Please ensure the rated current of the relay coil is less than 16 mA to avoid damage to
the hot water module P.C. board.
▼Output function wire
CAUTION
Output signal functions are separated from primary basic insulation.
• To prevent noise trouble, use 2-core shield wire.
• Determine the wire length between the hot water module output signal function terminal block and the relay up
to 2 m.
• Locally procure and install protective devices such as the heater and pump.
– 30 –
Relay
Output function wire
External
actuator
Locally procured
60-EN