Reliable DD56-6 Bulletin

Reliable DD56-6 Bulletin

Specific application sprinklers for attic spaces
Hide thumbs Also See for DD56-6:

Advertisement

Quick Links

Features
Coverage for DD80 spans up to 70 ft (21 m) with one row
of sprinklers
Coverage for DD80 spans up to 100 ft (30.5 m) with three
rows of sprinklers
All models use a 212°F (100°C) temperature rated fusible-
link operating element
150 square foot per sprinkler protection using GP56 and
AH Series sprinklers
Product Description
Reliable Attic Sprinklers are cULus Listed Specific Application
sprinklers. The sprinklers are available for protection of
combustible and non-combustible light hazard concealed
spaces with roof/ceiling slopes of 4:12 to 8:12. Reliable
Attic Sprinklers are upright sprinklers listed for use on
wet-pipe or dry-pipe sprinkler systems. All Reliable Attic
sprinklers use a 212°F (100°C) temperature rated fusible-
link operating element that is Listed for installation where the
maximum ceiling temperature is up to 150°F (66°C). Table A
provides a summary of available Reliable Attic sprinklers.
Application
Reliable Attic Sprinklers are listed for installation in
accordance with this bulletin and NFPA 13, "Standard for the
Installation of Fire Sprinklers." The sprinklers are classified
as Special Sprinklers by NFPA 13, and are intended for
installation within combustible or noncombustible roof
structures, including those with wooden trusses. Coverage
area, spacing requirements, and design flow and pressure
for each sprinkler are provided in tables B-I on the individual
sprinkler data sheets in this bulletin. Example sprinkler
layouts and hydraulic design criteria are provided in Figures
9 through 25. Please note that the example sprinkler layouts
are intended as design aids only, and do not necessarily
Attic Sprinkler Summary
Sprinkler
K-Factor
Model
gpm/psi
1/2
(L/min/bar
1/2
DD56-6
5.6 (80)
DD56-27
5.6 (80)
DD80-6
8.0 (115)
DD80-27
8.0 (115)
DS56
5.6 (80)
GP56
5.6 (80)
AH42
4.2 (60)
AH56
5.6 (80)
Thread Size
Max. Coverage Area
NPT or
(Measured on Floor)
ISO7-1
ft x ft (m x m)
)
½
6 x 40 (1.8 x 12)
½
6 x 40 (1.8 x 12)
6 x 66 or 5 x 70
¾
(1.8 x 20 or 1.5 x 21)
6 x 66 or 5 x 70
¾
(1.8 x 20 or 1.5 x 21)
½
6 x 40 (1.8 x 12)
½
10 x 15 (3.0 x 4.6)
½
10 x 15 (3.0 x 4.6)
½
10 x 15 (3.0 x 4.6)
www.reliablesprinkler.com
Models DD56-6, DD56-27, DD80-6, DD80-27,
DS56, GP56, AH42, & AH56 Sprinklers
Specific Application Sprinklers for Attic Spaces
Model DD56
(Model DD80 similar)
Model GP56
reflect all possible construction methods. In some cases,
a combination of layouts may be required. The Authority
Having Jurisdiction should be consulted for situations
that are not specifically addressed within this bulletin.
Special Note Regarding Insulation
Noncombustible insulation, properly secured with wire
netting to prevent sagging onto sprinklers may be used at
the roof deck. Attic sprinklers have not been evaluated and
are not listed for use with spray foam insulation. Use of attic
sprinklers with spray foam insulation should be evaluated on
a case by case basis with the Authority Having Jurisdiction.
Roof Slope
Design Criteria
4:12 to <6:12
6:12 to 8:12
4:12 to <6:12
6:12 to 8:12
4:12 to 8:12
4:12 to 8:12
4:12 to 8:12
4:12 to 8:12
Bulletin 056 February 2020
cULus Listed
Model DS56
Model AH56
(Model AH42 similar)
Table A
Sprinkler
Identification
Number (SIN)
Table B
RA5624
Table C
RA5694
Table D
RA5622
Table E
RA5692
Table F
RA5625
Table G
RA5695
Table H
RA5623
Table I
RA5626

Advertisement

loading
Need help?

Need help?

Do you have a question about the DD56-6 and is the answer not in the manual?

Questions and answers

Summary of Contents for Reliable DD56-6

  • Page 1 The sprinklers are available for protection of combustible and non-combustible light hazard concealed spaces with roof/ceiling slopes of 4:12 to 8:12. Reliable Attic Sprinklers are upright sprinklers listed for use on wet-pipe or dry-pipe sprinkler systems. All Reliable Attic sprinklers use a 212°F (100°C) temperature rated fusible-...
  • Page 2 Load Screw: Bronze Alloy Wet-pipe with steel or Listed CPVC pipe Deflector: Bronze Alloy Dry-pipe with steel pipe Model DD56-6 Sprinkler Components and Dimensions Figure 1 Model DD56-6 Minimum Required Flow and Residual Pressure Table B Max. Coverage Area Flow Pressure Ceiling Slope...
  • Page 3 Model DD56-27 Specific Application Sprinkler SIN RA5694 Technical Specifications Installation Criteria Style: Upright Sprinkler Spacing Orientation: Deflector horizontal Minimum 4 ft (1.2 m), maximum 6 ft (1.8m) Threads: 1/2” NPT or ISO 7-1R1/2 between sprinklers along ridge Nominal K-Factor: 5.6 (80 metric) Minimum 26 ft (7.9 m) down the roof slope Max.
  • Page 4 Model DD80-6 Specific Application Sprinkler SIN RA5622 Technical Specifications Installation Criteria Style: Upright Sprinkler Spacing Orientation: Deflector horizontal Minimum 4 ft (1.2 m), maximum 6 ft (1.8m) Threads: 3/4” NPT or ISO 7-1R3/4 between sprinklers along ridge Nominal K-Factor: 8.0 (115 metric) Minimum 26 ft (7.9 m) down the roof slope Max.
  • Page 5 Model DD80-27 Specific Application Sprinkler SIN RA5692 Technical Specifications Installation Criteria Style: Upright Sprinkler Spacing Orientation: Deflector horizontal Minimum 4 ft (1.2 m), maximum 6 ft (1.8m) Threads: 3/4” NPT or ISO 7-1R3/4 between sprinklers along ridge Nominal K-Factor: 8.0 (115 metric) Minimum 26 ft (7.9 m) down the roof slope Max.
  • Page 6 Model DS56 Specific Application Sprinkler SIN RA5625 Technical Specifications Installation Criteria Style: Upright Sprinkler Spacing Orientation: Frame arms Minimum 4 ft (1.2 m), maximum 6 ft (1.8m) perpendicular to roof deck between sprinklers along ridge Threads: 1/2” NPT or ISO 7-1R1/2 Minimum 26 ft (7.9 m) down the roof slope Nominal K-Factor: 5.6 (80 metric) toward eave to nearest sprinkler,...
  • Page 7 Model GP56 Specific Application Sprinkler SIN RA5695 Technical Specifications Installation Criteria Style: Upright Sprinkler Spacing Orientation: Top of deflector parallel to roof deck Minimum 6 ft (1.8 m), maximum 10 ft (3.0 m) Threads: 1/2” NPT or ISO 7-1R1/2 between sprinklers across roof slope. Nominal K-Factor: 5.6 (80 metric) Minimum 6 ft (1.8 m) up roof slope to Max.
  • Page 8 Model AH42 Specific Application Sprinkler SIN RA5623 Technical Specifications Installation Criteria Style: Upright Sprinkler Spacing Orientation: Top of deflector parallel to roof deck Minimum 5 ft (1.5 m), maximum 10 ft (3.0 m) Threads: 1/2” NPT or ISO 7-1R1/2 between sprinklers across roof slope. Nominal K-Factor: 4.2 (60 metric) Minimum 12 ft (3.7 m) down slope to nearest Max.
  • Page 9 Model AH56 Specific Application Sprinkler SIN RA5626 Technical Specifications Installation Criteria Style: Upright Sprinkler Spacing Orientation: Top of deflector parallel to roof deck Minimum 6 ft (1.8 m), maximum 10 ft (3.0 m) Threads: 1/2” NPT or ISO 7-1R1/2 between sprinklers across roof slope. Nominal K-Factor: 5.6 (80 metric) Minimum 12 ft (3.7 m) down slope to nearest Max.
  • Page 10 Model DD Series Sprinkler – Example Layout (Not to Scale) Figure 9 Model DS56 Sprinkler – Example Layout (Not to Scale) Figure 10 Bulletin 056 Page 10 of 27 February 2020 www.reliablesprinkler.com...
  • Page 11 Model DD Series Sprinklers at Ridge with Model DS56 Sprinklers Beyond Obstruction Figure 11 Example Layout (Not to Scale) Model DS56 Sprinklers at Ridge with Model DS56 Sprinklers Beyond Obstruction Figure 12 Example Layout (Not to Scale) Bulletin 056 Page 11 of 27 February 2020 www.reliablesprinkler.com...
  • Page 12 Model DD Series Sprinklers at Ridge with Model GP56 or AH Series Sprinklers Beyond Obstruction Figure 13 Example Layout (Not to Scale) Model DS56 Sprinklers at Ridge with Model GP56 or AH Series Sprinklers Beyond Obstruction Figure 14 Example Layout (Not to Scale) Bulletin 056 Page 12 of 27 February 2020...
  • Page 13 Model DD Series Sprinklers at Ridge with Model GP56 or AH Series Sprinklers in Dormers Figure 15 Example Layout (Not to Scale) Bulletin 056 Page 13 of 27 February 2020 www.reliablesprinkler.com...
  • Page 14 Model DD Series Sprinklers at Ridge with Standard Spray Sprinklers at Dormer or Cross Figure 16 Example Layout (Not to Scale) Bulletin 056 Page 14 of 27 February 2020 www.reliablesprinkler.com...
  • Page 15 Model DD Series Sprinklers at Ridge with Model DD Series Sprinklers in Dormers Figure 17 Example Layout (Not to Scale) Model DD Series Sprinklers at Ridge with Model GP56 or AH Series Sprinklers at Eave Figure 18 Example Layout (Not to Scale) Note: if necessary, a baffle may be added between the Model DD sprinklers and the...
  • Page 16 Model DS56 Sprinklers at Ridge with Model GP56 or AH Series Sprinklers at Eave Figure 19 Example Layout (Not to Scale) Note: if necessary, a baffle may be added between the Model DS sprinklers and the Model GP56 or AH Series sprinklers to prevent cold solder.
  • Page 17 Model DS56 Sprinklers at Ridge with DS56 Sprinklers at Hip or Ell Figure 21 Example Layout (Not to Scale) Model DD Series Sprinklers at Ridge with Standard Spray Sprinklers at Hip or Ell Figure 22 Example Layout (Not to Scale) Bulletin 056 Page 17 of 27 February 2020...
  • Page 18 Model DS56 Sprinklers at Ridge with Standard Spray Sprinklers at Hip or Ell Figure 23 Example Layout (Not to Scale) Bulletin 056 Page 18 of 27 February 2020 www.reliablesprinkler.com...
  • Page 19 Model DD Series Sprinklers at Ridge and Model AH Sprinklers at Hip and Ell Figure 24 Example Layout (Not to Scale) Bulletin 056 Page 19 of 27 February 2020 www.reliablesprinkler.com...
  • Page 20 Model DS56 Sprinklers at Ridge and Model AH Sprinklers at Hip and Ell Figure 25 Example Layout (Not to Scale) Bulletin 056 Page 20 of 27 February 2020 www.reliablesprinkler.com...
  • Page 21 Model AH Series Sprinklers at Ridge and DS56 Sprinklers in Attic (Plan View) Figure 26 Model AH Series Sprinklers at Ridge and DS56 Sprinklers in Attic (Cross Section) Figure 26A Bulletin 056 Page 21 of 27 February 2020 www.reliablesprinkler.com...
  • Page 22 Obstruction Criteria Figure 27 Additional sprinklers not required due to obstruction 6” (150 mm) or less Additional sprinklers required beyond obstruction greater than 6” (150 in height with a minimum 3-1/2” (90 mm) gap provided between the top of mm) in height or where a minimum 3-1/2” (90 mm) gap is not provided the obstruction and the roof deck between the top of the obstruction and the roof deck.
  • Page 23 Obstruction Criteria (cont.) Figure 28 Note: Reliable Attic sprinklers may be installed directly on pipe up to 2-1/2” NPS. For 3” NPS and larger pipe, the obstruction rules for Extended Coverage Upright Spray Sprinklers shall be followed. Bulletin 056 Page 23 of 27 February 2020 www.reliablesprinkler.com...
  • Page 24: Installation Orientation

    Installation Install Reliable Attic Sprinklers only in the orientation indicated in Figure 28. Figure 29 provides additional select installation criteria for each sprinkler model. Installation Orientation Figure 29 Figure 30 Installation Dimensions Model DD Series Model DD Series Install Model DD Series sprinklers with the deflector parallel to the floor and arrows on deflector pointing down the roof slope in both directions.
  • Page 25 Note: Where Reliable Attic Sprinklers are installed on wet-pipe sprinkler systems with CPVC pipe, the CPVC pipe must be protected in accordance with the pipe manufacturer’s installation instruction as well as the requirements in Figure 30. Installation Requirements for Use of Reliable Attic Sprinklers with Listed CPVC Pipe Figure 31 Maintain at least 18”...
  • Page 26 Installation Requirements for Use of Reliable Attic Sprinklers with LIsted CPVC Pipe Figure 32 Branch lines between joists must be protected with a minimum Branch lines between joists must be protected with a minimum 6” (150 mm) thickness of noncombustible insulation (e.g., 6”...
  • Page 27: Maintenance

    Authorities Having Jurisdiction. used to install Model DS56 sprinklers. The use of any other wrench to install Reliable Attic sprinklers is not permitted and Prior to installation, sprinklers should remain in the original may damage the sprinkler. Place the specified wrench over cartons and packaging until used.