☆ Setting acceleration/deceleration time (,) in conformance with mean load allows optimum
setting that conforms to further changes in load.
☆ Use this parameter after actually connecting the motor.
☆ When the inverter is used with a load that fluctuates considerably, it may fail to adjust the acceleration or
deceleration time in time, and therefore may be tripped.
☆ Do not use = when using a brake module (optional).
[Methods of setting automatic acceleration/deceleration]
Operation panel
5
☆ Assigning the forced detection command (function number 122, 123) to any logic input terminal, it can be
changed automatic detection on a mandatory.
5.3.2
Set acceleration time from 0.0 (Hz) operation frequency to maximum frequency and deceleration time as
the time when operation frequency goes from maximum frequency to 0.0 (Hz).
Output frequency (Hz)
[Parameter setting]
Note: When the acceleration/deceleration time is set to 0.0 seconds, the inverter accelerates and decelerates
LED display
action
MODE
Manually setting acceleration/deceleration time
O
Title
Function
Acceleration time 1
Deceleration time 1
0.05 seconds.
Displays the operation frequency.
(When standard monitor display selection is set to
[Operation frequency])
The first basic parameter "" (history function) is displayed.
Turn the setting dial to the right to change the parameter to .
Parameter values can be read by pressing the center of the setting
dial.
Turn the setting dial to the right to change the parameter to or .
Press the center of the setting dial to save the changed parameter.
and the parameter are displayed alternately.
Time [sec]
Adjustment range
0.0-3000 s
0.0-3000 s
E-6
E6582233
Operation
(Manual)
Default setting
10.0
10.0