INSTALLATION AND MAINTENANCE INSTRUCTIONS
D4120A Duct Smoke Detector
D4SA Sensor Component
D4P120A Power Board Component
NOTE: The D4120A duct detector consists of D4P120A Power Board component and the D4SA Sensor component.
SPECIFICATIONS
Operating Temperature:
Storage Temperature:
Humidity:
Air Velocity:
D4120A Footprint Dimensions:
D4SA/D4P120A Footprint Dimensions: 7.75 in L x 5 in W x 2.5 in D (19.7cm L x 12.7cm W x 6.35cm D)
D4120A Weight:
Electrical
Power supply voltage:
Input capacitance:
Reset Voltage:
Reset Time (with RTS451):
Reset Time (by power down):
Power Up Time:
Alarm response time:
Sensitivity Test:
Current Requirements (Using No Accessories)
Standby current
Alarm current
CONTACT RATINGS
Alarm initiation contacts
(SPST)
Alarm auxiliary contatcs
(DPDT)
NOTE: Alarm auxiliary contacts shall not be connected to initiating
circuits of control panels. Use the alarm initiation contact for this
purpose.
Supervisory Contacts
(SPDT)
TABLE OF CONTENTS
[1] Limitations of Duct Smoke Detectors
[2] Exploded View of Duct Smoke Detector Components
[3] General Description
[4] Contents of Duct Smoke Detector Kit
[5] Detector Installation
[6] Sampling Tube Installation
[7] Measurement Tests
[8] Field Wiring Installation Guidelines
[9] Unit Configuration
[10] Detector Status Indication
[11] Interconnection (Multiple Fan Shut Down)
[12] Verification of Operation
[13] Detector Cleaning Procedures
[14] Sensor replacement
[15] Optional Accessories
Wiring Diagrams
Warranty
BEFORE INSTALLING
Read the System Sensor Guide for Proper Use of Smoke Detectors in Duct
Applications (HVAG53), which provides information on detector spacing,
placement, zoning, wiring, and special applications. This manual is available
online at www.systemsensor.ca. CAN/ULC S524 should also be referenced
for detailed information.
NOTICE: This manual shall be left with the owner/user of this equipment.
D4120A & D4SA: –4° to 158° F (–20° to 70° C) D4P120A: –40° to 158° F (–40° to 70° C)
D4120A & D4SA: –22° to 158° F (–30° to 70° C) D4P120A: –40° to 158° F (–40° to 70° C)
0% to 95% Relative Humidity Non-condensing
100 to 4000 ft./min. (0.5 to 20.3 m/sec.)
Rectangular - 14.38 in L x 5 in W x 2.5 in D (37cm L x 12.7cm W x 6.36cm D)
Square - 7.75 in L x 9 in W x 2.5 in D (19.7cm L x 22.9cm W x 6.35cm D)
2.5 pounds; 1.14 kg
20-29 VDC
270 µF max.
3.0 VDC min.
.03 to 0.3 sec.
0.6 sec. max.
35 sec. max.
15 sec.
See detector label
21 mA @ 24 VDC
65 mA @ 24 VDC
2.0A @ 30 VDC (resistive)
10A @30 VDC (resistive)
10A @250 VAC (resistive)
1
/
HP @240 VAC
2
1
/
HP @120 VAC
4
2.0A @ 30 VDC (resistive)
2.0A @ 125 VAC (resistive)
24 VAC 50-60-Hz
270 µF max.
2.0 VAC min.
.03 to 0.3 sec.
0.6 sec. max.
35 sec. max.
15 sec.
See detector label
65 mA RMS @ 24VAC 60Hz
135 mA RMS @ 24 VAC 60 Hz
ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE
MHRA/MHWA
RA400ZA
RTS451
RTS451KEYA
NOTE: Any combination of accessories may be used such that the given
accessory loads are: 110mA or less at the Aux output, and 50mA or less at
the Alarm output.
PAGE
IMPORTANT: This detector must be tested and maintained regularly follow-
1
ing CAN/ULC S536 requirements. The detector should be cleaned at least
2
once a year.
2
[1] LIMITATIONS OF DUCT SMOKE DETECTORS
2
2
3
The National Fire Protection Association has established that DUCT DETEC-
3
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DE-
4
TECTOR PROTECTION as a means of providing life safety. Nor are they a
5
substitute for early warning in a building's regular fire detection system.
6
6
System Sensor supports this position and strongly recommends that the user
6
read NFPA Standards 90A, 72, 101and CAN/ULC S524. The D4120A Air
7
Duct Smoke Detectors are listed per ULC.
7
This device will not operate without electrical power. Fire situations may
7
cause an interruption of power. The system safeguards should be discussed
5-7
with your local fire protection specialist.
8
This device will not sense smoke unless the ventilation system is operating
and the cover is installed.
For this detector to function properly, it MUST be installed according to the in-
structions in this manual. Furthermore, the detector MUST be operated within
ALL electrical and environmental specifications listed in this manual. Failure
to comply with these requirements may prevent the detector from activating
when smoke is present in the air duct.
1
3333 Unity Drive, Mississauga, ON L5L 3S6
1-800-SENSOR2, FAX: 905-812-0771
www.systemsensor.ca
120 VAC 50-60 Hz
N/A
10 VAC min.
.03 to 0.3 sec.
0.6 sec. max.
35 sec. max.
15 sec.
See detector label
20 mA RMS @ 120 VAC 60 Hz
35 mA RMS @ 120 VAC 60 Hz
STANDBY
TROUBLE
0mA
n/a
0mA
n/a
0mA
n/a
12mA
n/a
WARNING
ALARM
29mA Max.
12mA Max.
12mA Max.
12mA Max.
I56-3102-003
7/8/2019
Need help?
Do you have a question about the Innovair flex D4120A and is the answer not in the manual?
Questions and answers