Restoring Factory Default Settings Using The Recommended Initialization; Restoring Factory Default Settings Using Manual Initialization - Danfoss VLT FC 103 Operating

110-800 kw, d9h-d10h and e5h-e6h enclosed drives
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

VLT® Refrigeration Drive FC 103
Operating Guide
-
- To download data from the LCP to the control card, select [2] All from LCP.
4.
Press [OK].
A progress bar shows the uploading or downloading process.
5.
Press [Hand On] or [Auto On].

7.5.3 Restoring Factory Default Settings Using the Recommended Initialization

LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
-
To create a back-up, upload data to the LCP before initialization. See
1.
Press [Main Menu] twice to access parameters.
2.
Go to parameter 14-22 Operation Mode and press [OK].
Parameter 14-22 Operation Mode does not reset the following settings:
Running hours.
Serial communication options.
Personal menu settings.
Fault log, alarm log, and other monitoring functions.
3.
Scroll to Initialization and press [OK].
4.
Remove power to the unit and wait for the display to turn off.
5.
Apply power to the unit. Default parameter settings are restored during start-up. Start-up takes slightly longer than normal.
6.
After alarm 80, Drive initialized appears, press [Reset].

7.5.4 Restoring Factory Default Settings Using Manual Initialization

LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
-
To create a back-up, upload data to the LCP before initialization. See
Procedure
1.
Remove power to the unit and wait for the display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] simultaneously while applying power to the unit (approximately 5 s or until
an audible click sounds and the fan starts).
Manually initializing does not reset the following parameter settings:
Parameter 15-00 Operating Hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Start-up takes slightly longer than normal.
Danfoss A/S © 2020.09
N O T I C E
7.5.2 Uploading and Downloading Parameter
N O T I C E
7.5.2 Uploading and Downloading Parameter
Commissioning
AQ357954340588en-000201 / 130R0881 | 103
Settings.
Settings.