Product Feature; Specification; Power Supply Coefficient, Power Consumption Coefficient, And L Coefficient; Appearance - Mitsubishi Electric PAC-SF46EPA-G Installation Manual

Air-conditioner network system transmission booster
Table of Contents

Advertisement

If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.

2 Product Feature

2-1. Specification

Source power requirement
Voltage/current of output on the
Transmission Booster side
Environmental condition
Dimensions
Weight
Installation Environment
Sound Pressure Level

2-2. Power supply coefficient, power consumption coefficient, and L coefficient

Power supply
coefficient
TB2
0
TB3
25

2-3. Appearance

TB1
Power line terminal
4
Rated input
EU: ~220 V - 240 V ; 0.7 A / 50 Hz Single-phase
voltage and current
US: ~208 V - 230 V ; 0.7 A / 60 Hz Single-phase
Fuse: 2.0 A Time-delay type (IEC127-2 S.S.5)
DC28 V - 30 V 1.7 A (Maximum loading)
Temperature
Operating range 0 - 40 °C / 32 - 104 °F
Storage range
Humidity
30 - 90 %RH (No condensation)
340 (H) × 360 (W) × 59.2 (D) mm / 13 7/16 (H) × 14 3/16 (W) × 2 3/8 (D) in
3.4 kg / 7 1/2 lb
In the metal control panel box (indoor)
* This unit is installed and used in a business office or equivalent environment.
The A-weighted sound pressure level is below 70 dB.
Power consumption
L coefficient
coefficient
0
0
Cable fixture
CAUTION
This appliance is intended to be used by expert or trained
users in shops, in light industry and on farms, or for
commercial use by lay persons.
-20 - 60 °C / -4 - 140 °F
0
0
360 (14 3/16)
240 (9 1/2)
UP
59.2 (2 3/8)
TB3
M-NET Transmission
terminal block 2
TB2
M-NET Transmission
terminal block 1
Cable fixture
Unit: mm (in)