PRE-COMMISSIONING
AC Smart / ACP Controller Setup
1. Under the AC Smart / ACP "Settings" tab, find and click on "Installing".
2. Press on the "AC Smart[00]" tab, go to "Registration Status", and change the CH1 set-
ting to "MODBUS_9600". For ACP: Press on the "ACP [00]" tab and change the CH6
setting to "MODBUS_9600".
3. Click "Auto Search" to find the devices connected to the controller.
4. After the search is complete, click "Send All".
5. Units can be added by clicking "Add Unit", and then clicking on the buttons next to the
name(s) of the applicable devices. After all necessary units are selected, click "Apply".
6. Click "Send All" to finish adding the device(s).
Figure 48: Clicking "Auto Search" (Step 3).
Figure 50: Adding Units (Step 5).
52
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 46: Clicking "Installing" Under the AC
Smart / ACP "Settings" Tab (Step 1).
Figure 47: Changing CH1 Setting to "MOD-
BUS_9600" (Step 2).
Figure 49: Clicking "Send All" (Step 4).
Figure 51: Clicking "Send All" to Finish Adding Devices (Step 6).