Configuration Data Sequencer Loop - Siemens 353 User Manual

Process automation controller
Hide thumbs Also See for 353:
Table of Contents

Advertisement

Data Mapping

6.3.12 Configuration Data Sequencer Loop

The Modbus registers on this page refer to configuration parameters of function blocks within a specific loop
previously defined by Modbus parameter MSLCP (40048). For example, to read or write the Step 1 Group 0 Input
Mask for the PRSEQ block that is in a loop with a Modbus Index of 3, write a 3 to 40048, then read or write to
register 410001.
Sequencer (MASK Configurations)
`R/W
Code
Description
S001G0I
R/W
Step 1 Group 0 Input Mask
S001G0O
R/W
Step 1 Group 0 Output Mask
S001G1I
R/W
Step 1 Group 1 Input Mask
S001G1O
R/W
Step 1 Group 1 Output Mask
S001G2I
R/W
Step 1 Group 2 Input Mask
S001G2O
R/W
Step 1 Group 2 Output Mask
S001G3I
R/W
Step 1 Group 3 Input Mask
S001G3O
R/W
Step 1 Group 3 Output Mask
.........................................................................................................................................................................................
S250GEI
R/W
Step 250 Group E Input Mask
S250GEO
R/W
Step 250 Group E Output Mask
S250GFI
R/W
Step 250 Group F Input Mask
S250GFO
R/W
Step 250 Group F Output Mask
Real TimeTrip Block Configurations
Code
R/W
Description
RTT01Y
R/W
Year
RTT01M
R/W
Month
RTT01D
R/W
Day
RTT01HR
R/W
Hour
RTT01MN
R/W
Minute
RTT01SC
R/W
Second
RTT01DA
R/W
Day
RTT02Y
R/W
Year
RTT02M
R/W
Month
RTT02D
R/W
Day
RTT02HR
R/W
Hour
RTT02MN
R/W
Minute
RTT02SC
R/W
Second
RTT02DA
R/W
Day
RTT03Y
R/W
Year
RTT03M
R/W
Month
RTT03D
R/W
Day
RTT03HR
R/W
Hour
RTT03MN
R/W
Minute
RTT03SC
R/W
Second
RTT03DA
R/W
Day
6-26
Range
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
Range
1999-
1-12
1-31
0-23
0-59
0-59
0000 0000 0SMT WTFS
1999-
1-12
1-31
0-23
0-59
0-59
0000 0000 0SMT WTFS
1999-
1-12
1-31
0-23
0-59
0-59
0000 0000 0SMT WTFS
Register (MB)
410001
410002
410003
410004
410005
410006
410007
410008
417997
417998
417999
418000
Register (MB)
419001
419002
419003
419004
419005
419006
419007
419008
419009
419010
419011
419012
419013
419014
419015
419016
419017
419018
419019
419020
419021
UM353-1B
April 2012

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents